SRC - C1    

 

Page 1 

Subject to alteration 

SRC- C1  
Indoor  CO2  Transmitter

 

Features

 

 

Indoor CO2 measurement 

 

Indication with three color led 

 

Minimum and maximum value memory 

 

0…10V, 0…20mA or 2…10V, 4…20mA measuring signals 

selectable with jumpers 

 

Optional alternative signal ranges programmable 

 

May be used as simple P-controller  

 

Selectable averaging signal

 

 

Optional external display (OPA-S)

 

 

Status LED

 

Applications

 

 

Indoor CO2 measurement. 

 

Recording of minimum and maximum limits for critical 

environments 

 

Direct control of extraction fan.  

CO2  Transmitter

 

The CO2 concentration is measured through non-dispersive infrared (NDIR) waveguide technology with ABC automatic 

background calibration algorithm. The applied measuring technology guarantees excellent reliability and long term 

stability. The microprocessor samples the CO2 once per second. It calculates an averaging signal over a preset number 

of seconds and generates the output signal.  

The output signal range and type may be customized by jumpers and if required by a programming tool. Standard 

signal ranges are 0-10VDC, 2-10VDC, 4-20mA and 0-20mA. These ranges can be set by jumpers. Other ranges can be 

set by using the external display and programming module. (OPA-S) 

Minimum and Maximum Values:

  

Using a display & programming accessory, the user has the option to read out and reset minimum and maximum 

values. The minimum and maximum values may as well be used as output signals. The minimum and maximum 

values are saved into the EEPROM and are available after a power interruption.  

Indication of air quality

:

  

A three color LED is used to indicate air quality: Green light for low CO2 concentration, orange light for medium and 

red light for high concentration. The levels for low-medium-high may be programmed.  

Default settings are 0 ppm< low < 800 ppm< medium < 1500 ppm high.  

Use as P-controller

 

Set a minimum concentration when the extract fan should start to run at its minimum speed. For example 700 ppm. 

Set this as the minimum value in IP03 parameter. Then define the value when the fan should run at full speed, for 

example 1500 ppm and set this value in IP04. Your transmitter has now been converted into an air quality P-controller! 

The fan will start to run if the CO2 concentration is higher than 700 ppm. It increases to its maximum when CO2 

concentration reaches 1500 ppm. y  

Ordering

 

Item Name

 

Item Code

 

Description/Option

 

SRC-C1 

40-30 0062 

CO2 transmitter 

Accessories

 

Item Name

 

Item Code

 

Description/Option

 

OPA-S 

40-50 0006 

External display module.  

For the correct display of values V1.4 and later is required 

Maintenance

 

The SRC-C1 CO2 transmitter is maintenance free in normal environments thanks to the built-in self-correcting ABC 

algorithm. Discuss your application with Vector Controls GmbH in order to get advice for a proper calibration strategy. 

 

When checking the sensor accuracy, PLEASE NOTE that the sensor accuracy is defined at continuous operation (at 

least 3 weeks after installation)! 

Error messages

 

visible on OPA - S  

Following error condition may be displayed:  

Err1:

  Communication time out between terminal unit and transmitter. Verify wiring, connections and state of sensor.  

Err3:

  The sensing element is damaged or became disconnected.  

Insight  Control

Ph 1300 665 831

www.insightcontrol.net.au

Summary of Contents for SRC-C1

Page 1: ... Indication of air quality A three color LED is used to indicate air quality Green light for low CO2 concentration orange light for medium and red light for high concentration The levels for low medium high may be programmed Default settings are 0 ppm low 800 ppm medium 1500 ppm high Use as P controller Set a minimum concentration when the extract fan should start to run at its minimum speed For e...

Page 2: ...ion Climatic Conditions Temperature Humidity To IEC 721 3 3 class 3 K5 0 50 C 32 122 F 95 R H non condensing Transport Storage Climatic Conditions Temperature Humidity Mechanical Conditions To IEC 721 3 2 and IEC 721 3 1 class 3 K3 and class 1 K3 30 70 C 22 158 F 95 R H non condensing class 2M2 Standards conformity EMC Directive Low Voltage Directive 2004 108 EC 2006 95 EC Product standards Automa...

Page 3: ...4 20mA 3 2 1 3 2 1 Status LED LED indicates status No light no power or unit damaged 5 sec blinking Normal 2 sec blinking OPA S connected 1 sec blinking Sensor element error if alternate in 2 sec interval with air quality LED Calibration is active OPA S 1 2 3 JP1 JP2 STATUS JP3 1 2 3 4 Calib 0 400 ppm G 24V G0 0V U1 I1 AO CO2 JP3 Calibration Calibrate 0 ppm Provide CO2 free gas Calibrate 400 ppm P...

Page 4: ...tuning speed is however limited to about 30 ppm week For post calibration convenience in the event that one cannot wait for the ABC algorithm to cure any calibration offset jumper 3 is provided for the operator to choose calibration options If jumper 3 is placed on position 1 2 for a minimum time of 8 seconds the internal zero calibration is executed in which case the sensor must be purged by some...