background image

® U.S. Registered Trademark
Copyright © 2002 Honeywell •   

 • All Rights Reserved 

INSTALLATION INSTRUCTIONS

69-1412-1

T8624D Chronotherm

®

 IV

Deluxe Programmable

Multistage Thermostats

APPLICATION

The T8624D Chronotherm® IV Deluxe Programmable 
Multistage Thermostats provides electronic control of 24 
Vac single-zone multistage systems.

Refer to Table 1 for a general description of the 
thermostats. All T8624 thermostats require a common 
wire to supply power.

Table 1. Description of T8624 Thermostats.

MERCURY NOTICE

If this control is replacing a control that contains 
mercury in a sealed tube, do not place your old 
control in the trash. Dispose of properly.

Contact your local waste management authority 
for instructions regarding recycling and the 
proper disposal of the old control. 

INSTALLATION

When Installing this Product...

1.

Read these instructions carefully. Failure to follow 
the instructions can damage the product or cause 
a hazardous condition.

2.

Check the ratings given in the instructions and on 
the product to make sure the product is suitable for 
your application.

3.

Installer must be a trained, experienced service 
technician.

4.

After completing installation, use these instructions 
to check out the product operation.

Location

Install the thermostat about 1.5m (5 ft) above the floor in 
an area with good air circulation at average temperature. 
See Fig. 1.

Do not install the thermostat where it can be affected by:

— drafts, or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall 

behind the thermostat.

T8624

Changeover

System Selection

Fan

Selection

Comments

D

Automatic

Heat-Off-Cool-Auto

On-Auto

System and fan selections are done by keyboard.

Summary of Contents for CHRONOTHERM IV T8624D

Page 1: ...ION When Installing this Product 1 Read these instructions carefully Failure to follow the instructions can damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After completing installation use these instructions to ...

Page 2: ...lush with the wall 4 Position the wallplate over the holes pulling wires through the wiring opening 5 Loosely insert the mounting screws into the holes 6 Tighten mounting screws Fig 2 Mounting the wallplate WIRING All wiring must comply with local electrical codes and ordinances Refer to Fig 3 for typical hookup A letter code is located near each terminal for identification CAUTION Electrical Shoc...

Page 3: ...ate W2 L1 HOT L2 M11309 FAN RELAY Y1 G C THERMOSTAT RC HEAT RELAY 1 R W1 L1 HOT L2 COMPRESSOR CONTACTOR 1 Y2 COMPRESSOR CONTACTOR 2 HEATING TRANSFORMER COOLING TRANSFORMER HEAT RELAY 2 OT OT B HEAT DAMPER OUTDOOR SENSOR COOL DAMPER O 2 2 3 3 3 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED JUMPER RC TERMINAL TO R TERMINAL WHEN INSTALLED ON A ONE TRANSFORMER SYSTEM CAN ...

Page 4: ...ram If the daytime energy savings period is not used press the period key Leave or Return until the time is blank The fan setting feature is available on select thermostat models See Owners Guide form number 69 0940 for complete instructions on changing the program Table 2 Default Program Settings M14624 Time Set Program System Fan Run Program Hold Temp Set Current Day Time Wake Leave Return Sleep...

Page 5: ...mbers are shown on the device Example If thermostat does not have a System key Installer Setup Number 12 will not be displayed Review Table 3 factory settings and mark any desired changes in the Actual Setting column When Installer Setup is complete review the settings to confirm that they match the system M14559 Aux Ht Set Day Time Set Program Mon Wake Leave Return Sleep Outdoor Room Filter Wait ...

Page 6: ...mperature is displayed 1 Outdoor temperature is displayed Needs a C7089B1000 Outdoor Temperature Sensor to operate Not Used 25 thru 29 Deadband 30 3 Heating and cooling setpoints can be set no closer than 3 F 1 5 C 4 thru 10 Heating and cooling setpoints can be set no closer than the chosen value 4 4 F 2 C 5 5 F 2 5 C 6 6 F 3 C 7 7 F 3 5 C 8 8 F 4 C 9 9 F 4 5 C 10 10 F 5 C Not Used 31 and 32 Minim...

Page 7: ...ture 1 Display adjusts to 1 F lower than actual room temperature 2 Display adjusts to 2 F lower than actual room temperature 3 Display adjusts to 3 F lower than actual room temperature Furnace Air Filter Timer 43 2 30 days System run time 0 1 3 4 0 Off 1 10 days 3 60 days 4 120 days Time counted when heat cool or fan is running Humidifier Pad Monitor 44 0 Off 1 2 3 1 90 days 2 180 days 3 365 days ...

Page 8: ...isplayed before the 10 appears See Fig 10 and 11 Table 4 Tests Available In Installer System Test Fig 10 Display of all the segments of the LCD Fig 11 Display of test number Refer to Table 5 for the directions and results of the specific tests Press Time to advance to the next test and Time to go back to the previous test Press Run Program to exit the system test M14622 Time Set Program System Fan...

Page 9: ... Stage one heat comes on The system fan is also energized 12 Stage two heat comes on Stage one heat and system fan remain on 11 Stage two heat turns off 10 Stage one heat and system fan turn off Cooling Equipment System Test Time 30 Change from heating to cooling equipment System Test 31 Stage one cool and system fan come on 32 Stage two cool comes on Stage one cool and system fan remain on 31 Sta...

Page 10: ... soft ware identification code Example 02 software ID code 2 4 Press the increase key again to display the soft ware revision number Example 001 Revision number 1 5 Press the increase key again to display the EEPROM identification code Example 314 EEPROM ID 314 6 Press the Run Program key to exit the system test The system test times out after four minutes with out any key presses CHECKOUT Outdoor...

Page 11: ...t come on No power to the thermostat Check for 24 Vac between R and W terminals If missing 24 Vac check if the circuit breaker is tripped reset the circuit breaker check if the system fuse is blown replace the fuse check if the power switch on the HVAC equipment is in the Off position set to the On position check wiring between thermostat and HVAC equipment replace any broken wires and tighten any...

Page 12: ...gisters Heating or cooling equipment is not operating Verify operation of heating or cooling equipment in self test Outdoor tempera ture not displayeda Option not activated Enter Installer Setup number 24 and set to 1 Thermostat must have OT terminals and a C7089B1000 installed Outdoor temperature display is incorrecta Outdoor sensor is connected incorrectly Refer to C7089B1000 Installation Instru...

Reviews: