GW-7552  PROFIBUS/MODBUS  GATEWAY  Quick  Start  User  Guide

 (Version 1.00)      

PAGE

 

Quick Start User Guide 

1. Introduction   

This manual introduces the GW-7552's basic setting and operating quickly, the user 
can  refer  to  the  user  manual  in  the  ICP  DAS  companion  CD-ROM  (Path: 
“CD:\PROFIBUS\Gateway\GW-7552\ manual\GW-7552 user manual.pdf”). 
This manual helps users to understand about the GW-7552 module and application. 
In the following examples the CIF50-PB PROFIBUS  master card from  Hilscher is 
used.  The  configuration  and  communication  is  done  by  the  program  “SyCon” 
provided by Hilscher.

 

 

Application example of PROFIBUS to Modbus 

In this example the GW-7552 acts as a Modbus slave device.  When the GW-7552 
module receives a write DO Modbus command from PC’s COM Port, the GW-7552 
module  can  send  the  message  to  the  input  data  area  of  PROFIBUS  master  station. 
When the GW-7552 module receives a read DI Modbus command from PC’s COM 
Port,  GW-7552  module  can  refer  to  the  output  data  area  of  PROFIBUS  master 
station to produce response message and send it to PC’s COM Port. 
 

2. Hardware configuration 

         

                         

       

   

 

 

RS232 connection 

 

Power connection 

 

GW-7552 PRIFIBUS/MODBUS GATEWAY 

Summary of Contents for GW-7552

Page 1: ...cher is used The configuration and communication is done by the program SyCon provided by Hilscher Application example of PROFIBUS to Modbus In this example the GW 7552 acts as a Modbus slave device W...

Page 2: ...he dip switch can be seen by open the cover as shown in the below The range of dip switch is 0 126 here we set GW 7552 module s dip switch to 1 LED status indicator LED Status Description flash When t...

Page 3: ...rom the CD of the GW 7552 module into the Profibus configuration tool File CopyGSD Directory CD PROFIBUS GATEWAY GW 7552 GSD the example of how to load GSD file Here we use the hilscher CIF50 PB PROFI...

Page 4: ...er to user manual section 4 3 The Configuration of the common parameters Click Parameter Data button to enter the Parameter Data dialog Double click the GW 7552 s icon to enter the Slave configuration...

Page 5: ...ut Relay Coil 1 32 Bytes Output Register 1 64 Words Input module Input Relay Coil 1 32 Bytes Input Register 1 64 Words In this example we configure a system setting module an Output Relay Coil 2 Byte...

Page 6: ...rned on That shows the GW 7552 working in the data exchange mode Click Online Download to download the setting into PROFIBUS master station 5 GW 7552 module communication test This demo uses utility M...

Page 7: ...low Send modbus command output data FF FF Receive 0xFF in input data area of Profibus master station Module Byte Data type Representation Value Input 0 Byte Hex 0xFF Input module Input 1 Byte Hex 0xFF...

Page 8: ...d button to send Modbus command again Then MBRTU can receive response message 01 02 02 FE DC F8 41 In this message the user can know the value of DI0 DI1 have changed into 0xFE 0xDC in the GW 7552 as...