ROME Series

Relay Option Module Enclosure

Product Installation Document

PN 53530:B   9/14/2009   09-327

The ROME (Relay Option Module Enclosure, red) and ROME-B (black) is shipped with one ANN-BUS Relay Module 
already installed.  The ROME Series provides mounting space for one additional Relay Module or one addressable Multi-
Module.  

Relay Module 

The Relay Module provides 10 programmable Form-C relays when used with a compatible FACP (Fire Alarm Control 
Panel).  This document is provided as a quick reference.  For more detailed programming information, refer to the appro-
priate FACP installation manual.

Relay Module Specifications

Relay Designations and Terminals

The relay numbers and terminal designations are illustrated in the following illustration.

Operating Voltage

24 VDC

Max. Current @ 
24 VDC

Alarm

75 mA

Standby

15 mA

Operating Temperature

32° to 120° F
(0° to 49° C)

Max. Wiring Distance from FACP
(with 12 AWG wire)

1,250 ft. (380 m)

Relay Contact Ratings

2 amps @ 30 VDC 
(resistive)

0.5 amps @ 30 VAC 
(resistive)

Indoor Use in Dry Location Only

Relay Module

Relay Module

Normally Open, 
Normally Closed 
and Common 
terminals for each 
relay follow the 
same pattern as 
illustrated above.

R9             R10

R7             R8

R5             R6

R3             R4

R1             R2

NO
NC
C

NO
NC
C

Summary of Contents for Fire-lite ROME Series

Page 1: ...more detailed programming information refer to the appro priate FACP installation manual Relay Module Specifications Relay Designations and Terminals The relay numbers and terminal designations are illustrated in the following illustration Operating Voltage 24 VDC Max Current 24 VDC Alarm 75 mA Standby 15 mA Operating Temperature 32 to 120 F 0 to 49 C Max Wiring Distance from FACP with 12 AWG wire...

Page 2: ...e in appropriate FACP manual for wire gauge and distance limitations Setting Relay Module DIP Switches Each ANN BUS device requires a unique address Relay Module DIP switch SW1 is used to set the address for the mod ule A maximum of 8 devices can be connected to the FACP ANN BUS communication circuit ANN BUS device addresses do not need to be sequential and can be set to any number between 01 and ...

Page 3: ...s a guide 3 Remove the ANN MBRLY from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the ANN MBRLY using the two supplied self tapping screws 4 Place the ANN MBRLY mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Install the two sup...

Page 4: ...odule on the ANN MBRLY mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 2 Secure the Relay Module to the ANN MBRLY mounting bracket with the four supplied screws 3 Set the SW1 DIP switches and connect the wiring as described in the previous sections mounting hole mounting hole mounting hole mounting hole ROME Series Optional Relay Modul...

Page 5: ...KT as a guide 3 Remove the MULTIMOD BRKT from the ROME Series and drill two 3 32 dia 0 093 holes in the locations marked in step 2 Note that these holes will be used to secure the MULTIMOD BRKT using the two supplied self tapping screws 4 Place the MULTIMOD BRKT mounting bracket oblong holes in position over the mounting studs and install the two supplied nuts but do not tighten at this time 5 Ins...

Page 6: ... and flat against the bracket as illustrated below 8 Install the addressable Multi Module on the MULTIMOD BRKT mounting bracket by positioning the four module mounting holes over the four standoffs on the mounting bracket 9 Secure the addressable Multi Module to the MULTIMOD BRKT bracket with the four supplied mounting screws as illustrated below standoff standoff standoff standoff mounting screw ...

Reviews: