background image

Summary of Contents for N9MSE

Page 1: ...personal injury SAFETY CONSIDERATIONS 3 INTRODUCTION 4 CODES AND STANDARDS 4 ELECTROSTATIC DISCHARGE ESD PRECAUTIONS 5 DIMENSIONS NEW 6 7 12 6 LOCATION 7 LOCATION RELATIVE TO COOLING EQUIPMENT 9 AIR...

Page 2: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS 4 INSPECTION The...

Page 3: ...ollow all warnings or cautions included in literature and attached to the unit CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs U...

Page 4: ...y affect reliability of heat exchangers motors and controls See Figure 1 The furnace should be sized to provide 100 percent of the design heating load requirement plus any margin that occurs because o...

Page 5: ...ONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY S ELECTROSTATIC CHARGE TO GROUND 2 Firmly touch the clean unpainted metal surface of the furnace chassis which is close to the control Tools held...

Page 6: ...8 SIDE INleT _ 7 8 RMOSTAT ENTRY BOTTOM iNLET 215 8_ IS4_ S 263 8 _ 51_ 01 26 5 16 _ e SD5060 4 Rev F N9MSB FURNACESIZE B OUTLET WIDTH D A CABINET WIDTH 14 3 16 361 14 3 16 361 17 1 2 445 17 1 2 445 2...

Page 7: ...ace must be installed so the electrical components are protected from water not be installed directly on any combustible material other than wood flooring refer to SAFETY CONSIDERATIONS be located clo...

Page 8: ...t 18 in 457 mm above the floor The furnace must be located or protected to avoid damage by vehicles When the furnace is installed in a public garage airplane hangar or other building having a hazardou...

Page 9: ...9 3 of the NFPA 54 ANSI Z223 1 2009 Air for Combustion and Ventilation and applicable provisions of the local building codes Canadian Installations Part 8 of CAN CSA B149 1 2010 Venting Systems and A...

Page 10: ...r greater than 0 10 ACH Infiltration rates greater than 0 60 ACH shall not be used The minimum required volume of the space varies with the number of ACH and shall be determined per Table 4 or Equatio...

Page 11: ...the Outdoor Combustion Air Method mentioned previously and Outdoor openings shall be sized as follows Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion Ai...

Page 12: ...necessary to relocate the condensate trap or associated tubing Refer to Figure8 for upflow condensate trap information Refer to Condensate Drain section for information how to install the condensate...

Page 13: ...ts of the collector box _ Connect relief tube to port on collector box _ Rotate elbow to desired position and tighten clamp to 15 lb in _ Slide tube in stand offs to adjust length Connect the new pres...

Page 14: ...between the casing side and the furnace platform for the trap to extend out of the casing in the horizontal position Allow at least 1 4 in per foot 20mm per meter of slope down and away from the furna...

Page 15: ...y vary in appearance Unconverted Factory Configuration as viewed in the Horizontal Left Orientation Remove the screw that secures the condensate trap to the collector box and remove trap If alternate...

Page 16: ...precautions MUST be made if installing furnace in an area which may drop below freezing This can cause improper operation or damage to the equipment If the furnace environment has the potential of fre...

Page 17: ...fter inserting the Z pipe through the casing slide a spring clamp over each end of the Z pipe 8 From inside the casing insert the short end of the formed grommet cut from the rubber drain elbow throug...

Page 18: ...he outlet stub on the drain elbow 10 Connect additional condensate piping to a code approved drain or to a condensate pump approved for use with acidic furnace condensate and compatible with mineral a...

Page 19: ...stance or a probe can be inserted for sampling the air stream The cover attachment shall prevent leaks Connect supply air duct to flanges on furnace supply air outlet Bend flange upward to 90 with wid...

Page 20: ...ace must be pitched as shown in Figure 18 for proper condensate drainage Supply Air Connections NOTE For downflow applications this furnace is approved for use on combustible flooring when any one of...

Page 21: ...wn in Figure 27 DO NOT cut into casing sides left or right Bypass humidifier connections should be made at ductwork or coil casing sides exterior to furnace See Figure 27 FIRE HAZARD A failure to foll...

Page 22: ...le or Noncombustible Flooring 19 1 2 21 5 8 20 1 8 22 1 4 subbase not required 495 549 511 565 Downflow Applications on Noncombustible Flooring 19 3 8 19 20 19 5 8 21 subbase not required 492 483 508...

Page 23: ...nace can be hung from floor joists rafters or trusses or installed on a non combustible platform blocks bricks or pad Suspended Furnace Support The furnace may be supported under the entire length of...

Page 24: ...e casing side to attach supply air duct humidifier or other accessories All supply side accessories MUST be connected to duct external to furnace main casing Return Air Connections The return air duct...

Page 25: ...er for additional assembly and installation options Filter and Return Duct Sizing Pressure drop must be taken into account when sizing filters filter racks IAQ devices and associated system ductwork S...

Page 26: ...in 2 5 cm 1 in 2 5 cm 2 in 5 cm 1 in 2 5 cm 5 cm 0 03 9 0 05 12 0 07 18 O 17 43 28 0 04 11 0 06 16 0 09 24 0 22 55 37 0 05 13 0 08 20 0 12 31 0 27 68 47 0 06 15 0 10 24 0 15 38 58 0 06 16 O 11 29 O 18...

Page 27: ...Y AIR 24 NOTE RESTRICTION SAME FOR HORIZONAL HORIZONAL LEFT RETURN AIR RESTRICTIONS RETURN AIR SIDE RETURN AIR NOT PERMITTED FOR 2000 CFM AND ABOVE OF AIR FLOW L10F034 External Figure 30 Filter Cabine...

Page 28: ...ded Maintain a 1 in 25 mm clearance from combustible materials to supply air ductwork for a distance of 36 in 914 mm horizontally from the furnace See NFPA 90B or local code for further requirements R...

Page 29: ...ide the furnace Table 10 Maximum Capacity of Pipe NOMINAL INTERNAL LENGTH OF PIPE FT a IRONPIPE SIZE DIA 10 2O 30 40 50 IN MM IN MM 3 0 6 0 9 1 12 1 15 2 1 2 13 0 622 158 175 120 97 82 73 3 4 19 0 824...

Page 30: ...he limitations of 63 F 33 C rise ELECTRICAL SHOCK AND FIRE HAZARD Failure to follow this warning could result in personal injury death or property damage The cabinet MUST have an uninterrupted or unbr...

Page 31: ...If field supplied manual disconnect switch is to be mounted on furnace casing side select a location where a drill or fastener cannot damage electrical or gas components The J Box is used when field...

Page 32: ...CSA C22 1 Figure 38 I Field Supplied Electrical Box on Furnace Casing GROUNU NEUTRAb A10141 Power Cord Installation in Furnace J Box NOTE Power cords must be able to handle the electrical requirements...

Page 33: ...to operate on a utility generated power which has a smooth sinusoidat waveform If the furnace is to be operated on a generator or other alternate power supply the alternate power supply must produce...

Page 34: ...Y COMPONENT TEST TERMINAL 24 V THERMOSTAT TERMINALS J2 JUMPER 8 AMP FUSE LED OPERATION DIAGNOSTIC LIGHT 115 VAC L2 NEUTRAL CONNECTIONS _ _ BLOWER SPEEE SELECTION TERMINALS TES _W rl HUM _ HUMIDIFIER T...

Page 35: ...ce standard Au Canada I appr_t et le ciment doivent _tre du m_me fabricant que le systeme d evacuation L appr_t GVS 65 Purple et le ciment solvant GVS 65 doivent _tre utitise avec les Royal Pipe Syst...

Page 36: ...M G DuraVent PolyPro polyproplylene venting systems are ULC S636 listed NOTE When using polypropylene venting systems all venting materials used including the vent terminations must be from the same m...

Page 37: ...pipe to the outdoors is not required for a single pipe vent system A 12 in 304 mm long pipe with a 2 in 50 mm Nominal Dimension ND tight radius 90 degree elbow is required to be attached to the combu...

Page 38: ...er Al1314 SOLVENT CEMENT AND PRIMERS Solvent Cement Solvent Cement Solvent Cement Primer Figure 42 DESCRIPTION Schedule 40 Schedule 40 For ABS SDR 21 SDR 26 Schedule 40 Schedule 40 For PVC DWV at Sche...

Page 39: ...peration could result in carbon monoxide poisoning or death For all venting configurations for this appliance and other gas appliances placed into operation for the structure provisions for adequate c...

Page 40: ...for terminations approved for use in Alberta and Saskatchewan Figure 44 ITee at Termination Outlet I OPTIONALTERMINATION BRACKETFOR2 PIPE TERMINATIONS _ 12 in 30 48 cm Above anticipated snow level L12...

Page 41: ...he first 2 vents Third vent and fourth vent if used must be 36 in Away 914mm L12F044 Figure 48 Vent Pipe Termination for Non Direct Vent and Ventilated Combustion Air System Roof Termination Preferred...

Page 42: ...entric vent terminations or pipe lengths and elbows used for standard vent terminations see vent termination figures associated with Table14 do not require a deduction from the Maximum Equivalent Vent...

Page 43: ...eed total allowable pipe length as calculated from Table 14 through Table 16 Configure the Furnace CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or de...

Page 44: ...stten air o_r_actten Rotate vent elbow to required position d2b_ UPFLOW LEFT VENT CONFIGURATION Representative drawing only some models may vary in appearance Al1309 Upflow Configurations CONTINUED An...

Page 45: ...ONFIGURATION Representative drawing only some models may vary in appearance Horizontal Left Configurations CONTINUED ALTERNATE COMBUSTION AIR A11328 HORIZONTAL LEFT LEFT VENT CONFIGURATION Representat...

Page 46: ...ructions CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death DO NOT use cement to join polypropylene venting systems Follow the polypropylene venti...

Page 47: ...e 47and Figure 48 Alberta Figure 44 and Figure 46 For ventilated combustion air terminations refer to Figure 48 Alberta Figure 44 and Figure 46 19 Use appropriate methods to seal openings where combus...

Page 48: ...sulation or other materials to accumulate inside of pipe assembly when installing it through hole Disassemble loose pipe fittings Clean and cement using same procedures as used for system piping DO NO...

Page 49: ...pe fittings Clean and cement using same procedures as used for system piping DO NOT CEMENT POLYPROPYLENE FITTINGS Direct Vent Two Pipe System ONLY When two or more furnaces are vented near each other...

Page 50: ...ipe hangar _ 76 mm t Ventilated Combustion Air 12 305 mm intake termination in crawl space CRAWL SPACE Figure 57 l Attic Vent Termination Vent throuhgb__ _ roof flashing Ventilated Combustion Air inta...

Page 51: ...veranda porch deck or balcony Permittedonly if veranda porch deck or balconyis fully openon a minimumof two sides beneaththe floor Manufacturer sRecommendation See Notes3 8 Clearanceto each side of th...

Page 52: ...in 305 ram See Note4 Clearanceundera veranda porch deck or balcony Permittedonly if veranda porch deck or balcony isfully open on a minimumof two sides beneath thefloor Manufacturer sRecommendation Se...

Page 53: ...120 000 83 25 3 217 66 1 140 0004 69 21 0 146 44 5 See notes at end of Venting Tables See Table 16 for altitudes over 4500 ft 1370m Figure 60 _Elbows Configurations MEDIUM MITERED LONG L11 F082 Figure...

Page 54: ...0 long radius elbows and a polypropylene concentric vent kit Also includes 20 feet 6 1 M of flexible polypropylene vent pipe included within the 100 feet 30 M of vent pipe Assume that one meter of fle...

Page 55: ...32 9 8 I 10 3 0 I 121 I 36 9 I 130 39 6 I 7 2 1 I 82 1 25 o 1 152 46 3 168 51 2 35 1 10 7 1 111 33 8 148 45 1 67 20 4 157 47 9 56 17 1 23 7 0 I 5 1 5 I 110 I 33 5 I 115 35 1 76 I 23 2 I 142 43 3 156...

Page 56: ...99 89 78 N A 25 110 233 265 N A 25 110 235 229 20 10 M N A 7 6 30 2 27 1 23 8 N A 7 6 33 5 71 O 80 8 N A 7 6 33 5 71 6 69 8 Ft N A 25 55 46 33 N A 25 110 145 117 N A 25 110 173 140 0 20 M N A 7 6 16...

Reviews: