ETH-1000 Chillgard LC Quick Start Guide for BACnet
MS/TP
This document provides a brief overview of the connections and settings that must be used to connect a
preconfigured ETH-1000 gateway to a MSA Chillgard LC Refrigerant Monitor. This document also contains the
BACnet object mapping for the application and some troubleshooting tips. For more information, please refer to
the ETH-1000 User’s Manual available at
http://www.iccdesigns.com/products/millennium/eth-1000.html
.
Wiring
Power Supply Wiring
A 7 – 24V DC power supply must be connected to the gateway’s terminal block at terminals TB:5 (POWER) and
TB:6 (GND) as highlighted in Figure 2.
Figure 1: Terminal Block Power Supply Connections