Model 686B0X-0003

Smart Vibration Switch

Installation and Operating Manual

For assistance with the operation of this product,

contact PCB Piezotronics, Inc.

Toll-free: 800-959-4464

24-hour SensorLine: 716-684-0001

Fax: 716-684-3823

E-mail: imi@pcb.com

Web: www.imi-sensors.com

Summary of Contents for 686B0X-0003

Page 1: ... Switch Installation and Operating Manual For assistance with the operation of this product contact PCB Piezotronics Inc Toll free 800 959 4464 24 hour SensorLine 716 684 0001 Fax 716 684 3823 E mail imi pcb com Web www imi sensors com ...

Page 2: ...ity regimen When in doubt about a calibration cycle a good rule of thumb is to recalibrate on an annual basis It is also good practice to recalibrate after exposure to any severe temperature extreme shock load or other environmental influence or prior to any critical test PCB Piezotronics maintains an ISO 9001 certified metrology laboratory and offers calibration services which are accredited by A...

Page 3: ...urchase Order should include authorization to proceed and return at current pricing which can be obtained from a factory customer service representative Contact Information International customers should direct all inquiries to their local distributor or sales office A complete list of distributors and offices can be found at www pcb com Customers within the United States may contact their local s...

Page 4: ... O PCB板 X O O O O O 电气连接器 O O O O O O 压电晶体 X O O O O O 环氧 O O O O O O 铁氟龙 O O O O O O 电子 O O O O O O 厚膜基板 O O X O O O 电线 O O O O O O 电缆 X O O O O O 塑料 O O O O O O 焊接 X O O O O O 铜合金 黄铜 X O O O O O 本表格依据 SJ T 11364 的规定编制 O 表示该有害物质在该部件所有均质材料中的含量均在 GB T 26572 规定的限量要求以下 X 表示该有害物质至少在该部件的某一均质材料中的含量超出 GB T 26572 规定的限量要求 铅是欧洲RoHS指令2011 65 EU附件三和附件四目前由于允许的豁免 CHINA RoHS COMPLIANCE ...

Page 5: ...te O O X O O O Wires O O O O O O Cables X O O O O O Plastic O O O O O O Solder X O O O O O Copper Alloy Brass X O O O O O This table is prepared in accordance with the provisions of SJ T 11364 O Indicates that said hazardous substance contained in all of the homogeneous materials for this part is below the limit requirement of GB T 26572 X Indicates that said hazardous substance contained in at le...

Page 6: ...ONITORING 686 Series Smart Vibration Switch Operating Guide with Enclosed Warranty Information 3425 Walden Avenue Depew New York 14043 2495 Phone 716 684 0003 Fax 716 684 3823 Toll Free Line 1 800 959 4IMI MANUAL NUMBER 40112 MANUAL REVISION D ECN NUMBER 47032 ...

Page 7: ...ectromechanical Relay Automatic Machinery Shutdown Using External Electromechanical Relay While Monitoring 2 Axes Switch and External Latching for Automatic Machinery Shutdown Both Alarm Siren and Automatic Machinery Shutdown Using Two Switches Automatic Machinery Shutdown Based on Normally Open Solid State Relay Automatic Machinery Shutdown of a Three Phase Electrical Motor Based on a N O Solid S...

Page 8: ... be used to replace more expensive electronic vibration switches where separate vibration output is not required and to replace troublesome mechanical vibration switches Every Smart Switch is factory programmed See Page 28 for more information General Features Fully USB programmable from any PC with optional USB Programmer Kit Hermetically sealed stainless steel housing for use in corrosive enviro...

Page 9: ...he load s power circuit is completed to facilitate the desired alarm or shutdown Figure 1 Block Diagram Benefits of Solid State Relays A solid state relay is an electronic component that functions in the same way as an electromechanical relay but without any moving parts A solid state relay offers the most reliable switch action especially for vibration applications where moving relay components r...

Page 10: ...t the end of this Manual Direct Adhesive Mount Procedure For restrictions of space or for convenience most sensors with the exception of integral stud models can be adhesive mounted directly to the machine surface Step 1 Prepare a smooth flat mounting surface A minimum surface finish of 63 µin 0 00016 mm generally works best Step 2 Place a small portion of adhesive on the underside of the sensor F...

Page 11: ... machine surface consider using an adhesive mounting pad as a possible alternative Inspect the area checking that there are no burrs or other foreign particles interfering with the contact surface Step 2 Wipe clean the mounting surface and spread on a light film of grease oil or similar coupling fluid prior to installation Adding a coupling fluid improves vibration transmissibility by filling smal...

Page 12: ...best frequency response Contact the factory for recommended epoxies This method involves attaching a base to the machine surface then securing the sensor to the base This allows for easy removal of the accelerometer Step 1 Prepare a smooth flat mounting surface A minimum surface finish of 63 µin 0 00016 mm generally works best Step 2 Stud mount the sensor to the appropriate adhesive mounting base ...

Page 13: ...er first weld epoxy or otherwise adhere a steel mounting pad to the test surface This provides a smooth and repeatable location for mounting Figure 6 Magnet Types Step 1 After choosing the correct magnet inspect the unit to verify that the mounting surfaces are flat and smooth Step 2 Stud mount the accelerometer to the appropriate magnet according to the guidelines set forth in Steps 2 and 3 of th...

Page 14: ...ation Attribute Omron Model Number MJN2C AC120 MJN2C AC240 MJN2C DC12 MJN2C DC24 MJN2C DC110 Contact Form 2 Form C DPDT Relay Rated Resistive Load 10 A 240 VAC 28 VDC Service Life Electrical Min Rated Loads 100 000 operations average Relay Max Resistive Switching Capacity 2400 VA 280 W 240 VAC 12 VDC 24 VDC 110 VDC Coil Nominal Voltage 120 VAC 1 2 W Coil Power Consumption 1 7 VA Coil Type Non Latc...

Page 15: ... the vibration level during the specified delay time After this delay the vibration switch will be activated If the vibration level exceeds the alarm threshold for a time period greater than the specified operational delay time the relay will trip This action will close the contact to the pilot lamp Since the NL non latching option is specified the pilot lamp will illuminate only while alarm thres...

Page 16: ...p delay option for the switches is enabled the Smart Switches will not trip during the specified startup delay time regardless of the vibration level After this delay the switch relays will be activated if the vibration level on both machines exceeds the alarm threshold for a period greater than the specified operation delay time This action will close the contact to the pilot lamp Since the NL no...

Page 17: ... Switches will not trip during the specified startup delay time regardless of the vibration level After this delay the switch relay will be activated if the vibration level exceeds the alarm threshold for a period greater than the specified operational delay time This action will close the contact to the alarm siren and activate it Since the LA latching option is specified the alarm siren will be ...

Page 18: ...he start up delay option for the switches is enabled then during the specified startup delay time the switches will not trip regardless of the vibration level After this delay the alarm siren will be activated if either of the switches experiences a vibration level over the alarm threshold lasting greater than the specified operation delay time Since the NL non latching option is specified the ala...

Page 19: ...e corresponding M contact and start the motor If the start up delay option for the switches is enabled then during the specified startup delay time the switches will not trip regardless of the vibration level After this delay the pilot lamp will be illuminated if any of the switches experience a vibration level over the alarm threshold value lasting greater than the specified operational delay tim...

Page 20: ...led the Smart Switches will not trip during the specified startup delay time regardless of the vibration level After this delay the switch relay will be activated if the vibration level exceeds the alarm threshold for a period greater than the specified operational delay time This action will close the contact and send a voltage to the RL relay coil This will open the RL1 and close the RL2 contact...

Page 21: ...the motor If the start up delay option for the switches is enabled the Smart Switches will not trip during the specified startup delay time regardless of the vibration level After this delay the switch relay will be activated if the vibration level of either switch exceeds the alarm threshold for a period greater than the specified operational delay time This action will close the contact and send...

Page 22: ...on level After this delay the switch relay will be activated if the vibration level of either switch exceeds the alarm threshold for a period greater than the specified operational delay time This action will close the contacts and send a voltage to the RL relay coil This will open the RL2 contacts and shut down the motor Since the LA latching option is specified the RL1 contacts are used for exte...

Page 23: ...ring the specified delay time After this delay if the vibration level exceeds the alarm threshold for the alarm switch it will be activated and apply a voltage to the alarm siren Since the NL non latching option is specified for this switch the alarm siren will be energized until the vibration level falls below the alarm threshold value based also on the specified hysteresis If the vibration level...

Page 24: ... This will start the motor If the start up delay option is enabled the switch will not trip regardless of the vibration level during the specified delay time After this delay if the vibration level exceeds the alarm threshold it will be activated thereby opening its contacts and de energizing the solid state relay input This will open the RL contacts and shut down the motor Since the LA latching o...

Page 25: ...start the motor If the start up delay option for the switch is enabled the switch will not trip regardless of the vibration level during the specified delay time After this delay if the vibration level exceeds the alarm threshold it will be activated thereby opening its contacts and de energizing the solid state relay input This will open the RL1 RL2 RL3 contacts and shut down the motor Since the ...

Page 26: ... in order to install the drivers Once installed administrative rights are not required for use Figure 25 Model 600A29 USB Programmer Kit Program Installation Installing the Software and USB Driver Insert the software CD provided into the CD drive The software will start the installation automatically if your PC is set to auto install applications If not browse the CD and click on Setup exe to star...

Page 27: ...2 SENSORS AND INSTRUMENTATION FOR MACHINE CONDITION MONITORING Figure 27 National Instruments Software License Agreement Figure 28 Installation Verification Screen Figure 29 Installation Complete Screen ...

Page 28: ...ler will start automatically The initial USB installer will look similar to the one below Figure 30 WinUSB Driver Installation Screen The drivers will now be properly installed and you should get the following screen Click Finish The software is now ready to use Figure 31 WinUSB Driver Installation Complete Screen ...

Page 29: ...ms PCB EE225 Software menu item Initially the screen will appear as in Error Reference source not found with a yellow bar and status indicating Initializing followed by the message Connecting to USB Dongle Figure 32 Software While Connecting to USB Programmer Cable Once the connection is made the bar at the top of the screen will turn green and the status will indicate USB Connection Success Selec...

Page 30: ...USB programmer cable Click OK to proceed Figure 35 Sensor Connection Screen While the software is establishing communication with the sensor the status will display Checking Status and the colored indicator box next to the status will alternate between red and yellow This will take approximately 15 seconds Once communication is established the indicator box will turn green and the software will re...

Page 31: ...rs Reading Parameters To read the current sensor settings click the Read Parameters button This operation takes approximately 45 seconds to complete Transferring Actual Settings to Settings to Write Field Use the button to transfer all Actual Settings to the Settings to Write fields Writing Parameters Select the appropriate mode and enter any pertinent parameter information Click the Set Parameter...

Page 32: ...set State How the relay operates once actual vibration falls below the alarm threshold Latching Relay to latch or stay in the alarm state until manually reset regardless of the vibration level Non Latching Relay automatically resets once the vibration level falls below the alarm threshold hysteresis level Latching Non Latching Power On Delay Specified time period immediately after power is applied...

Page 33: ...aracter 1 2 3 4 X Parameter MAVT Enabled Custom Customer Specific Configuration Alarm Threshold 0 60 ips Hysteresis 6 Relay Contacts Normal State Normally Open Normally Closed Normally Open Normally Closed Relay Contacts Reset State Latching Latching Non Latching Non Latching Power On Delay 3 sec Operation Delay 6 sec Startup Delay Status Enabled Startup Delay Time Period 3 sec Startup Delay Start...

Page 34: ...l times during the procedure and will cause the machine to shut down and turn on several times This could cause damage to your machinery 1 Mount the Smart Switch on the machine that the switch will monitor Be sure that the machine is operating in a steady state condition If it is not operating turn the machine on and allow enough time for the vibration level to normalize before going to the next s...

Page 35: ...PAGE 30 SENSORS AND INSTRUMENTATION FOR MACHINE CONDITION MONITORING Factory Programmed Ordering Guide Figure 39 Ordering Guide ...

Page 36: ... com for product details Figure 40 Battery Powered Signal Conditioner Calibration Cable The calibration cable Model 052BR010AC is a 10 foot twisted pair shielded cable with a 2 Pin MIL type connector terminating to a BNC plug for use with 480C02 power supply and Smart Switch Figure 41 Calibration Cable Magnet Clip The magnet clip Model 080A214 is supplied as part of the optional 600A29 USB Program...

Page 37: ...d Twisted Pair 048 Armored Polyurethane Shielded Twisted Pair Switch Connector Type AE 2 socket MIL type with environmental boot BP 2 socket MIL type high temp with strain relief BR 2 socket MIL type molded composite BQ 2 socket MIL type molded composite right angle Cable Length 010 10 feet 020 20 feet 030 30 feet 040 40 feet 050 50 feet XXX Any length Cable termination BZ Blunt Cut Consult factor...

Page 38: ...discharge ESD can damage electrical devices Similar to a capacitor a cable can hold a charge caused by triboelectric transfer such as that which occurs in the following Laying on and moving across a rug Any movement through air The action of rolling out a cable and or Contact with a non grounded person The PCB solution for product safety Connect the cables only with the AC power off Temporarily sh...

Page 39: ...ngineer for a RETURN MATERIAL AUTHORIZATION RMA NUMBER Please have information available such as model and serial number Also to insure efficient service provide a written description of the symptoms and problems with the equipment to a local sales representative or distributor or contact IMI if none are located in your area Customers outside the U S should consult their local IMI distributor for ...

Page 40: ... 6 in 1 25 in x 66 mm Weight 5 2 oz 148 gm Mounting Torque 3 to 5 ft lb 4 to 7 Nm Mounting Thread 1 4 28 Female 1 4 28 Female Sensing Element Internal Piezoelectric Accelerometer Piezoelectric Accelerometer Housing Material Stainless Steel Stainless Steel Sealing Welded Hermetic Welded Hermetic Electrical Connector 2 Pin MIL C 5015 2 Pin MIL C 5015 Electrical Connection Position Top Top All specif...

Page 41: ... OF 1 FULL MODEL 686B 686C SERIES VIBRATION SWITCH DECIMALS XX 03 XXX 010 DECIMALS X 0 8 XX 0 25 KRM 7 11 17 JDM 7 11 17 BAM 7 11 17 40111 PCB Piezotronics Inc claims proprietary rights in the information disclosed hereon Neither it nor any reproduction thereof will be disclosed to others without the written consent of PCB Piezotronics Inc REVISIONS REV DESCRIPTION DIN B REVISED TITLE 46960 1 25 3...