Page 1: ...Installation Instructions SINGLE PACKAGE HEAT PUMPS PHF HPFM Series 3 to 5 TON Three Phase 515 01 1102 O0 10 25 01 Printed in U S A...
Page 2: ...ch COULD result in minor personal injury or product or property damage Signal Words in Manuals The signal word WARNING is used throughout this manual in the following manner The signal word CAUTION is...
Page 3: ...4 BASE RAIL SUPPLY 19 I 1 9 16 2 3 16 12 1 4 BASE RAIL 19 RETURN 3 3 4 46 1 4 Condensate Drain 2 3 16 UNIT SIZE A B C 3 Ton 29 1 2 47 1 2 47 1 2 4 TO5 Ton 37 1 2 47 1 2 47 1 2 Measured from inside to...
Page 4: ...nstruction or materials While minimum clearances are acceptable for safety reasons they may not allow adequate air circulation around the unit for proper operation in the cooling mode Whenever possibl...
Page 5: ...on the horizontal return and supply air openings 3 Install roof curb on the building Be sure to follow all directions included with curb and all applicable building codes in your installation Condens...
Page 6: ...tatDiagram Low Voltage Electronic Thermostat Subbase _ White Rodgers 1F92 71 and 1F94 71 P 1 f 1 2 3 I 1 l C G R O1 YI Wl W21 Ell I I I If _ _ I I I Jumper Wire C 1_ 61 _ 11 V_I V_ 21 Com Fan 24V Rev...
Page 7: ...erminal of the 24V control transformer 5 Replace the electrical access panel Final Electrical Check Make a final wiring check to be sure system is correctly wired Inspect field installed wiring and th...
Page 8: ...ead to premature failure of components This will also adversely affect dayto day unit performance Refer to unit rating plate for proper Electric Heat Accessory sizing and see the Temperature Rise Chec...
Page 9: ...Cooling Heating Heat Pump and Auxiliary Electric Strip Heat NOTE The cooling heat pump and strip heat airflows are all on the same speed tap The refrigerant system requires the same specific CFM for...
Page 10: ...he compressor and condenser fan will de energize immediately The evaporator blower motor will have a delay off and will de energize after 30 seconds Defrost Mode Energized R G Y1 De energized 0 Defros...
Page 11: ...CONTROL CONT CONTACTOR 0 DENOTES SPLICE SHOCK HAZARO OiSCONNEC1 POWER BEFORE SERVICING 3 SPEED r n v_v FROM u BL _ UNIT CDNT BLOWER _ IFMcFROM MOTOR HI c BK MED c o_ _ _ LO c HTR SPEED HI TAP CONN 3...
Page 12: ...ning can result in prop erty damage personal injury and or death To adjust defrost interval 1 Turn off all power to Heat Pump 2 Remove control box cover 3 Locate electronic control board 4 The Control...
Page 13: ...1 Typical Branch Duct Dampers Air Filters Condenser Coil and Condensate Drain Maintenance Refer to Home Owners Manual supplied with your heat pump for information on filter sizes condenser coil clear...
Page 14: ...RE 10 l Blower Motor and Housing FIGURE 1i Wire Colors Circulating Air Blower Visually inspect the blower wheel for accumulations of dirt or lint Clean the compartment and the blower wheel If ac cumul...
Page 15: ...Warranty DOES NOT COVER any labor material refractory chambers oii nozzles refrigerant refrigerant inspection and refrigerant reclaiming freight and or handling charges associated with any repair or r...
Page 16: ...CAC4 KAC0 TCA0 TCA2 TCA4 HHP0 HHP2 HHP4 CliP0 CliP2 CliP4 TCH0 TCH2 TCH4 PGME PYMC PHAD PGAD PA95 PAPC PAK APK Tothe original purchaser a replacement for 10 years from original date of installation o...