Summary of Contents for HiRun N50 Series

Page 1: ......

Page 2: ... only at high speeds but also low speeds in its driving characteristics Convenient for users through development of various optional products N50 Series name Applicable maximum motor rating 0 75 1 5 2 2 kW Input power rating single phase 200 V class 007 SF Model Number Information Motor kW Singlephase 200Vclass 0 75 1 5 2 2 Series Type ...

Page 3: ...E We build a better future C O N T E N T S Features 04 External Dimension Diagram 05 Operation 06 General Specifications 07 Function List 09 Protective Functions 14 Terminal Functions 15 Application Wiring Apparatus Option 16 Option 17 Proper Operation 18 ...

Page 4: ... by rapid speed restoration characteristics Applicable to the transfer machine treadmill industrial washing machine due to its function of momentary current suppression Possible to select various operation methods It is possible to select the operation methods of either RS485 communication driving or analog signal driving for the user s convenience Compact size for simplicity to install Reduction ...

Page 5: ...n Table External Dimension Diagram Type Weight kg External Dimension mm W H D Installation Dimension mm W H 80 142 135 70 130 M4 1 0 1 3 85 130 M4 95 142 135 007SF 015SF 022SF 80 142 135 V I RS 485 CM1 CM2 5 4 3 2 1 FM H L T1 O OI RUN FUNC STR STOP RESET MIN MAX L1 L2 P RB U V W 1 220V POWER A RUN PRG Hz 007SF 135 95 142 V I RS 485 CM1 CM2 5 4 3 2 1 FM H L T1 O OI RUN FUNC STR STOP RESET MIN MAX L...

Page 6: ...e A group appears A 01 appears Turn on the power Press the FUNC key Display A mode using the UP DOWN key Set the frequency using the UP DOWN key Press the FUNC key Press the STR key Press the FUNC key Press the UP key three times 0 0 or previously monitored value is displayed The motor rotates at the frequency set by the volume The motor stops Turn on the power Press the RUN key and adjust the vol...

Page 7: ...urve Operating current level setting possible 20 200 enable disable selection Operating current level constant enable disable selection DC 0 5 V or DC 0 10 V 4 20 mA 10 40 no freezing 90 RH or less non condensing 20 60 short term temperature during transport Indoors without corrosive gases flammable gases oil mist or dust Maximum 1000m or less above sea level 5 9 m s2 or less Forced cooling IP20 V...

Page 8: ...age Input selection of frequency setting current signal Self protection selection of start signal Contact input for when stopping the inverter with external terminal Thermal contact input for when stopping inverter with externally mounted thermal relay Control panel or external operation transition selection programmable V f control or sensorless vector control method selection programmable Multis...

Page 9: ...ip event Previous 1 trip event Previous 2 trip events Previous 3 trip events Trip accumulation count 0 00 99 99 Hz by 0 01 Hz 100 0 400 0 Hz by 0 1 Hz 0 1 999 9 sec by 0 1 sec 1000 3000 sec by 1 sec 0 1 999 9 sec by 0 1 sec 1000 3000 sec by 1 sec 0 forward 1 reverse Setting range A01 A65 Setting range b01 b17 Setting range C01 C23 Setting range H01 H15 10 0 10 0 Output frequency monitor Output cur...

Page 10: ... 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 5 10 00 Hz by 0 01 Hz 0 free run 1 deceleration stop 2 DC braking Frequency commanding RUN commanding Base frequency setting Maximum frequenc...

Page 11: ... 1 100 0 by 0 1 sec 0 0 100 sec by 0 1 sec 0 0 100 sec by 0 1 sec 0 1 1000 0 by 0 1 sec 0 current input 1 voltage input 0 constant on 1 constant off 2 off during deceleration 0 1 999 9 sec by 0 1 sec 1000 3000 sec by 1 sec 0 terminal 2CH 1 transition frequency A57 A58 0 00 400 0 Hz by 0 01 Hz 0 00 400 0 Hz by 0 01 Hz 0 linear 1 S curve 2 U curve 0 linear 1 S curve 2 U curve Voltage offset Voltage ...

Page 12: ... 0 Korea version 1 Europe version 2 US version 0 SUB reduced torque characteristic 1 CRT constant torque characteristic 0 overload overvoltage restriction mode OFF 1 overload restriction mode ON 2 overvoltage restriction mode ON 3 overload overvoltage restriction mode ON Deceleration rate when inverter restricts overload 0 1 10 0 sec by 0 1 sec 0 All parameters are locked when SFT from terminal is...

Page 13: ...requency setting PID deviation level setting 1 2 3 8 0 0 0 0 0 1 0 0 100 0 0 0 100 0 0 00 10 0 0 0 0 0 3 0 0 00 0 00 0 0 1 2 250 0 10 0 200 0 400 0 400 0 100 0 Hz Hz 0 NO 1 NC 0 output frequency 1 output current 2 output voltage 0 45 250 220 by 1 3 0 10 0 by 0 1 0 5 inverter rated current 2 0 inverter rated current 0 0 400 Hz by 0 01 Hz 0 100 by 0 01 0 5 0 NO 1 NC 0 NO 1 NC 0 NO 1 NC 0 NO 1 NC 0 N...

Page 14: ...OM error External trip Temperature trip Function Display Standardoperator Remoteoperator Description When the inverter output current exceeds the rated current by more than approximately 200 while the motor is locked or reduced in speed the protection circuit activates halting inverter output When the inverter output current causes the motor to overload the electronic thermal trip in the inverter ...

Page 15: ... Output frequency meter output current meter output voltage meter Power supply for frequency setting Voltage frequency command signal Current frequency command signal Common terminal for frequency command Intelligent output terminal Run status signal RUN frequency arrival signal FA1 Set frequency arrival signal FA2 overload advance notice signal OL PID error deviation signal OD and alarm signal AL...

Page 16: ... power capacity exceeds 500 kVA or when a sudden power voltage variation occurs It also helps to improve the power factor Vibration may increase when driving a general purpose motor with an inverter as compared with commercial power operation Connecting this reactor between the inverter and the motor allows reduction of motor pulsation When the cable between the inverter and the motor is 10 m or m...

Page 17: ...UN FUNC STR STOP RESET POWER RUN PRG A Hz STOP RESET key This key is use for stopping the motor or resetting errors RUN LED On when the inverter is running Power LED On when the inverter power is inputted Display part LED display Displays frequency motor current motor rotation speed alarm history and setting value RUN key Press this key to run the motor This key works only when LED is on FUNCTION ...

Page 18: ...motor base Under continuous low speed operation oil lubrication can deteriorate in a power transmission mechanism with an oil type gear box gear motor or reducer Consult the motor manufacturer for the permissible range of continuous speed To operate at more than 60 Hz confirm the machine s ability to withstand the centrifugal force generated Application to General Purpose Motors Run or stop of the...

Page 19: ...ernal chemical reaction it should normally be replaced every five years Be aware however that its life expectancy becomes considerably shorter when the inverter is subjected to such adverse factors such as high temperature or heavy load exceeding the rated current of the inverter Also consumable parts such as cooling fans should be replaced according to the inverter periodic inspection of the main...

Page 20: ... Grove London W6 0LG UK Tel 44 20 8741 0501 Fax 44 20 8741 5620 Tokyo 8th Fl Yurakucho Denki Bldg 1 7 1 Yuraku cho Chiyoda gu Tokyo 100 0006 Japan Tel 81 3 3212 2076 3215 7159 Fax 81 3 3211 2093 Osaka I Room 5th Fl Nagahori Plaza Bldg 2 4 8 Minami Senba Chuo Ku Osaka Japan 542 0081 Tel 81 6 6261 5766 5767 Fax 81 6 6261 5818 Dubai Level 2 Unit 205 Emaar Square Bldg 4 Sheikh Zayed Road P O Box 25245...