background image

HD105

Gas Detector

With Relay Output

User’s Guide

Ver5.2

ATTENTION:

Please take a few minutes to thoroughly read

this manual, which should be saved for future reference and
passed on to any subsequent owner.

IMPORTANT! READ ALL INSTRUCTIONS BEFORE

INSTALLATION AND KEEP THIS MANUAL NEAR THE

ALARM FOR FUTURE REFERENCE.

CONTENTS OF THIS MANUAL

1 – DESCRIPTION

2 – FEATURES

3 -- TECHNICAL SPECIFICATION

4 -- INSTALLATION INSTRUCTIONS

5 -- OPERATION AND TESTING

6 -- GAS SAFETY GUIDE

7 -- HOME SAFETY GUIDE

8 -- SERVICE AND WARRANTY

1. DESCRIPTION

The gas alarm is designed for single station use. Small and

compact, the design and color makes it ideal for use in the

home, small commercial properties, and recreational vehicles.

It is intended to detect leakage of natural gas (methane

gas), town gas, and bottled gas (propane gas). The unit

is designed for DC wire-in applications. The gas alarm

can be mounted high (for methane gas) or low (for

propane (LPG) gas). It is equipped with a sturdy metal

mounting bracket for quick, easy, and secure

installation.

2. FEATURES

Detect all sorts of combustible gases, natural gas

(methane), bottled gas (propane), LPG (Liquefied

petroleum Gas), LNG (Liquefied natural gas), coal

gas, including town gas.

Easy to install, mounting bracket included.

Loud 75dB alarm and LED warning light.

High quality durable sensor.

Self diagnostic function by MCU intelligent

software.

Excellent reliability & High stability.

Ideal for all kitchens.

3. TECHNICAL SPECIFICATIONS

Unit Dimensions:

103mm (D) x 55 mm (H)

Color:

Ceiling White

Weight:

155g

Operating Temperature:

-10°C to +50°C

Ambient Humidity:

≤95% RH

Alarm Horn:

75dB at 3m (10 feet)

Operating Voltage:

DC9-28V

Power Consumption:

<2W (Standby), <5W (Alarm)

Value of Detection Threshold (Lower Explosive Limit):

Natural Gas: 5000ppm (10% LEL)

Method of Alarm:

Flashing Red LED with 75dB alarm

Warm Up Time:

approximately

120 seconds

Alarm Output:

Relay Output (Normal Open 2A@DC24V)

4. INSTALLATION INSTRUCTIONS

The Gas Alarm is intended to detect leakage of natural

gas, town gas and bottled gas. It is intended for

installation in the home, small commercial properties,

and recreational vehicles.

Installation shall only be undertaken by technicians

holding a certificate issued by an authorized

distributor.

For detecting natural gas (lighter than air), the

alarm should be installed within 30 centimeters

below the ceiling and the maximum distance away

from the furnace or gas appliances is 8 meters.

For detecting LPG (heavier than air), the alarm

should be installed within 30 centimeters above the

floor and the maximum distance away from the

furnace or gas appliances is 4 meters.

The alarm should not be located close to any

obstacles preventing natural air circulation. It

should also not be located in a draft or close to a

cooker (cooking smells and other fumes can have a

bad influence on gas detection).

The detector can be connected with Security alarm

panel as Figure1. Relay output signal can be

changed from Normal Close(NC) to Normal

Open(NO) by Jump JP1 on the PCB board.

The detector can be connected with conventional

alarm panel as Figure 2 or Figure3.

For your convenience,

write down the following information.

If you call Us for Service, these are the first questions you

will be asked.

Gas Alarm Model Number (located on back of alarm):

Gas Alarm Assembly Number (Located on back of alarm):

Date of Purchase:

Where Purchased:

©

Reviews: