background image

INSTALLATION INSTRUCTIONS

62-0325ES-01

T6811DP08/T6812DP08 Digital Thermostat

Display

INSTALLATION GUIDE

CAUTION

Electrical Hazard.

Can cause electrical shock or equipment damage.

Disconnect power before installation.

Terminal Designations

Wiring Diagrams

Fig. 1. Typical wiring for ON/OFF control in 2 pipes Heat/

Cool/1H1C (for 2-wire valve actuators).

DOWN BUTTON

FAN SWITCH

UP BUTTON

MODE BUTTON

POWER SWITCH

MCR29502

Setup

Test

Set to

Lock

INDICATES THE

INSTALLER SETUP

INDICATES THE NUMBER

OF SETUP OR TEST

INDICATES THE 

INSTALLER TEST

KEYPAD LOCK

INDICATES THE

SETPOINT

INDICATES THE

TEMPERATURE

CURRENT

MODE

INDICATES TEMPERATURE IS 

“CALLING” FOR HEAT OR COOL

M29503

Terminal

Designation

L

Line Voltage Power

Ch/Cc

Heating close/Cooling close

W/Y

Heating open/Cooling open

N

Line Voltage Ground

Gl

Low speed fan

Gm

Medium speed fan

Gh

High speed fan

FAN

VALVE

L

N

L

Ch/Cc

W/Y

N

GI

Gm

Gh

M29504

Summary of Contents for T6811DP08

Page 1: ...s DOWN BUTTON FAN SWITCH UP BUTTON MODE BUTTON POWER SWITCH MCR29502 Setup Test Set to Lock INDICATES THE INSTALLER SETUP INDICATES THE NUMBER OF SETUP OR TEST INDICATES THE INSTALLER TEST KEYPAD LOCK INDICATES THE SETPOINT INDICATES THE TEMPERATURE CURRENT MODE INDICATES TEMPERATURE IS CALLING FOR HEAT OR COOL M29503 Terminal Designation L Line Voltage Power Ch Cc Heating close Cooling close W Y ...

Page 2: ... screws and tighten See Fig 3 left 3 Loosen screw terminals used for the application Insert the wires into the terminal block and tighten each screw terminal See Fig 3 right Fig 3 Wiring thermostat 4 Align the top of the thermostat with the back cover and push down on the back cover See Fig 4 left 5 Insert the locking screw into the whole on the bottom of the thermostat and tighten See Fig 4 right...

Page 3: ...ault 18 Display Temperature adjustment 2 C 4 F 1 5 C 3 F 1 C 2 F 0 5 C 1 F 0 C 0 F Default 0 5 C 1 F 1 C 2 F 1 5 C 3 F 2 C 4 F 19 Temperature Display mode 0 Display Room Temperature Default 1 Display Setpoint 20 Heating Range Stops 10 32 C Default 32 C 50 90 F Default 90 F 21 Cooling Range Stops 10 32 C Default 10 C 50 90 F Default 50 F 22 Keypad Lockout 0 All keys available Default 1 All keys loc...

Page 4: ...olutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Toronto Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2009 Honeywell International Inc 62 0325ES 01 M S 10 09 ...

Page 5: ...O CONMUTADOR DEL VENTILADOR BOTÓN ARRIBA BOTÓN DE MODO CONMUTADOR DE ENCENDIDO MSCR29502 Setup Test Set to Lock INDICA LA CONFIGURACIÓN DEL INSTALADOR INDICA EL NÚMERO DE AJUSTE O DE TEST INDICA EL TEST DEL INSTALADOR BLOQUEO DE TECLADO INDICA EL PUNTO DE AJUSTE INDICA LA TEMPERATURA MODO ACTUAL INDICA SI LA TEMPERATURA ESTÁ EN FRÍO O EN CALOR MS29503 Terminal Descripción L Voltaje de línea Ch Cc ...

Page 6: ...g 3 a la izquierda 3 Suelte los terminales de tornillo utilizados para la apli cación Inserte los cables en el bloque de terminales y apriete cada terminal de tornillo Consulte la Fig 3 a la derecha Fig 3 Cableado del termostato 4 Alinee la parte superior del termóstato con la tapa pos terior y empuje la tapa posterior hacia abajo Consulte la Fig 4 a la izquierda 5 Inserte el tornillo de bloqueo e...

Page 7: ...r Cool frío o Vent vent En el modo de ventilación sólo funcionará el ventilador 4 Ajuste de temperatura En modo de calor frío presione o arriba o abajo para seleccionar la temperatura deseada No Descripción Opciones 1 Tipo de Sistema 0 Solamente calor 1 Solamente frío 2 Dos tubos 1C1H manual Prestablecido de fabrica 9 Escala de temperatura 0 F 0 C Prestablecido de fabrica 13 Valor CPH para calor 1...

Page 8: ...por encima del setpoint Verifique si el icono de calor se encuentra sólido en la pantalla Espere cinco minutos para que el sistema de calor responda El sistema de enfriamiento no se inicia Seleccione el modo en Cool frío presionando el botón de modo Verifique si la temperatura del cuarto está por debajo del setpoint Verifique si el icono de frío se encuentra sólido en la pantalla Espere cinco minu...

Reviews: