1
Issue: 04
Date: 2020-03-30
PowerCube 500 V200R001C10 Quick Guide
(CPS300-N18A1H1)
Copyright © Huawei Technologies Co., Ltd. 2020. All rights reserved.
1
Overview
Power module: CPS300-N18A1H1
Lithium battery: CBM20E-N14A1
Appearance
Solar Hybrid Scenario
Lithium battery
Lithium battery
Power module
Pole mounting kit
Pole mounting kit
Bullet
cameras
Dome camera
CPE
Lightning rod
Antenna
PV modules
PV module support
Pole
Cantilever
Lithium
Battery
Indicator
Color
Status
Meaning
Run
indicator
(RUN)
Green
Off
The lithium battery has no power input or
is faulty.
Steady on The lithium battery is powered on.
Blinking
slowly
(0.5 Hz)
The lithium battery is communicating
properly with upstream monitoring
equipment.
Blinking
fast (4 Hz)
The lithium battery fails to communicate
with upstream monitoring equipment.
Alarm
indicator
(ALM)
Red
Off
There is no alarm.
Steady on
The lithium battery has generated a fault
alarm and needs to be replaced.
Blinking
slowly
(0.5 Hz)
The lithium battery has generated a
protection alarm, which can be cleared.
Power
Module
Indicator
Color
Status
Meaning
Run
indicator
Green
Off
The power module has no power input
or is faulty.
Blinking
slowly
(0.5 Hz)
The power module is communicating
properly with upstream monitoring
equipment.
Blinking
fast (4 Hz)
The power module fails to communicate
with upstream monitoring equipment.
Alarm
indicator
Yellow
Off
There is no alarm.
Blinking
slowly
The power module has generated an
alarm, which can be cleared.
Steady
on
The power module has generated an
AC power failure or PV array fault alarm,
which can be cleared.
Fault
indicator
Red
Off
The power module is normal.
Blinking
slowly
The power module has an external fault,
which can be cleared.
Steady
on
The power module has an internal fault,
which cannot be cleared.
NOTE
The three indicators are steady on when the power module is
upgrading. They return to normal status after the upgrade is complete.