background image

INSTALLATION INSTRUCTIONS

® U.S. Registered Trademark
© 2004 Honeywell International Inc.
All Rights Reserved 

95-7538—4

T7770A,B,C,D,E,F,G

Wall Modules

BEFORE INSTALLATION

Cover Disassembly

Two locking mechanisms are used on the cover of the wall 

module. After installation, to disassemble the cover and the 

subbase see Fig. 1.

Fig. 1. Cover disassembly.

CAUTION

Erratic System Operation Hazard.

Failure to follow proper wiring practices can 

introduce disruptive electrical interference (noise).

Keep wiring at least one foot away from large inductive 

loads such as motors line starters, lighting ballasts, 

and large power distribution panels.

Shielded cable is required in installations where these 

guidelines cannot be met.

Ground shield only to grounded controller case.

IMPORTANT

All wiring must comply with local electrical codes 

and ordinances or as specified on installation 

wiring diagrams.

— Wall module wiring can be sized from 14 to 22 AWG 

(2.0 to 0.34 sq mm) depending on the application.

— The maximum length of wire from a device to a wall 

module is 1000 ft (305m).

— Twisted pair wire is recommended for wire runs longer than 

100 ft (30.5m).

— The cover for the wall module is packed separately from 

the subbase for ease of installation.

See Fig. 2 to release/replace the subbase terminal block.

Fig. 2. Releasing/replacing terminal block.

INSTALLATION

Mount the T7770A,B,C,D,E,F,G Wall Modules on an inside 

wall approximately 54 in. (1372 mm) from the floor (or in the 

specified location) to allow exposure to the average zone 

temperature. Do not mount the wall modules on an outside 

wall, on a wall containing waterpipes or near air ducts. Avoid 

locations that are exposed to discharge air from registers or 

radiation from lights, appliances, or the sun.

The wall modules can be mounted on a wall, on a standard 

utility conduit box using No. 6 (3.5 mm) screws or on a 60 mm 

wall outlet box (see Fig. 3). When mounting directly on a wall, 

use the type of screws appropriate for the wall material.

M11394

T7770E

BUTTON HEAD

SOCKET CAP

SCREW

ALLEN TOOL

STEP 1

STEP 2

STEP 3

70

65

60

55

75

auto

 0 1

80

85

M17988

PRESS SHADED AREA 

OF TAB WITH THUMB TO 

RELEASE TERMINAL BLOCK 

FOR EASIER WIRING

Summary of Contents for T7770A

Page 1: ...tion The maximum length of wire from a device to a wall module is 1000 ft 305m Twisted pair wire is recommended for wire runs longer than 100 ft 30 5m The cover for the wall module is packed separately from the subbase for ease of installation See Fig 2 to release replace the subbase terminal block Fig 2 Releasing replacing terminal block INSTALLATION Mount the T7770A B C D E F G Wall Modules on a...

Page 2: ...t polarized reversing the two sensor leads does not affect the signal Wiring Modules With a Removable Terminal Block Wire the terminal blocks as follows 1 For single wires strip 3 16 in 5 mm for multiple wires going into one terminal strip 1 2 in 13 mm insulation from the conductor 2 If two or more wires are being inserted into one terminal twist the wires together before inserting NOTE When two o...

Page 3: ...ITH T7770C MODEL SENSORS NOTE CHANGE AND VERIFY DIP SWITCH POSITIONS FOR THESE EXCEL CONTROLLERS S4 1 4 ON 2 3 5 OFF 1 2 3 4 5 6 7 8 9 SENSOR GND E BUS E BUS NOTE VERIFY DIP SWITCH POSITIONS S4 1 3 5 ON 2 4 OFF M11403 SETPT 1 2 3 4 5 ON S4 BYPASS LED 1 1 TERMINAL 5 IS USED ONLY WITH T7770C MODEL SENSORS 1 2 3 4 5 6 7 8 9 SENSOR GND E BUS E BUS NOTE VERIFY DIP SWITCH POSITIONS S4 1 2 3 4 ON 5 OFF M...

Page 4: ...w by reversing step 1 on Fig 1 NOTE The locking screw must be installed and tight for a secure T7770 installation 1 2 3 4 5 6 7 8 9 SENSOR AI COM NOTES T7770G HAS A THREE SPEED FAN CHANGE AND VERIFY DIP SWITCH POSITIONS FOR THESE EXCEL CONTROLLERS S4 2 4 ON 1 3 5 OFF M11411 1 2 3 4 5 ON S4 BYPASS FAN LED LED RETURN FAN SPEED SWITCH 1 1 USING AN EXCEL 20 WITH THIS WALL MODULE REQUIRES WIRING AT CON...

Reviews: