background image

GUIDE SPECIFICATION

63-2621—2

T7350 Programmable Commercial Thermostat

FOR MULTISTAGE CONVENTIONAL, HEAT PUMP, 

AND MODULATING SYSTEMS 

GENERAL

A. Overview:

The contractor shall furnish, install, and place in operating condition an HVAC control system 

described herein. All units shall be located in accordance with the plans.

B. Type of System:

System Requirements:

a. Control up to three heating and three cooling stages for gas heat, electric heat, heat pump or 

compressor cooling.

b. Permit 365-day programming with schedule copy.

c. Provide 365-day clock with automatic daylight savings changeover and up to 10 holidays.

d. Provide 48-hour clock backup.

e. Provide two occupied and two unoccupied periods per day.

f. Offer automatic heat/cool changeover with 2°F (1°C) minimum deadband.

g. Provide override capability for a 1 to 8 hour configurable period, with 3-hour default.

h. Include a comfort adjust feature to modify setpoints for the override duration.

i. Provide configurable Proportional plus Integral plus Derivative (P + I + D) temperature 

control.

j. Display room temperature in °F or °C.

k. Use multiple remote sensors (optional).

l. Use in conjunction with an economizer (optional).

m. Provide three levels of keypad lockout - none, overrides only and complete.

n. Provide occupancy input for Standby setpoint (optional).

o. Provide Temporary Not Occupied Override, 1-99 days.

p. Provide discharge high and low limits (with optional sensor).

q. Provide outdoor ambient lockout (with optional sensor).

r. Provide keypad method for saving and restoring both user and factory default settings.

s. Provide five methods for dehumidification (minimum ON time, reheat, reset temp setpoint, hot 

gas bypass and simple dehumidification.

t. Provide 2 modulating 4-20 mA (direct or reverse action) outputs for modulating heat and/or 

cooling.

u. Provide separate configurable recovery ramps for heating and cooling.

v. Provide sequential start after power failure.

w. Provide separate configurable cycle rates for heating and cooling response.

x. Provide ability to calibrate temperature sensor.

System Components:

a. Seven day (365 day optional) programmable thermostat with subbase.

b. Discharge air sensor (optional).

c. Wall mount temperature and integral or wall mount humidity sensors (optional).

d. Outdoor air sensor (optional).

e. Occupancy sensor (optional).

C. Codes and Standards:

The system shall comply with applicable provisions of ASHRAE 90-75.

These specifications are based on equipment from Honeywell to set a standard for design and 

quality.

D. Wiring:

All wiring shall meet National Electrical Codes and local electrical codes.

Summary of Contents for WebStat T7350

Page 1: ...evels of keypad lockout none overrides only and complete n Provide occupancy input for Standby setpoint optional o Provide Temporary Not Occupied Override 1 99 days p Provide discharge high and low limits with optional sensor q Provide outdoor ambient lockout with optional sensor r Provide keypad method for saving and restoring both user and factory default settings s Provide five methods for dehu...

Page 2: ...e of the deviation derivative gain The thermostat shall energize cooling equipment when space temperature exceeds cooling setpoint Optional Remote Equipment A solid state enthalpy changeover control shall determine the capability of the outdoor air to provide free cooling optional The system shall operate as follows a Free cooling available from Outdoor Air On a call for cooling the system shall e...

Page 3: ...cupied or Standby mode It shall switch to the Occupied mode for an installer configured number of hours The default shall be three hours b The Temporary Not Occupied Override shall fix the schedule to operate in Not Occupied mode for a number of days between 1 and 99 without changing programming saved in memory c Pressing Run Schedule shall cancel the overrides and return to the program THERMOSTAT...

Page 4: ...1046 T7770C1044 T7770D1000 and T7771A1005 any T7770 20K NTC D Economizer Logic Modules W6210 W6215 W7210 W7212 W7215 W7459 E Humidity Sensors Remote H7625 H7635 H7655 F PDA Units Palm V Vx M105 M125 and i705 handhelds TRGPro handheld ZIRE 71 handheld TUNGSTEN T T2 and C handhelds NOTE See customer honeywell com for software to configure a T7350 with a PC G Other Accessories 209651A Vertical Mounti...

Reviews: