background image

HUAWEI TECHNOLOGIES CO., LTD. 

PDC-0038V4ACIOA-V2 

V100R001C11 

Quick Installation Guide 

Issue: Draft B 

Part Number: 31506178 

Date: 2013-06-08 

Summary of Contents for PDC-0038V4ACIOA-V2

Page 1: ...HUAWEI TECHNOLOGIES CO LTD PDC 0038V4ACIOA V2 V100R001C11 Quick Installation Guide Issue Draft B Part Number 31506178 Date 2013 06 08 ...

Page 2: ...e and maintain Huawei equipment and they must understand basic safety precautions 2 You can modify default parameters only after being granted approval from Huawei technical support Symbols Alerts you to a potentially hazardous situation that could if not avoided result in equipment damage data loss performance deterioration or unanticipated results Provides additional information to emphasize or ...

Page 3: ...ypass circuit breaker 8 Maintenance bypass circuit breaker cover PDC 0038V4ACIOA V2 Front panel under the cover Rear panel 1 2 4 5 6 7 3 8 9 10 11 12 13 14 15 16 1 Maintenance bypass ports 2 Dual in line package DIP switch 3 Control area network CAN communications ports 4 Output ports 5 Bypass input ports 6 Mains input ports 7 Output socket group 1 250 V AC 15 A disabled in the case of 110 V outpu...

Page 4: ...Check against the delivery list that the types of fittings are complete and correct If there is any discrepancy contact the local Huawei office immediately Wire stripper Polyvinyl chloride PVC insulation tape Heat gun Cable tie Electrostatic discharge ESD gloves Protective gloves Insulation gloves Cotton cloth Hydraulic pliers Heat shrink tubing Φ6 Electrician s knife Power screwdriver Multimeter ...

Page 5: ... mounting brackets and place the PDU on the guide rails Secure the UPS to the rack using M6x12TM screws through the holes in the mounting brackets Bolt 12 24 16 PCS Guide rails Do not move the PDU by holding its mounting brackets front panel or terminal cover ...

Page 6: ...5 2 Cable Installation Remove the front panel of the PDU and open the circuit breakers OFF Loosen screws to remove the busbar cover ...

Page 7: ...t off the mains circuit breaker output circuit breaker bypass circuit breaker maintenance bypass switch and battery circuit breaker 2 The 2 pole circuit breakers of K1 and Q1 used for cable connection are provided by the user 3 For the cable connection of single phase see the dual live wire connection method 4 If customers purchase input and output power cables by themselves use the cables that co...

Page 8: ...side you are advised to connect the load to the pL terminal and disable Power segment 3 In the case of 110 V parallel output short circuit L1 and L2 and short circuit N1 and N2 Ensure that the L1 and L2 cables are of an equal length and N1 and N2 cables are of an equal length Do not use the high voltage output port in the case of 110 V output otherwise devices may be damaged Do not use the high vo...

Page 9: ...ter check Power segment is Disable and set Output transformer to Enable 1 indicates press 2 indicates press then 3 indicates press then 4 indicates press then 5 The data in the menus is for reference only The LCD figures in this document correspond to V100R001C00SPC113 If the LCD is updated contact Huawei for the latest LCD figures ...

Page 10: ...ut circuit breaker on the PDU front panel Open the battery switch if the battery pack does not have a switch disconnect the battery pack hot swap terminal Disconnect the hot swap terminals between the PDU and the UPS Use a multimeter to check that the UPS input and output voltages are 0 You can maintain the UPS 1 UPS1 mains input circuit breaker 2 UPS2 mains input circuit breaker 3 UPS1 bypass inp...

Page 11: ...Huawei Technologies Co Ltd Huawei Industrial Base Bantian Longgang Shenzhen 518129 People s Republic of China www huawei com ...

Reviews: