K3590-2CF   9/08  Rev. B  

 

 

ADEMCO 6160CR

ADEMCO 6160CR

ADEMCO 6160CR

ADEMCO 6160CR----2222

Commercial Alpha Keypad

Commercial Alpha Keypad

Commercial Alpha Keypad

Commercial Alpha Keypad

INSTALLATION AND SETUP GUIDE 

Keypad Features 

 

Programmable function keys 

 

Built-in sounder 

 

ARMED, READY, POWER, FIRE ALARM, SILENCED, 
SUPERVISORY, TROUBLE LEDs  (see note 1) 

 

RED keypad for Commercial Fire applications

 

 

Supervised by control panel (required for Commercial Fire 
installations) 

 

 

Supported Control Panels 

 

VISTA-32FB (see note 2) 

 

VISTA-128FBP (see note 2) 

 

VISTA-250FBP (see note 2)  

 

 

Notes:

 

 

1. 

 

Trouble and Supervisory LEDs are supported only in the panels listed above. 

 2. 

Keypad 

address 

may

 be set to address 00 through 30 to operate with these controls (see control's instructions for 

 details).

 

 

GENERAL INFORMATION 

The 6160CR-2 is an addressable remote keypad intended for 
use in commercial applications with Honeywell control panels 
listed above. The 6160CR-2’s address is set locally, via the 
keypad’s keys (

see note 2, above)

. The keys are continuously 

backlit for convenience. The LCD display is backlit only when 
a key is depressed, or when the system is in alarm or trouble 
condition.  

Note:

   On some controls, the LCD may be programmed to 

remain on at all times 

(see control’s instructions for details)

 

KEYPAD LED INDICATIONS 

The keypad’s LEDs will light under the following conditions:

 

ARMED (Red) 

ON 
OFF 

System is Armed 
System is Disarmed 

READY (Green) 

ON 
OFF 

System is Ready  
System is Not Ready 

POWER (Green)  

ON 
OFF 

AC power is O.K.  
AC power is removed 

FIRE ALARM 
(Red)  

ON 
OFF 

Fire Alarm has occurred 
Normal 

SILENCED 
(Yellow) 

ON 
OFF 

Fire Alarm has been silenced 
Normal

 

SUPERVISORY 
(Yellow) 

ON 
 
 
OFF 

Supervisory condition exists 
(see control’s instructions for 
details) 
Normal 

TROUBLE  
(Yellow) 

ON 
 
 
OFF 

Trouble condition exists 

(see 

control’s instructions for details) 
Normal 

 

SPECIAL FUNCTION KEYS 

The keypad also features programmable function keys labeled 
A, B, and C. These keys may be programmed to initiate panic 
or emergency alarms. Refer to the individual control panel’s 
instructions for details.)  

 

These keys 

must

 be held down for at least 2 seconds to 

initiate the assigned function. 

 

 

WIRING AND INSTALLATION 

The keypad may be surface-mounted directly to a dry wall or 
to a single- or double-gang electrical box. If this is the primary 
Fire Keypad, connect to Keypad Port 2, wire in conduit, and 
mount within 20 ft. of the control. 
1.  Detach the case back by pushing up into one of the two slots 

at the bottom of the keypad with the blade of a small 
screwdriver (this will push in the release tab), then pull 
that side of the case back away. Repeat for the other side. 
Refer to Figure 1 for location of the case back release tabs.

 

2.  Route wiring through the large rectangular opening in the 

case back.

 

3.  Mount the case back to the wall or electrical box. 

4.  Wire directly from the keypad’s terminal block (see Figure 

2) to the terminal block on the control panel (see control’s 
Summary of Connections label for correct terminal 
connections).   

 

NOTE:

 No more than one wire per terminal may be 

connected. If daisy-chained configuration is required, pig-
tail wires together so that only one wire is terminated 
under the screw. 

Use 16-24  AWG wire only!

 

TABLE 1 - Wiring Connections 

Keypad 

Control Panel  

Wire Color 

 Y 

Data Out  

Yellow 

+ Aux. Pwr  

Red 

 –   

– Aux Pwr (GND) 

Black 

 

G

 

Data In 

Green 

5.

 

Reattach the keypad to its case back.

 

Attach the top of 

the keypad first, and then press the bottom section down 
until it snaps into place securely.

 

6160CR-006-V2

A

B

C

D

ARMED

POWER

FIRETROUBLE

FIRESUPERVISORY

READY

SILENCED

FIREALARM

 

Figure 1 – Removing the Case Back 