background image

 

ADEMCO 5819

 

SHOCK PROCESSOR TRANSMITTER 

INSTALLATION AND SETUP GUIDE

 

 

+

B

A

TTER

Y

REED
SWITCH
(LOOP 2)

COVER PRY-0FF POINT

ALIGN MAGNET
WITH MARKS ON
CASE AND GUIDE
ON MTG. PLATE

MAGNET 

(OBTAIN 

SEPARATELY)

LOOP 1 TERMINALS

(See Detail “B”)

LOCKING TAB

RELEASE WINDOW

COVER HOLDING

HOOKS (2)

COVER
TAMPER
SWITCH

MOUNTING

HOLE

ANTENNA

DIP SWITCHES
See Detail “A”

DIP
SWITCHES

JUMPER PINS
See Detail “B”

SLOT FOR
CONCEALED

WIRING ACCESS

MA

GNET

Diagram 2: 5819 (SHOWN WITH COVER REMOVED)

1/2"

MAX

1

2

3

4

5

ON

TB2

TB1

MAGNETIC
ALIGNMENT
GUIDE
STRIP

RELEASE 
FOR
BRACKET

CASE

HOLDING

POSTS

(2)

SLOT 
FOR 
WIRE

SCREW
HOLES

Diagram 1:  MOUNTING PLATE

TABLE 1

SWITCH

RESPONSE TIME

SW1   (Most Sensitive)

1ms

SW2

2ms

SW3

5ms

SW4

10ms

SW5   (Least Sensitive)

20ms

JUMPER
PINS

SHOCK SENSOR
TERMINALS
(INPUT LOOP 1)

TABLE 2

JUMPER

COUNT

J1       

(Most Sensitive)

1

J2

2

J3

4

J4

6

J5       

(Least Sensitive)

8

J5 J4 J3 J2 J1

DETAIL B

DETAIL A

CONTACT
TERMINALS
(INPUT LOOP 3)

LOOP 3 TERMINALS

(See Detail “B”)

5819 -001-V1

MOUNTING HOLE

 

 

GENERAL INFORMATION 

The ADEMCO 5819 Shock Processor Transmitter connects to 
inertia type shock detectors that are mounted externally to the 
transmitter case (detector not supplied), and is intended for use 
only with a wireless alarm system that supports 5800 Series 
wireless receivers. 

The 5819 has three unique zones.  The first is for a wired, 
normally closed shock sensor loop (TB1), the second is for a 
closed contact loop using the unit's built-in magnetic reed switch 
in conjunction with a magnet, and the third is for a wired closed 
circuit contact loop (TB2).   

The 5819 has a built-in cover tamper switch that activates when 
the cover is removed. 

INSTALLATION 

Mounting 

For proper orientation of the unit in relation to the mounting plate, 
loop wiring, DIP switch adjustment, jumper positions, and/or 
magnet, read all of this section before installing the unit. 

!

 

Do not mount the transmitter on or near metal 
objects, as this may affect transmission range. It is 
also good practice to avoid locating the transmitter 
near wiring such as AC, telephone, HVAC, 
computer data cables, etc.

 

The description that follows assumes that the unit will be 
mounted as shown in the diagrams, with the magnet (if used) 
located to the left of the unit.  The unit can be installed in any 
direction, as long as the relationship of the unit to its mounting 
plate and (if used) magnet is maintained. 

Although two mounting holes are provided in the unit that would 
permit mounting directly to a surface, it is recommended that the 
mounting plate be used as described in this document, for ease 
in removing the unit for servicing should it become necessary. 

Before mounting the transmitter permanently, conduct Go/No Go 
tests (see control's instructions) to verify adequate signal strength 
and reorient or relocate the transmitter if necessary. 

1. 

Remove transmitter's cover by inserting the flat blade of a 
small screwdriver into the pry-off slot nearest to the cover's 
decorative ribs, and twisting the blade. 

!

Do not remove the printed circuit board from its 
plastic case!

 

2.   Disengage the supplied mounting plate from the unit by 

inserting the blade of a small screwdriver into the locking tab 
release window (see Diagram 2) and pressing it against the 
locking tab  (see Diagram 1) while sliding the plate 
downward along the case back. 

3. 

If a shock processor or wired contact loop is to be used with 
concealed wiring, feed the wires through the concealed 
wiring entry hole at one corner of the plate. For surface 
wiring entry, a thin "breakout" area is provided in the case 
wall. 

4.  Install the mounting plate, with its case-holding posts 

pointing up (in this example), in the location selected. 

5. 

Attach the case back to the mounting plate by sliding the 
keyhole slots in the case back down onto the mounting 
plate's case-holding posts.  The locking tab will click as the 
case back locks in place. 

6. 

If the unit's REED SWITCH is to be used, mount a 5799 
Magnet (obtained separately) adjacent to the alignment 
marks on the case and the mounting plate's alignment strip 
(see Diagram 2). 

7. 

Set response time (from Table 1) using the DIP switches. 
SW1 sets a response time of 1mS. SW5 sets a response 
time of 20mS.  For a response time of 0.5mS, set all DIP 
switches to OFF (as shown in DETAIL A in Diagram 1 
above).   

8. 

Set the pulse count jumper (see Table 2).  The pulse count 
is reset 3-seconds after the first pulse is detected. There is 
an LED on the PCB that flashes rapidly on transmission. 

Note:  Make the device highly sensitive for the purpose 
of enrolling the shock sensor loop (TB1) into the system 
(turn SW1 on and put jumper on J1).  After the device 
has been enrolled, adjust settings as described in steps 
7 and 8 (above). 

Reviews: