background image

Operating instructions

Relay plug (2 NC)

DP1613

11441564 / 00   11 / 2022

GB

Summary of Contents for DP1613

Page 1: ...Operating instructions Relay plug 2 NC DP1613 11441564 00 11 2022 GB ...

Page 2: ...Safety instructions 4 3 Intended use 5 3 1 Application example 5 4 Installation 6 5 Electrical connection 7 5 1 Input side 7 5 2 Output side 7 5 3 Connecting the device 8 5 3 1 Mounting the connector 9 5 3 2 Removing the connector with vibration protection 9 6 Operation 10 7 Troubleshooting 11 8 Maintenance repair and disposal 12 ...

Page 3: ...sult Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Warnings used ATTENTION Warning of damage to property CAUTION Warning of personal injury w Slight reversible injuries may result 1 3 Safety symbol on the device Safety symbol on the device u Adhere to the operating instructions f...

Page 4: ...the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Ò Intended use If the operating instructions or the technical data are not adhered to personal injury and or damage to property may occur The manufacturer assumes no liability or wa...

Page 5: ...hapters Installation and Electrical connection 3 1 Application example 2 3 4 1 2 2 1 1 4 3 4 OUT1 IN1 IN2 OUT2 L1 L L L 2 IN1 4 IN2 2 OUT1 4 2 4 OUT2 3 L 1 L 3 L2 L 3 1 L1 L 1 L1 L DP1613 Fig 1 Signalling device with own power supply 1 Control systems 2 Y cable 3 Power supply for supplying the outputs SELV PELV 4 Load 4 5 6 2 2 1 1 4 3 4 OUT1 IN1 IN2 OUT2 L1 L L L 2 OUT1 4 2 4 OUT2 3 L2 L 3 L 3 1 ...

Page 6: ...e corresponding protective caps ATTENTION No protection rating no protection of the contacts without mounted connectors protective caps w Inadmissible soiling moisture possible w Disconnection of circuits safety possibly impaired w Before installation when replacing the device maintain pollution degree 2 u Disconnection safety guaranteed u Install the device so that the M12 connection parts and th...

Page 7: ... wiring has to be carried out in a way that ensures the required separation from other circuits 5 1 Input side Operating voltage SELV PELV CAUTION The input current of the operating voltage is not limited w No fire protection u Protect the circuit u Protect the sensor supply via the same fuse Potential M12 connector Fuse L supply voltage Pin 1 2 A Required tripping characteristic of the fuse Tfuse...

Page 8: ...fast acting total current with common protection 1 A Capacitive loads are not permitted opto semiconductor relay Max switching frequency of the outputs 1 Hz 5 3 Connecting the device u Disconnect power u Connect the unit as follows 2 1 4 3 2 1 3 1 2 4 5 Fig 5 Electrical connection 1 4 pole M12 connector Input side Pin 1 L Operating voltage Pin 2 IN1 Digital input 1 Pin 3 L Operating voltage Pin 4 ...

Page 9: ... rating u Use connectors with gold plated contacts u During installation place the connectors vertically so that the coupling nut will not damage the thread u Observe the coding of the connectors during installation If connector in the device u Tighten the cable sockets according to the torque specifications indicated by the cable manufacturer Maximum permissible tightening torque 1 3 0 1 Nm If so...

Page 10: ...DP1613 Relay plug 2 NC 10 6 Operation After power on the device is ready for operation It switches the outputs according to the incoming input signals ...

Page 11: ...C DP1613 11 7 Troubleshooting Error Root issue Troubleshooting The output does not switch Supply voltage too low at the input side Apply correct supply voltage at the input side No input signal Apply the input signal ...

Page 12: ... possible to repair the unit u After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations Cleaning the unit u Disconnect the unit from the voltage supply u Clean the unit from dirt using a soft chemically untreated and dry micro fibre cloth ...

Reviews: