background image

HUAWEI TECHNOLOGIES CO., LTD.

SmartLogger2000-10-B-JP

Quick Guide (Japan)

Issue: 03
Part number: 31507917
Date: 2019-06-30

Summary of Contents for 31507917

Page 1: ...HUAWEI TECHNOLOGIES CO LTD SmartLogger2000 10 B JP Quick Guide Japan Issue 03 Part number 31507917 Date 2019 06 30 ...

Page 2: ...ation and recommendations in this document do not constitute a warranty of any kind express or implied 2 Before installing the device carefully read the SmartLogger2000 User Manual to get familiar with the product information and precautions SmartLogger is short for SmartLogger2000 10 B JP in the following text 3 Install and use the device according to this document and the user manual Otherwise t...

Page 3: ... 20 mA 0 20 mA current output 14 DI1 DI8 Digital input DI Connects to a dry contact input 2 Typical Cable Connection Scenarios 2 2 1 2 1 Non Smart Array Controller Scenario 2 1 1 If the SmartLogger communicates with an inverter over an AC power cable three fuses and a 3P3E switch need to be installed to prevent device damage in the case of short circuits 2 If the SmartLogger communicates with an i...

Page 4: ... Fuse Rated voltage 500 V rated current 6 A Prepared by the customer 3 PCS 3P3E switch The switch has a rated insulation voltage of 600 V a rated current of 15 A and three poles Kawamura NX53E 15W switch is recommended Prepared by the customer 1 PCS Socket Connects to the power adapter Prepared by the customer 1 PCS Smart Array Controller Scenario 2 2 The following describes the application scenar...

Page 5: ...er Recommended cable three core armor cable with the operating voltage to the ground greater than or equal to 600 V and the cross sectional area of a single core wire being 4 mm2 3 The SmartLogger and the three RS485 signal surge protective devices SPDs used by the SmartLogger have been installed before delivery 4 The SmartLogger PGND cable AC power cable power adapter and its power cable and the ...

Page 6: ... Purchased from Huawei 1 PCS Fuse Rated voltage 500 V rated current 6 A Prepared by customer 3 PCS 3P3E switch The switch has a rated insulation voltage of 600 V a rated current of 15 A and three poles Kawamura NX53E 15W switch is recommended Prepared by customer 1 PCS Installation Space Unit mm 3 1 3 Installing the SmartLogger Chassis dimensions including mounting ears Installation clearances Ins...

Page 7: ... mounting holes using a marker If you need to use a ladder to install the device on a high position take measures to protect yourself from falling down 2 Drill holes by using a hammer drill and install expansion sleeves washers and tapping screws Unit mm Screw assembly for wall mounting 1 ST3 5 tapping screw 2 Washer 3 Expansion sleeve Unit mm 3 Put the tapping screws through the SmartLogger mount...

Page 8: ...r using a Phillips screwdriver 2 Secure the guide rail clamps using M4x8 screws removed from the mounting ears and tighten the screws to a torque of 1 2 N m 1 Secure the guide rail before mounting the SmartLogger 2 Verify that the length of the guide rail is sufficient for securing the SmartLogger The recommended length is 450 mm or greater 7 4 Tighten the tapping screws to a torque of 0 3 N m usi...

Page 9: ...mmended to connect an RS485 signal SPD to strengthen the surge protection capability 2 Each RS485 signal SPD can connect to two COM ports Each SmartLogger can be configured with a maximum of three RS485 signal SPDs 3 When the RS485 signal SPD is to be installed in a non smart array controller you are recommended to install it on a guide rail 4 If the SmartLogger is installed on a guide rail the RS...

Page 10: ...rts To connect a COM port on the SmartLogger to a COM port on an outdoor device you are recommended to connect an RS485 signal SPD to strengthen the surge protection capability Installing the RS485 SPD Ground Cable 5 2 An outdoor copper core cable with a cross sectional area of 4 mm2 or 12 AWG is recommended 1 Prepare a ground cable with an appropriate length and strip 8 mm of the insulation layer...

Page 11: ...S485A RS485 differential signal 3 RS485B IN RS485B RS485 differential signal 4 RS485B OUT RS485B RS485 differential signal No Port Symbol Function 1 COM1 RS485A RS485 differential signal RS485B RS485 differential signal 2 COM2 RS485A RS485 differential signal RS485B RS485 differential signal 3 COM3 RS485A RS485 differential signal RS485B RS485 differential signal 4 COM4 RS485A RS485 differential s...

Page 12: ...otection ports 2 and 6 and surge ports 1 and 5 form an RS485 signal SPD port for protecting one COM port Protection ports 8 and 12 and surge ports 7 and 11 form another RS485 signal SPD port for protecting one more COM port RS485 Signal SPD RS485 Surge Protectio n Port Prote ction Port Port Definit ion Function Surge Port Port Definition Function RS485 surge protectio n port 1 2 RS485 A IN RS485A ...

Page 13: ...t of the RS485 signal SPD Verify that the COM port on the SmartLogger connects to protection port 2 or 8 on the RS485 signal SPD and that the COM port on the SmartLogger connects to protection port 6 or 12 on the RS485 signal SPD NOTE Unit mm A two core or multi core cable with a cross sectional area of 0 5 2 5 mm2 is recommended 1 Remove an appropriate length of the steel armor and insulation lay...

Page 14: ... sectional area being 1 mm2 and the cable outer diameter in the range of 14 mm to 18 mm 6 When you connect the RJ45 network port to the SUN2000 you are recommended to use the CAT 5E outdoor shielded network cable 1 Remove an appropriate length of the steel armor and insulation layer from both ends of the cable using a wire stripper Unit mm Connecting an RS485 Communications Cable 6 3 2 Connect the...

Page 15: ...ing the same protocol are connected to the same COM port Devices using different protocols for example the cubicle which uses the IEC103 protocol and the electricity meter which uses the DL T645 protocol need to be connected to separate COM ports 14 Recommended Connection Mode 1 If the SUN2000 is equipped with a PLC MBUS device the SmartLogger can communicate with the SUN2000 through an AC power c...

Page 16: ...DI1 GND1 to DI4 GND1 and DI5 GND2 to DI8 GND2 An OVGR can connect to any DI port 2 Two core or multiple core cables with a cross sectional area of 1 5 mm2 are recommended No Port Function 1 GND1 Dry contact input common terminal 1 2 DI1 DI_1 3 DI2 DI_2 4 DI3 DI_3 5 DI4 DI_4 6 DI5 DI_5 7 DI6 DI_6 8 DI7 DI_7 9 DI8 DI_8 10 GND2 Dry contact input common terminal 2 2 Connect the AC1 and AC2 terminals a...

Page 17: ... the SmartLogger can connect to a third party device 2 The SmartLogger can connect to a PC through a LAN switch or router over an Ethernet cable It can also be directly connected to a PC Select the connection device based on the actual networking scenario 3 Verify that the Ethernet communications cable is no longer than 100 m 1 Connect one end of the delivered network cable to the Ethernet electri...

Page 18: ...odule into the SFP1 or SFP2 port of the SmartLogger 2 Connect the two cables delivered with the optical module to the ports on the optical module 3 Connect the other ends of the cables to the ports of the device on the other side such as an ATB 11 Verifying the Installation No Check Item Check Result 1 The SmartLogger is properly installed Passed Failed 2 All cables are properly connected without ...

Page 19: ...ed Failed 12 Powering On the System Power on Procedure 12 1 1 Insert the output terminal of the power adapter into the 12V IN port of the SmartLogger 2 Insert the power cable into the power adapter 3 Insert the power cable plug into an AC socket 1 The rated input of the power adapter is 100 240 V AC 50 Hz or 60 Hz 2 Select an AC socket that matches the power adapter 4 Switch on the circuit breaker...

Page 20: ... SmartLogger or the devices connected to it generate minor alarms Steady red The SmartLogger or the devices connected to it generate major alarms Mainte nance status Green off No near end maintenance Blinking green slowly on for 1s and then off for 1s Near end maintenance is in progress Steady green The near end maintenance is successful Blinking green quickly on for 0 125s and then off for 0 125s...

Page 21: ...orm commissioning by connecting the SmartLogger to the SUN2000 APP NOTE NOTE 1 The SUN2000 app is a convenient maintenance platform that communicates with the monitoring system for you to query alarms configure parameters and perform routine maintenance The app name is displayed as SUN2000 2 Mobile phone operating system Android 4 0 or later or iOS 7 0 or later 3 To download the SUN2000 app softwa...

Page 22: ...is entered for five consecutive times the interval between two consecutive invalid password entries is less than 2 minutes the account will be locked for 10 minutes 1 If the SmartLogger is powered on for the first time or restores initialization and parameter configuration is not performed on the embedded WebUI the Quick Settings screen is displayed when the SmartLogger connects to the APP You can...

Page 23: ...nd tap SmartLogger Setting Currency Factor 13 2 At the bottom of the main menu choose More Settings User Param Income Then set Currency factor according to the actual situation Because of the permission restriction log in to APP as a common user or an advanced user to set Currency factor NOTE ...

Page 24: ...k port connection Check whether the RJ45 connector is correctly crimped with shielded cable wires of various colors connected to the correct pins 2 Terminal block connection Check whether the RS485 communications cable is connected to the correct port of the terminal block 3 Verify that the RS485 ports of other devices are connected to the correct ports on the SmartLogger 4 Check the RS485 communi...

Page 25: ...24 Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com ...