INSTALLATION INSTRUCTIONS

Copyright © 1995 Honeywell Inc. •             •  All Rights Reserved

T874G,R Multistage Heat Pump Thermostats

and Q674F,J,L Subbases

APPLICATION

The T874G,R Thermostats with Q674F,J,L Subbases
provide 24 to 30 Vac control of a two-stage heating/one-

stage cooling heat pump system. See Table 1 for
thermostat/subbase specifications.

Table 1. Thermostat/Subbase Specifications.

Switching

Thermostat/Subbase

System

Fan

Changeover

T874G/Q674F

OFF-EM.HT.-HEAT-AUTO-COOL

AUTO-ON

Auto and Manual

T874G/Q674J

EM.HT.-AUTO-OFF

AUTO-ON

Auto

T874R/Q674L

EM.HT.-HEAT-OFF-COOL

AUTO-ON

Manual

OPERATION

On a two-heat thermostat, the two stages of heat 

make

sequentially as the temperature drops. 

Make refers to the

mercury switch initiating a call for heat or cool.

There are about 2

°

F (1

°

C) between stages so that the

second stage makes only when the first stage cannot
handle the load. This is the 

interstage differential.

LEDs (light emitting diodes) are included on your subbase.
Refer to the list below for specific meaning.

The CHECK LED lights when something needs to be
checked or done to maintain efficient operation of the
system. See your heating system instructions for the
specific meaning.

The SYSTEM LED lights when the system is calling for
heating or cooling.

The AUX. HT. LED lights when the auxiliary heat (second
stage) is operating. Auxiliary heat operates when the heat
pump alone cannot handle the load.

The EM. HT. LED lights when the system switch is placed
in the EM. HT. position. Emergency heat is operating; in
most systems, the compressor has failed and the heat
pump is not operating.

LEDs are not field replaceable or addable.

RECYCLING NOTICE

This control contains mercury in a sealed tube. Do
not place the control in the trash at the end of its
useful life.

If this control is replacing a control that contains
mercury in a sealed tube, do 

not place your old

control in the trash.

Contact your local waste management authority for
instructions regarding recycling and the proper
disposal of this control, or of an old control
containing mercury in a sealed tube.

INSTALLATION

When Installing this Product…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a
hazardous condition.

2. Check the ratings given in the instructions and on

the product to make sure the product is suitable for
your application.

3. Installer must be a trained, experienced service

technician.

4. After installation is complete, check out product

operation as provided in these instructions.

69-0268-11

Summary of Contents for Q674J

Page 1: ...ions for the specific meaning The SYSTEM LED lights when the system is calling for heating or cooling The AUX HT LED lights when the auxiliary heat second stage is operating Auxiliary heat operates when the heat pump alone cannot handle the load The EM HT LED lights when the system switch is placed in the EM HT position Emergency heat is operating in most systems the compressor has failed and the ...

Page 2: ...he assembly includes an adapter ring two screws and a cover plate to cover marks on the wall Install the ring and cover plate on the vertical outlet box For a wall installation hold the subbase in position and mark holes for the anchors See Fig 2 Obtain wall anchors locally Take care that the wires do not fall back into the wall opening Set aside the subbase Drill four 3 16 in 5 mm holes and gentl...

Page 3: ...E MODELS ONLY C1 ANTICIPATOR H1 ANTICIPATOR FAN SWITCH AUTO ON SYSTEM SWITCH AUTO HEAT OFF COOL 1 2 4 6 8 9 10 O W2 X E L B W3 R G Y AUX HT RELAY FAN RELAY EM HT RELAY B RELAY M5986A THERMOSTAT SUBBASE SYSTEM COMPONENTS 11 12 COMPRESSOR CONTACTOR EM HT EM HT LED RED AUX HT LED GREEN COOL CHANGEOVER VALVE H2 FALL H2 ANTICIPATOR AUX HT RELAY Fig 3 Internal schematic and typical hookup for T874G Q674...

Page 4: ...ND E TERMINALS THERMOSTAT SUBBASE SYSTEM COMPONENTS H1 ANTICIPATOR H2 ANTICIPATOR C1 ANTICIPATOR SYSTEM SWITCH FAN SWITCH AUTO ON OFF EM HT AUTO EM HT RELAY COOL CHANGEOVER VALVE COMPRESSOR CONTACTOR M1629 1 2 4 6 8 9 10 Y C X E W1 R G O AUX HT LED YELLOW CHECK LED RED SYSTEM LED GREEN 4R HPS 4R 5R 4R 4R SEQ 1 SEQ 2 3R FAN RELAY Fig 4 Internal schematic and typical hookup for T874G Q674J in heat p...

Page 5: ... COMPONENTS H1 C1 ANTICIPATOR H2 ANTICIPATOR SYSTEM SWITCH FAN SWITCH AUTO ON OFF HEAT EM HT COOL FAN RELAY EM HT RELAY COOL CHANGEOVER VALVE COMPRESSOR CONTACTOR M1628A COMPRESSOR FAILURE C815A OUTDOOR THERMISTOR SYSTEM LED GREEN CHECK LED RED AUX HT LED YELLOW 2 3 4 5 6 11 12 RESET Y T C X E W1 R G O Fig 5 Internal schematic and typical hookup for T874R Q674L in heat pump system with outdoor res...

Page 6: ...4R 5R HPS 4R 4R C815A OUTDOOR THERMISTOR SYSTEM LED GREEN EM HT LED RED W1 AUX HT LED YELLOW Fig 6 Internal schematic and typical hookup for T874R Q674L in heat pump system with outdoor reset Includes AUX HT EM HT and SYSTEM LEDs C1 H1 H1 C1 ANTICIPATOR FALL H2 ANTICIPATOR L1 HOT L2 1 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED H2 FALL FAN RELAY EM HT RELAY B RELAY ...

Page 7: ...LVE COMPRESSOR MONITOR FAN RELAY H2 FALL H1 ANTICIPATOR C ANTICIPATOR H2 ANTICIPATOR POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED REMOVE JUMPER WHEN W1 RELAY IS USED FACTORY INSTALLED JUMPER 1 M5067 FAN SWITCH AUTO ON SYSTEM SWITCH EM HT HEAT OFF COOL 3 2 2 3 THERMOSTAT SUBBASE SYSTEM COMPONENTS 1 2 3 4 5 6 11 Fig 8 Internal schematic and typical hookup for T874R Q674L...

Page 8: ...AUX HT LED GREEN EM HT LED RED FAN SWITCH ON AUTO SYSTEM SWITCH EM HT HEAT OFF COOL H2 FALL H1 FALL C1 2 3 4 5 6 H1 C1 ANTICIPATOR H2 ANTICIPATOR 1 POWER SUPPLY PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED AUXILIARY HEAT LED AVAILABLE ON SOME MODELS THERMOSTAT SUBBASE SYSTEM COMPONENTS 2 2 Fig 9 Internal schematic and typical hookup for T874R Q674L in heat pump system Includes EM H...

Page 9: ...ve the thermostat cover by pulling the bottom edge of the cover outward and away from the base until it snaps free of the retaining posts NOTE The cover is hinged at the top and must be removed by pulling the bottom edge outward and away from the base 쐇 Carefully remove and discard the polystyrene packing insert that protects the mercury switches during shipment 쐋 Turn over the thermostat base and...

Page 10: ...LED RED 2 4R SEQ 1 4R 2 HPS 4R 5R 4R EM HT RELAY SEQ 2 3R G O FAN RELAY CHANGEOVER RELAY SYSTEM LED GREEN H1 C1 Fig 11 Internal schematic and typical hookup for T874R Q674L in heat pump system Includes AUX HT CHECK and SYSTEM LEDs Fig 13 Wiring connections SPIRIT LEVEL MOUNTING HOLES 2 M927 TOP MOUNTING HOLES 2 WIRING TERMINAL THERMOSTAT CABLE OPENING TO SPRING FINGER CONTACTS ON THE THERMOSTAT UP...

Page 11: ...0 F 10 C Refer to manufacturer recommendations Move the system switch on the subbase to COOL Move the setpoint lever cooling lever on T874G on the thermo stat about 10 F 6 C below the room temperature Cooling and fan should start Move the lever cooling lever on T874G about 10 F 6 C above the room temperature Cooling and fan should stop Emergency Heat Move the system switch on the subbase to EM HT ...

Page 12: ...ent recalibrate the thermostat thermometer see step 4 쐏 Insert a small screwdriver in the thermometer shaft Fig 16 and turn it until the thermometers read the same When the thermometer is calibrated replace cover and place into operation NOTE Radiant heat from your hands will offset the thermometer reading After making each adjustment wait five or ten minutes for the thermometer to stabilize befor...

Reviews: