INSTALLATION

WHEN INSTALLING THIS PRODUCT…

1. Read these instructions carefully. Failure to follow

them could damage the product or cause a hazardous
condition.

2. Check the ratings given in the instructions and on the

product to make sure the product is suitable for your
application.

3. Installer must be a trained, experienced service tech-

nician.

4. After installation is complete, check out product op-

eration as provided in these instructions.

CAUTION

1. Disconnect power before beginning installation to

prevent electrical shock or equipment damage.

2. Make sure combustion chamber is free of oil or

vapor before starting system.

R8184G PROTECTORELAY

OIL PRIMARY

APPLICATION

The TRADELINE intermittent ignition oil primary control

operates the oil burner, oil valve (if desired) and the ignition
transformer in response to a call for heat from the thermo-
stat. Through a C554 Cad Cell Flame Sensor, the R8184
monitors the burner flame and shuts down the system on
ignition failure or on flame failure during the run cycle. A light
emitting diode (LED) on the terminal strip lights when the
safety switch opens to provide safety shutdown indication.
A manual reset button is provided to reset the safety switch
after lockout.

For convenience in system maintenance, the safety

switch can be manually opened using a lever on the front of
the control. Clock thermostats that power the clock through
the primary control transformer will lose time during lockout
unless backup batteries are installed.

R8184G is component recognized by Underwriters Labo-

ratories Inc. and meets their flammability test requirements
for a final enclosure.

D.T.

Form Number 69-0617—1

Rev. 4-91

© Honeywell Inc. 1991

Fig. 1—Mounting the  R8184G  controls with 130

°

 F

[54

°

 C] maximum ambient temprature.

 LOCATION

1. Mount  on a 4 x 4 inch junction  box, directly on the main

burner, or inside the appliance cabinet. In replacement
applications, mount in the same location as the old control.

2. Ensure the operating temperatures are within the am-

bient temperature range. Ambient temperature ranges are
either  -40

°

  to  130

°

  F  [-40

°

 C to 54

°

 C] or  -40

°

 F to 150

°

 F

[-40

°

 C to 66

°

 C] (Refer to box label).

MAKE WIRING CONNECTIONS AND MOUNT CONTROL

Wiring must comply with all local codes and ordinances.
Before mounting the control, make line voltage connec-

tions as shown in Fig. 1 or 2. Splice leads with solderless
connectors. Do not exceed load ratings shown on the device
label.

If cad cell leads are run with line voltage wires, breakout

knockout at the bottom of the low voltage terminal strip and
thread can cell leads through the hole.

If necessary use control as a template to mark and drill new

mounting holes. Mount using No. 6 screws (obtain locally).

Fig. 2—Typical hookup for TRADELINE R8184G with indicator light.

CAD 
CELL LEADS

LINE 
VOLTAGE LEADS

MOUNTING
SCREW HOLE

RED RESET
BUTTON

4 x 4 JUNCTION
BOX

HOLE OR KNOCKOUT FOR
CAD CELL LEADS

LOW VOLTAGE
TERMINAL STRIP

1

STRIP WIRES 3/8 in. (9.5 mm); INSERT FROM SIDE, ABOVE OR BELOW.

T-T TERMINALS ON R8184G;  T1-T2 TERMINALS ON R8184N.

1

2

2

M1643B

JUNCTION BOX

BLACK

L1
(HOT)

L2

LIMIT

BURNER
MOTOR

IGNITION

OIL VALVE
(OPTIONAL)

ORANGE

WHITE

BILATERAL
SWITCH

CAPACITOR

TRIAC

1K1

R2

R8184G PROTECTORELAY CONTROL

SAFETY
SWITCH

R1

1K2

M1635

SAFETY
SWITCH 
HEATER

1K

CAD CELL

1

F

F

T

T

THERMOSTAT

2

LINE VOLTAGE 
THERMOSTAT

2

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

TO USE R8184 WITH LINE VOLTAGE CONTROLLER, JUMPER T-T TERMINALS AND CONNECT LINE VOLTAGE THERMOSTAT IN 
SERIES WITH LIMIT CONTROLLER.

1

2

SAFETY
SWITCH

LOCKOUT 
INDICATOR 
LED

Summary of Contents for TRADELINE R8184G

Page 1: ...991 Fig 1 Mounting the R8184G controls with 130 F 54 C maximum ambient temprature LOCATION 1 Mount on a 4 x 4 inch junction box directly on the main burner or inside the appliance cabinet In replacement applications mount in the same location as the old control 2 Ensure the operating temperatures are within the am bient temperature range Ambient temperature ranges are either 40 to 130 F 40 C to 54...

Page 2: ...s Strip leads 3 8 in 10 mm and insert under terminal screw See Fig 1 or 2 Connect cad cell leads to F F terminals and thermostat leads to T T terminals See Fig 3 or 4 CHECK SAFETY FEATURES Simulate flame failure 1 Follow starting procedure to turn on burner 2 Close hand valve in oil supply line 3 Safety switch should lock out approximately in safety switch timing indicated on label Indicator light...

Page 3: ...uts down the burner but doesnotdisconnectthepowersupply Turnoffpower at system switch or circuit breaker before servicing the control system burner motor oil valve or ignition to avoid electric shock To trip the safety switch move the safety switch lever down until the red reset button pops out and the indicator light comes on See Fig 5 Burner will not operate until safety switch is reset by pushi...

Page 4: ...omation and Control Solutions Honeywell International Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 www honeywell com ...

Reviews: