HPE-MRBN – 

BACnet MS/TP Gateway to Modbus RTU 485

 

FW4.01 

 
Integration of BACnet MS/TP conforming devices in to Modbus RTU based systems. Up to 247 BACnet 
MS/TP devices may be connected to the gateway for read access of up to 250 BACnet data objects 
 

Typical Applications

 

 
Modbus RTU 485 network integration of BACnet MS/TP devices: 
 

  HVAC Controllers 

  PMAC770 electricity meters (c/w BACnet module) 

  Sontex SC531 chilled/hot water energy integrators (c/w BACnet module) 

  Belimo energy Valves * 

 

Belimo energy valves should have dedicated gateway, with System Vendor ID# 423 (SV=423) set in the gateway. 

Other BACnet devices may share a gateway, with default SV=0 setting. 

 

Feature Summary

 

 

  Modbus RTU RS485 slave port (BMS port) 

  BACnet MS/TP master-slave/token-passing (Sub-bus port)  

  User customised BACnet object data based 

  Modbus Long Integer and IEEE Floating Point register address ranges 

  Smart-polling of BACnet objects (only actively polled when active on the Modbus BMS side)  

 
 
 
 
 
 
 
 
 

 

Summary of Contents for BACnet HPE-MRBN

Page 1: ...et MS TP devices HVAC Controllers PMAC770 electricity meters c w BACnet module Sontex SC531 chilled hot water energy integrators c w BACnet module Belimo energy Valves Belimo energy valves should have dedicated gateway with System Vendor ID 423 SV 423 set in the gateway Other BACnet devices may share a gateway with default SV 0 setting Feature Summary Modbus RTU RS485 slave port BMS port BACnet MS...

Page 2: ...gs 6 Connecting at 76800 Baud Rate 6 Saving HyperTerminal Settings 6 BREAK IN TO TERMINAL MODE 6 MODBUS CONFIGRATION COMMANDS 7 BACNET CONFIGURATION COMMANDS 8 DATA BASE MAPPING TOOL 9 TERMINAL OPERATION 10 DOWNLOAD TEXT FILE 10 ENABLE BACNET MS TP PORT 11 VERIFY BACNET NETWORK COMMUNICATION 11 INSTALLATION COMMISSIONING 12 POWER RS485 12 CONNECTIONS 13 DIMENSIONS 13 TECHNICAL DATA 14 ORDERING INF...

Page 3: ...e 250 registers relating to the BACnet network devices data objects being read Long Integer Registers 4 6 8 502 Modicon Register Addresses using F03 Holding Register as example 40005 40007 40009 40503 IEEE Floating Point Registers 1004 1006 1008 1502 Modicon Register Addresses using F03 Holding Register as example 41005 41007 41009 41503 Write Relinquish The gateway operates on the BACnet side wit...

Page 4: ...manual available to assist with BACnet Object settings The gateway data base consists of 250 Modbus registers each configured with a target BACnet object s data 1 BACnet device address where the object resides MS TP Node address MAC 2 Object type BI BV BO AI AV AO MI MV MO 3 Object Instance object number Separately the BACnet network baud rate and Maximum Master value must be set The gtaeway is ge...

Page 5: ...or from Shade Blue are recommended The USB driver for the HPECOMU may be found on our web site The following settings reflect HyperTerminal Please contact us if you require assistance setting up Indigo HyperTerminal Settings For successful communication between HyperTerminal and the device initial Properties setup of HyperTerminal should be as per the screen prints below Connect to Comm Configurat...

Page 6: ...allow later terminal communication a device set with 76800 baud will operate at 9600 baud for the first 5 seconds after a power up If no attempt to connect the terminal at 9600 baud is made within 5 seconds of a power up then the device will automatically switch to 76800 for normal network operation Saving HyperTerminal Settings For ease of connection it is recommended to save the HyperTerminal se...

Page 7: ...57600 76800 Example 1001 38400 After changing comm speed it will be necessary to reconnect with HyperTerminal at the new comm speed to save write the change Zero the Reset counters 1 0 All Reset counters are zeroed Factory diag In order as displayed Rx timeout Tx timeout Hardware reset Zero the BACnet comms error counter 2 0 BACnet comms error counter is reset Example 2 0 Zero the M Bus comms erro...

Page 8: ... entered one by one Delete current point data base DE followed by 10000 1 Any configuration of point 4 502 is deleted Download of a text file with new data base will delete an old existing data base as a matter of course Enable BACnet subnet communication E Toggles Enabled Disabled of M Bus Subnet communication Default Disabled to allow easy configuration when no devices are connected Always Enabl...

Page 9: ...uest or by download from www hrw hk Resources Tools you can use our the HPE MRBN mapping Tool for creation of a table of data base settings which can be downloaded to the gateway as a text file txt As well as the generic BACnet mapping tool we also have Belimo device specific mapping tools available on request Copy the Download Table lines from the tool to Notepad text file and save for download t...

Page 10: ... entering the required settings Note that after changing the Modbus baud rate the terminal mode baud rate is also changed so reconnect HyperTerminal at the newly set baud rate and then Write W the new setting Download Text File Enter DE The display will indicate that the existing data base is being blanked and now Ready to receive data base text file While in the Ready state navigate to the text f...

Page 11: ...et MS TP communication and enter W to write the enabled state so that it will still be enabled after a power failure Note To disable enter E again to toggle from enabled to disabled state Verify BACnet Network Communication In terminal mode any scanning of the BACnet network will only occur after the data based points are added to the Log list 1 Enter L to place all points on log 2 Enter X to eXit...

Page 12: ...oing screen at each device should be continuously connected via the S terminal of the device note that the device s S terminal has no electrical connection to the device it merely acts as a junction terminal for the purpose of screen continuity The RS485 cable should avoid cable routes that run with power cables Where the RS485 cable must cross power cables then they should cross at 90 avoiding pa...

Page 13: ...1 Manual 170912 E O E Subject to change without notice Page 13 of 15 Connections Dimensions If using HDA0002 DIN rail adapter brackets the overall depth from the gear plate to the front surface of the device is 45 5mm ...

Page 14: ...e for control panel mounting Standard package 40 units per carton Accessories HDA0002 DIN rail adapter brackets factory fitted HPECOMU Configuration cable USB Other HP_MR Series Devices HPC0662MR Universal Controller 12 Point Modbus RTU 24Vac HPC8884MR Universal Controller 28 Point Modbus RTU 24Vac HPD0440BNMR Network HMI Universal Ctrl Scheduler Modbus RTU gateway 8 Point BACnet MS TP 24Vac HPD04...

Page 15: ...HRW HPE MRBN V401 Manual 170912 E O E Subject to change without notice Page 15 of 15 Notes ...