PO Box 15732, Brooksville, FL 34604 - Phone: 888-987-8877/850-654-5559, Fax 850-654-3844
www.surgesuppression.com
2018 SSI
®
. Rev Date 10/4/2018
Page
1
of
2
SS05975
“
“
Description:
Parallel connected, AC power Surge Protective Device.
Application:
Designed for use at ANSI/IEEE C62.41.1 & C62.41.2 location
categories C, B and A. Designed to protect critical and sensitive
loads fed from individual disconnects, sub panels, distribution
panels and service entrance locations.
Warranty:
15 Years
Unit Listings:
Listed to ANSI/UL 1449-2006 4
th
Edition by UL (E315947), CSA
(MC#241804); UL1283
Circuit Design:
Parallel connected, multi-stage hybrid Frequency Responsive
Circuitry circuit design incorporating discrete all mode protection
and both component level thermal fusing and internal over-current
fusing. All protection circuits are encapsulated in our high dielectric
compound to promote long component life and protection from the
weather and vibration.
Protection Modes:
All Mode - L-L, Discrete L-N (Normal Mode), and Discrete L-G,
N-G (Common Mode).
Input Frequency:
50-60 Hz (60 Hz typical)
Insertion Loss Data:
(L-N for 3Y1)
Frequency:
Attenuation:
10 kHz
14 dB
100 kHz
38 dB
1 MHz
21 dB
Max Attenuation & Freq.
52 dB @ 148 kHz
Circuit Diagnostics:
LED, 1 per phase, normally on. See pg. 2 for additional diagnostics
options
Connection/mounting:
#10 Wire (pre-installed), hub (pre-installed on base models,
installed at time of installation on optional enclosures) and integral,
multi-point mounting feet.
Circuit Interrupt:
Internal component-level, thermal fusing and patented circuit board
mounted, over-current fusing. No external over-current protection
required. (Note: National and local codes may require the use of a
circuit interrupt device(s) if conduit is added to make the wired
connection to the panel or gear.) SCCR = 200 kA
Nominal Discharge
Current (I
n
) Rating:
10 kA (CSMA40); 20 kA (CSMB40**) (
**
Complies with the requirements
of UL 96A Master Label for Installation Requirements for Lightning
Protection Systems
)
Accessory Units:
EACS =
(External Alarm, Dry Relay Contact, LEDs and Surge
Counter) Stand alone enclosure (battery powered, mute and test
switch, surge counter reset and reset disable).
Other combinations are available (i.e. EAC, ES, ECS, etc.).
Designed specifically for new construction, “bid spec” market place, the CSM series
of Surge Protective Devices provides the features, performance and value required
by discriminating specifying engineers. This device is intended for protection of
critical and sensitive load applications ranging from individual equipment
disconnects, sub panels and distribution panels to service entrances. It is extremely
effective in limiting lightning surges as well as internally generated transients.
The CSM series provides an effective blend of leading edge suppression design
technology, straight forward, no frills engineering and customer driven, value added
options. Specify the CSM with confidence.
Key Features:
Industry Leading Measured
Limiting Voltage Performance
EMI/RFI Parallel Configured
listed to UL 1283
Independent Verification of
Performance and Safety
Component-Level, Thermal
Fusing and Over-Current
Fusing
No moving parts or springs - No
mechanical or electro-
mechanical thermal/over-
current protection
Circuit Encapsulation
15 Year Warranty
Voltage
Code
ANSI/UL 1449 (Fourth Edition)
Voltage Protection Rating (VPR)
L-N
HL-N
L-G
HL-G
N-G
L-L
HL-L
1P1
600
-
600
-
600
-
-
1S1
600
-
600
-
600
1200
-
3Y1
600
-
600
-
600
1200
-
3D1
600
1000
600
1000
600
1200
1800
3Y2
1000
-
1000
-
1000
2000
-
3N4
-
-
1800
-
-
1800
-
CSMx40 Series
400 kA Per Phase
Peak Surge Current
ANSI/UL1449 UL Fourth Edition
A = Type 2 SPD, I
n
= 10 kA
B = Type 2 SPD, I
n
= 20 kA