background image

1

ESL 500 Series

ESL 500 Series
Smoke Detector

Installation Instructions

Description

The ESL 500 Series Smoke Detectors offer 2-wire, 4-wire, 12VDC,
and 24VDC detectors for fire system applications.
Depending on the model, the smoke detector provides the following
features:

Detector/base lock
Discourages unauthorized removal of the smoke detector by requiring
a screwdriver to remove the detector from the base.

CleanMe®
Enables the control panel to receive a warning signal via a 505
module, or CleanMe compatible panel, indicating that the optical
chamber needs to be replaced. This feature is available on the 521/
528 Series 2-wire detectors only.
The detectors ship with the CleanMe feature turned off. To turn on
the CleanMe signal move DIP switch 2 on the back of the detector to
the “on” position. See Figure 1.

Self-diagnostics
Includes automatic sensitivity testing. Once a day and immediately
upon first power up, each 500 Series detector performs a full
diagnostic test that includes a dynamic test of the sensing chamber
and internal electronics. This meets NFPA 72 field sensitivity testing
requirements without the need for external meters.

Drift compensation
The detectors automatically adjust sensitivity, up to a maximum of
1.0%/ft., as the detectors become dirty.

Using the 2-wire 521/528 Series with a panel that does not have 2-
wire capabilities
The ESL 505 module can convert the 2-wire 521/528 Series to a 4-
wire input on the control panel. The 521/528 Series is UL Listed as
compatible with the 505 module and will be fully UL compliant with
any UL listed 24 VDC control panel and panels that do not operate
below 12V. Each 505 module will accommodate up to 20 ESL 521/
528 Series smoke detectors. See the 505 module installation
instructions for more information.

Selectable voltage range for UL 2-wire compatibility
The 500 Series 2-wire smoke detectors have a DIP switch that allows
the installer to choose between 12/24V operation and 6/12V
operation. See Figure 1 and Specifications.

Note

Please refer to the ESL Compatibility Index for a complete
listing of control panels and proper identifiers. For a copy
of the Compatibility Index, call 1-800-648-7424 or visit
www.sentrol.com for a copy to down load. Remember,
4-wire smoke detectors do not require a
compatibility listing.

WARNING

This document is intended for licensed electricians/
alarm installers. Interlogix cannot provide technical
support to unqualified persons.

If you have questions, call Interlogix at 1-800-648-7424.

Selecting a Location

Selecting a suitable location is critical to the operation of smoke
detectors. This equipment should be installed in accordance with
the National Fire Protection Association’s (NFPA) Standard 72.

A-8-1.2.1.a  Where to Locate the Required Smoke Detectors in
Existing Construction.
 The major threat from fire in a family
living unit occurs at night when everyone is asleep. The
principal threat to persons in sleeping areas comes from fires in
the remainder of the unit. Therefore, a smoke detector(s) is best
located between the bedroom areas and the rest of the unit. In
units with only one bedroom area on one floor, the smoke
detector(s) should be located as shown in Figure 2 A.
In family living units with more than one bedroom area or with
bedrooms on more than one floor, more than one smoke detector
is required, as shown in Figure 2 B.

Figure 2. Detector placement

2 A

= Required smoke detectors
= Additional smoke detectors required for new construction

Dining
Room

Kitchen

Bedroom

Bedroom

Bedroom

Living Room

TV Room

Dining
Room

Kitchen

Bedroom

Bedroom

Bedroom

Living Room

Dining 

Room

Basement

Bedroom

Bedroom

Living 

Room

2 B

2 C

Figure 1. Switches

1

2

ON

1. On=A (6-12V) range
   Off=C (12-24V) range

2. On=CleanMe signal on
   Off=CleanMe signal off
   (521/528 Series only)

Note
Turning the CleanMe signal
on without using the 505
module and/or compatible
panel will create a trouble
signal.

NO  COM  NC

Relay (CRXT) unit only

Correct  Incorrect

X

ON

1   2

Summary of Contents for 511C

Page 1: ... DIP switch that allows the installer to choose between 12 24V operation and 6 12V operation See Figure 1 and Specifications Note Please refer to the ESL Compatibility Index for a complete listing of control panels and proper identifiers For a copy of the Compatibility Index call 1 800 648 7424 or visit www sentrol com for a copy to down load Remember 4 wire smoke detectors do not require a compat...

Page 2: ...t least 4 inches 10cm from any walls or partitions Locate wall mounted smoke detectors so the top of the detector is 4 to 12 inches 10 to 30cm below the ceiling Do not locate detectors in or near bathrooms or kitchens Locate in a suitable environment as follows Temperature between 32 F 0 C and 100 F 37 C Humidity between 0 and 95 non condensing Locate away from air conditioners heating registers a...

Page 3: ... ON 2 1 ON 2 Models with gaskets 521CRXT 528CRXT 541C 541CXT 541AXT 548C 548CXT 548 AXT Models without gaskets 511C 511AFT 518C 518AFT 521B 521BXT 528B 528BXT Figure 5 Detector installation ESL 204 12 24V Power Supervision Relay 541 548 Series 4 wire wiring diagram Figure 6 Wiring diagrams First Detector Last Detector EOL Resistor Model 541CXT 548CXT Model 541C 548C 541AXT 548AXT Power Listed Alar...

Page 4: ... must be reset from the control panel If the sensitivity is not within limits or an unserviceable hardware fault has been detected the detector LED flashes every 1 5 seconds until the detector is serviced Cleaning the Detector Clean the detector cover with a dry or damp water cloth as needed to keep it free from dust and dirt When necessary clean the detector interior and replace the optical chamb...

Page 5: ...rded to the customer suggesting a replacement unit and the cost of that unit This warranty does not apply to units which have been subject to abuse misuse negligence or accident or to which any modifications alterations or repairs have been made or attempted This warranty is extended only to the original purchaser of the smoke alarm and may be enforced only by such person During the warranty perio...

Page 6: ...nsions 5 in 12 7cm diameter 2 in 5cm height Mounting dimensions 4 75 in 12 1cm diameter 0 3 in 0 8cm height Reset time 1 second minimum Listings 511 521 541 UL 268 518 528 548 ULC 1036205 Rev A 06 01 Product Ordering Model Description 511C 518C 2 wire photoelectric 6 5 33VDC 511AFT 518AFT 2 wire photoelectric 6 5 33VDC rate of rise heat sensor 521B 528B 2 wire photoelectric 6 5 33VDC 521BXT 528BXT...

Reviews: