Installation Instructions
MX3431
Smart DC Remote Power Supply
The HySecurity Smart DC Remote Power Supply provides an optional power
source for Smart DC gate operators that are configured for solar-power. The kit
converts high voltage AC power into low voltage DC power which eliminates the
need for solar panels. Low voltage wire is run out to the gate operator while the
power supply remains in garage or shed plugged into the AC power source.
NOTE:
To install the Smart DC operator on site, follow the separate installation
instructions that accompany the gate operator.
To install the Smart DC Remote Power Supply, review the illustrations and the
steps found on the following pages.
Tools required
• Pliers for crimping
• Wire cutter
Power Cable and Wire Connections
Follow the steps to secure power connections. Wire size and appropriate distance
run to operator is shown in Table 1.
NOTE:
The Smart DC Remote Power Supply must be located in a cool, dry location.
Examples include: Off the floor in a garage or inside a weather tight shed.
Table 1: Wire Size to Maximum Run
Wire size*
Maximum Run
100% Duty Cycle
Maximum Run
50% Duty Cycle
Voltage Rating
for Direct Buried Cable
12 AWG
400 ft (122 m)
800 ft (244 m)
300V
14 AWG
250 ft (76 m)
500 ft (152 m)
300V
16 AWG
175 ft (53 m)
350 ft (107 m)
300V
*Other cable sizes not recommended.
12
1
Run a “two conductor” power cable from the
Smart DC Remote Power Supply location to the
HySecurity Smart DC gate operator.
SwingSmart operator
shown as reference only.
Trench and install in-ground cable.
To protect cable wire, conduit is
recommended.
Output of power supply internally set to 48VDC.
No adjustment can be made.