Before installing sensors, please thoroughly read the System Smoke Detector 
Application Guide, which provides detailed information on sensor spacing, 
placement, zoning, and special applications. Copies of this manual are avail-
able from Honeywell.

NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This sensor must be tested and maintained regularly following 
NFPA requirements. It should be cleaned at least once a year.

GENERAL DESCRIPTION

Model TC846A1005 is a plug-in type smoke sensor that uses a laser based 
sensing chamber. The sensor uses analog-addressable communications to 
transmit smoke density and other information to the control panel. Rotary-de-
cade switches are provided for setting the sensor’s address. Two LEDs on the 
sensor are controlled by the panel to indicate sensor status. An output is pro-
vided for connection to an optional remote LED annunciator (P/N RA400Z/
RA100Z). 

The TC846A1005 requires compatible addressable communications to 
function properly. Connect these sensors to listed-compatible control pan-
els only.

SPACING

Honeywell recommends spacing sensors in compliance with NFPA 72. In low 
air flow applications with smooth ceilings, space sensors 30 feet apart. For 
specific information regarding sensor spacing, placement, and special applica-
tions, refer to NFPA 72.

WIRING INSTRUCTIONS

All wiring must be installed in compliance with the National Electrical Code, 
applicable local codes, and any special requirements of the Authority Having 
Jurisdiction. Proper wire gauges should be used. The installation wires should 
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the 
event of a fire.

REMOVE POWER FROM THE COMMUNICATION LINE BEFORE INSTALL-

ING SENSORS.

All wiring must conform to applicable local codes, ordinances, and regula-
tions.

1.   Wire the sensor base (supplied separately) per the wiring diagram, see 

Figure 1.

2.   Set the desired address on the sensor address switches, see Figure 2.
3.   Install the sensor into the sensor base. Push the sensor into the base 

while turning it clockwise to secure it in place.

4.   After all sensors have been installed, apply power to the control unit and 

activate the communication line.

5.   Test the sensor(s) as described in the TESTING section of this manual.

TC846A1005 

Intelligent Laser Smoke Sensor

INSTALLATION INSTRUCTIONS

I56-0060-00

7

SPECIFICATIONS 

Operating Voltage Range: 

15 to 32 VDC

Standby Current: 

330µA @ 24 VDC (one communication every 5 sec. with LED blink enabled)

Max. Alarm Current (LED on): 

6.5 mA @ 24 VDC

Operating Humidity Range:  

10% to 93% Relative Humidity, noncondensing

Operating Temperature Range: 

0°C to 38°C (32°F to 100°F); U.S.

 

–10°C to 50°C (14°F to 122°F); Europe

Height:  

1.7 inches (43 mm) installed in B210LP Base

Diameter: 

6.1 inches (155 mm) installed in B210LP Base

 

4.1 inches (104 mm) installed in B501 Base

Weight:    

5.0 oz. (142 g)

CAUTION

Dust covers provide limited protection against airborne dust particles during 
shipping. Dust covers must be removed before the sensors can sense smoke. 
Remove sensors prior to heavy remodeling or construction.

TESTING

Before testing, notify the proper authorities that the system is undergoing 
maintenance, and will temporarily be out of service. Disable the system to 
prevent unwanted alarms.

All sensors must be tested after installation and periodically thereafter. Test-
ing methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors 
offer maximum performance when tested and maintained in compliance with 
NFPA 72. 

The sensor can be tested in the following ways:

A. FUNCTIONAL: MAGNET TEST (P/N M02-04-01 OR M02-09-00) 

This sensor can be functionally tested with a test magnet. The test magnet 
electronically simulates smoke in the sensing chamber, testing the sensor elec-
tronics and connections to the control panel.

1.   Hold the test magnet in the magnet test area as shown in Figure 3.
2.   The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor status. 
Coded signals, transmitted from the panel, can cause the LEDs to blink, latch 
on, or latch off. Refer to the control panel technical documentation for sensor 
LED status operation and expected delay to alarm.

B. SMOKE ENTRY: AEROSOL GENERATOR (GEMINI 501) 

The GEMINI model 501 aerosol generator can be used for smoke entry testing. 
Set the generator to represent 4%/ft. to 5%/ft. obstruction as described in the 
GEMINI 501 manual. Using the bowl shaped applicator, apply aerosol until 
the panel alarms.

A sensor that fails any of these tests should be cleaned as described under 
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced 
and returned for repair.

When testing is complete, restore the system to normal operation and notify 
the proper authorities that the system is back in operation.

1985 Douglas Drive North

Golden Valley, MN 55422 USA

customer.honeywell.com

Honeywell Control Systems Ltd

  Honeywell House, Arlington Business Park

  Bracknell, Berkshire RG12 1EB  UK

  

I56-0060-007 

 

 10-03

Summary of Contents for TC846A1005

Page 1: ...060 007 SPECIFICATIONS Operating Voltage Range 15 to 32 VDC Standby Current 330µA 24 VDC one communication every 5 sec with LED blink enabled Max Alarm Current LED on 6 5 mA 24 VDC Operating Humidity Range 10 to 93 Relative Humidity noncondensing Operating Temperature Range 0 C to 38 C 32 F to 100 F U S 10 C to 50 C 14 F to 122 F Europe Height 1 7 inches 43 mm installed in B210LP Base Diameter 6 1...

Page 2: ...ign the cover and then gently pushing it until it locks into place 8 Reinstall the detector 9 Test the detector as described in TESTING 10 Reconnect disabled circuits 11 Notify the proper authorities that the system is back on line CAUTION Do not loop wire under terminal 1 or 2 Break wire run to provide supervision of connection LASER SAFETY INFORMATION This smoke detector does not produce any haz...

Page 3: ... FIGURE 2 ROTARY DECADE ADDRESS SWITCHES FIGURE 3 TEST MAGNET POSITION FIGURE 4 SENSOR ASSEMBLY TENS ONES 9 8 7 6 5 4 3 2 1 0 9 8 7 6 5 4 3 2 1 0 D N T N I A P T O O T E S T M A G N E T TEST MAGNET PAINTED SURFACE MAGNET TEST MARKER LED STATUS INDICATORS PAINTED SURFACE 3 I56 0060 007 10 03 ...

Page 4: ...d in the SDU data file from the TC846 tab in the 3 AADC configuration screen The TC846A1005 is connected to the 3 AADC Analog Addressable Device Con troller using a Honeywell B210LP standard base B224RB relay base B224BI isolator base B501BH Horn Base or B501BHT Temporal Tone Sounder Base PREINSTALLATION Configure and install the XLS1000 fire alarm control panel with a 3 AADC An alog Addressable D...

Reviews: