background image

RA-2000 Remote Annunciator 
Installation

The optional Model RA-2000 Remote Annunciator, shown in 
Figure 1, performs the same functions as the on-board 
annunciator. Operation is identical. The RA-2000 can be surface 
or flush monted.
Up to 8 RA-2000s can be added to the IFP-2000 system.  

Figure 1: Model RA-2000 Remote Annunciator

RA-2000 installation involves the following steps:
1.

Make sure power is off at the panel.

2.

Mount the RA-2000 in the desired location (see Section 
“Mounting the RA-2000” ).

3.

Connect the RA-2000 to the panel (see Figure 2).

4.

Use the dipswitches on the back of the RA-2000 to assign 
an ID# to the RA-2000 (see Section 4.10.1 of Manual P/N 
151430).

5.

The RA-2000 module must be added to the system through 
programming. JumpStart AutoProgramming will add the 
module automatically (refer to Manual P/N 151430). 

Wiring Connections

Wire the RA-2000 to the FACP as Shown in Figure 2.

Figure 2: SBUS Connections

Specifications

Mounting the RA-2000

This section of the manual describes mounting the remote 
annunciator. The annunciator can be flush- or surface-mounted.

Flush Mounting

This section of the manual describes flush mounting.
Follow these steps to flush mount the RA-2000
1.

The back box dimensions are 9-3/8" w x 8-3/8" h. The 
minimum depth 2". The back box can be mounted prior to 
the complete installation of the RA-2000 using any of the 
mounting holes shown in Figure 3.

Figure 3: Back Box Mounting Holes

2.

Remove knockout holes as needed for wires. See Figure 4 

Parameter

Value

Operating Voltage:

24 VDC

Current

Standby:

25 mA

Alarm:

50 mA

Operating Temperature: 0° to 49° C (32° to 120° F)

Dimensions:

Flush 
Mount:

Overall: 12-1/4” W x 11.5” H x 7/8” D
31.1 cm W x 29.2 cm H x 2.2 cm D
See “Flush Mounting”  for back box 
dimensions.

Surface 
Mount:

Including trim ring:
12-1/4” W x 11.5” H x 3” D
31.1 cm W x 29.2 cm H x 7.6 cm D

Mounting Holes

Mounting Holes

firealarmresources.com

Reviews: