GENERAL INFORMATION

The 

I-

PS24 adjustable power supply is a low cost, 

dependable external power supply. This unit will 
accept an input of up to 26 VAC or 36 VDC, and provides 
an adjustable 1.5 to 26 VDC output. Field voltage 
adjustment is done by adjusting a potentiometer 
using a flat-head screwdriver.  The 

I-

PS24 is setup for 

Half-wave rectification from factory, but can be set to 
Full-wave rectification via jumpers. 

MOUNTING

I-

PS24 is supplied with a snap track for mounting. 

The  circuit board may be mounted in any 
position. In equipment / electrical compartments, 
mounting upside down at top of the enclosure is not 
recommended as heat build-up could be a problem 
when running higher current loads.

Use only fingers to remove board from snap track.  
Slide out of snap track or push against side of snap 
track and lift that side of the circuit board to remove.  
Do not flex board or use tools. 

WIRING INSTRUCTIONS

PRECAUTIONS
• Remove power before wiring. Never connect or
disconnect wiring with power applied.

• All wiring must comply with local and National
Electric Codes.

• It is recommended you use an isolated UL-listed class 2 transformer when powering the unit with 24 VAC.
Failure to wire the devices with the correct polarity when sharing transformers may result in damage to any 
device powered by the shared transformer.

• In applications where a Pilot Duty or remote relay is required, the I-DO008 transorb can be placed across the
coil of the relay to snub electrical spikes when the relays are de-energized. An external transorb may not 
be required if the relay and I-PS24 power supply is mounted within the same control panel.

FIGURE 1: 

DIMENSIONS

PCB Board

Snap 

Track

2.88”

(73.2mm)

0.70”

(17.78mm)

2.05”

(52.07mm)

3.10”

(78.74mm)

Fuse

24 VAC

VDC

Output Selection Jumpers

V-OUT

Adjustment

Power

Indicator

(LED)

+

-

+

-

INTEC Controls | 12700 Stowe Drive, Suite 100, Poway, CA 92064 | Ph: (858) 578.7887 & (888) GO.INTEC | inteccontrols.com

Specifications subject to change without notice. | I0000824, Version 3 | USA 200211 | Page 1 of 3