SS05975

 

 

 

 

 

 

 

 

 

 
“ 

“ 

 

 

 

 

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 

 
 
 
 
 
 
 
 
 
 
 
 
 
  
 
 
 
 
  

 

 
  
 
 
 
 
 

 
 
 
 
 
 

Description:

 

Parallel connected, AC power Surge Protective Device. 

Application:

 

Designed for use at ANSI/IEEE C62.41.1 & C62.41.2 location 
categories C, B and A. Designed to protect critical and sensitive 
loads fed from individual disconnects, sub panels, distribution 
panels and service entrance locations. 

Warranty: 

15 Years  

Unit Listings: 

Listed to ANSI/UL 1449-2006 4

th

 Edition by UL (E315947), CSA 

(MC#241804); UL1283

 

Circuit Design:

 

Parallel connected, multi-stage hybrid Frequency Responsive 
Circuitry circuit design incorporating discrete all mode protection 
and both component level thermal fusing and internal over-current 
fusing. All protection circuits are encapsulated in our high dielectric 
compound to promote long component life and protection from the 
weather and vibration. 

Protection Modes:

 

All Mode - L-L, Discrete L-N (Normal Mode), and Discrete L-G,  
N-G (Common Mode). 

Input Frequency:

 

50-60 Hz (60 Hz typical) 

Insertion Loss Data:    
(L-N for 3Y1)

 

Frequency: 

Attenuation: 

10 kHz 

14 dB

 

100 kHz 

38 dB

 

1 MHz 

21 dB

 

Max Attenuation & Freq. 

52 dB @ 148 kHz

 

Circuit Diagnostics:

 

LED, 1 per phase, normally on. See pg. 2 for additional diagnostics 
options  

Connection/mounting: 

#10 Wire (pre-installed), hub (pre-installed on base models, 
installed at time of installation on optional enclosures) and integral, 
multi-point mounting feet.  

Circuit Interrupt:

 

 

Internal component-level, thermal fusing and patented circuit board 
mounted, over-current fusing.  No external over-current protection 
required.  (Note: National and local codes may require the use of a 
circuit interrupt device(s) if conduit is added to make the wired 
connection to the panel or gear.) SCCR = 200 kA   

Nominal Discharge 
Current (I

n

) Rating: 

10 kA (CSMA40); 20 kA (CSMB40**) (

**

Complies with the requirements 

of UL 96A Master Label for Installation Requirements for Lightning 
Protection Systems

)

 

Accessory Units: 

EACS = 

(External Alarm, Dry Relay Contact, LEDs and Surge 

Counter) Stand alone enclosure (battery powered, mute and test 
switch, surge counter reset and reset disable). 
Other combinations are available (i.e. EAC, ES, ECS, etc.). 

Designed specifically for new construction, “bid spec” market place, the CSM series 
of Surge Protective Devices provides the features, performance and value required 
by  discriminating  specifying  engineers.  This  device  is  intended  for  protection  of 
critical  and  sensitive  load  applications  ranging  from  individual  equipment 
disconnects, sub panels and distribution panels to service entrances. It is extremely 
effective in limiting lightning surges as well as internally generated transients.  
 
The  CSM  series  provides  an  effective  blend  of  leading  edge  suppression  design 
technology, straight forward, no frills engineering and customer driven, value added 
options. Specify the CSM with confidence. 

 

 

Key Features: 

 

 

Industry Leading Measured  

     Limiting Voltage Performance 

 

EMI/RFI Parallel Configured 

listed to UL 1283 

 

Independent Verification of 

Performance and Safety 

 

Component-Level, Thermal 

Fusing and Over-Current 

Fusing 

 

No moving parts or springs - No 

mechanical or electro-

mechanical thermal/over-

current protection 

 

Circuit Encapsulation  

 

15 Year Warranty 

 

 

 

 

Voltage 

Code

 

ANSI/UL 1449 (Fourth Edition) 

Voltage Protection Rating (VPR)

 

L-N 

HL-N 

L-G 

HL-G 

N-G 

L-L 

HL-L 

1P1 

600 

600 

600 

1S1

 

600 

600 

600 

1200 

3Y1

 

600 

600 

600 

1200 

3D1 

600 

1000 

600 

1000 

600 

1200 

1800 

3Y2

 

1000 

1000 

1000 

2000 

3N4 

1800 

1800 

 

CSMx40 Series 

400 kA Per Phase 

Peak Surge Current

 

ANSI/UL1449 UL Fourth Edition

 

A = Type 2 SPD, I

n

 = 10 kA 

B = Type 2 SPD, I

n

 = 20 kA 

Reviews: