background image

POLYMER-HOUSED ARRESTERS EVP - SERIES

 

Installation Instructions: 17-5156

Introduction

Hubbell Power Systems surge arresters are designed to limit 
surge voltage by conducting the surge current to ground, 
and thus avoiding equipment damage. The arresters are of 
single pole design, suitable for outdoor use, and designed in 
accordance with the latest revision of industry standard IEEE 
C62.11 and IEC 60099-4. 

Each EVP arrester contains a number of vertically stacked zinc 
oxide valve elements overwrapped with an epoxy-impregnated 
fiberglass filament wrap, contained within ESP® polymer 
weathershed housing(s). The metal end fittings attached to the 
housing(s) vary with the specific design ordered.   

Three arresters are required for three-phase installation. With the 
exception of special multi-rated designs, arresters are shipped as 
a single assembled unit.  Multi-rated arresters consist of separate 
units that must be stacked and bolted together in the field. 

Application

Initial Inspection

Rough handling can result in damage to the surge arrester. 
Arresters should be carefully removed from the carton or crate 
for inspection. If damage is apparent, do not install the arrester. 
Claims for shipping damage should be registered immediately 
with the common carrier.

The arrester model number, rated voltage (Ur for IEC arresters), 
and MCOV (Uc for IEC arresters) are identified on the arrester 
nameplate. The nameplate information should be checked 
against the shipping memorandum.

Line and Ground Connections

Line and ground hardware are shipped unassembled to the 
arrester and will be contained inside the carton or crate. Install 
supplied line and ground terminals to the arrester as indicated 
on the outline drawing. Connect the arrester ground to the 
apparatus ground and the main station ground, utilizing a reliable 
common ground network of low resistance. Line connections 
should not place excessive mechanical stress on the arrester.

Installation Location

Install the arrester electrically as close as practicable to the 
equipment to be protected. Keep the arrester connections short 
and direct. The footings of all outdoor piers or supports should 
extend below the frost line and be elevated above the ground 
line sufficiently to meet personnel safety requirements.

Altitude and Temperature

EVP-series arresters can be used from 0 to 12,000 feet (3600m) 
altitude. These arresters can be used in locations where the 
maximum temperature does not exceed 60° C and where the 
weighted average temperature does not exceed 45° C. The 
minimum operating temperature is -60° C.

Mounting 

Ensure that all feet are firmly positioned before drawing down 
foundation bolts to avoid unnecessary stresses in the end fittings. 
Tighten the bolts firmly.

It is permissible to mount some lower voltage arresters 
horizontally. However, please consult your HPS sales 
representative to be sure that horizontal mounting is permissible 
for a particular arrester.

!

  

CAUTION

The equipment covered by these instructions should be installed and serviced only by competent personnel familiar with 
good safety practices. This instruction is written for such personnel and is not intended as a substitute for adequate training 
and experience in safe procedures.

!

  WARNING

Prior to installing this product, check the nameplate information to verify that it is the correct product for the 
application. Verify that the nameplate information corresponds to the information provided on the outline drawing.

!

  WARNING

EVP Arresters must be applied where the continuous 
phase-to-ground voltage at the arrester location does 
not exceed the arrester continuous voltage capability 
as indicated on the nameplate. Arrester physical size 
may not determine the voltage rating. Do not install 
arrester If type, rated voltage (Ur for IEC arresters) and 
maximum continuous operating voltage (Uc for IEC 
arresters) are not exactly the same on the nameplate 
and packaging labels.

Stud Size

Maximum Recommended 

Tightening Torque

3/8"

20 ft-lb (27 Nm)

1/2"

40 ft-lb (54 Nm)

3/4"

125 ft-lb (170 Nm)

EVP Series - Rev 05/2020

Reviews: