Main Breaker
2-Pole, 20 A circuit
breaker shown
A=Black (Line)
B=Black (Line)
C=Neutral/Grounded (White)
Type 2 Installation
Type 1 installation:
A typical installation of a type 1 SPD will be connected between the
secondary of the service transformer and the line side of the service
panel. This installation is intended to be installed without overcurrent
protection to the SPD.
1. Determining location:
•
Ensure conductor lengths are as short and straight as
possible for best performance. Do not coil excess wire. The
SPD functions best if all bends in wires are rounded, ideally
to a 4” radius. Hard 90 degree bend will reduce efficiency.
Cut all leads to the correct length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be
mounted outside.
2. Ensure all mounting and connections are correct and secure.
Once energized the green indicator LED will be ON and visible
through the cover of the SPD.
Type 2 installation:
A typical installation of a type 2 SPD will be connected to the load side
of the service panel and is intended to be installed with overcurrent
protection to the SPD.
1. Determining location:
•
Ensure conductor lengths are as short and straight as
possible for best performance. Do not coil excess wire. The
SPD functions best if all bends in wires are rounded, ideally
to a 4” radius. Hard 90 degree bend will reduce efficiency.
Cut all leads to the correct length. Do not coil excess leads.
• Install appropriate weatherproof fittings if the unit is to be
mounted outside.
2. Connect the white wire from the SPD to the neutral bus bar in
the panel as shown.
• Connection may also be made to the neutral/ground bus bar
if panel does not have a separate ground bus bar.
3. Connect the two black wires to a circuit breaker as shown.
For best performance from SPD the maximum recommended
circuit breaker size of 240 VAC,up to 30 A, 2-pole should be
used.
4. Ensure all mounting and electrical connections are correct and
securely fastened. Once energized the green indicator LED will
be ON and visible through the cover of the SPD.
AC Disconnect Installation
1. To be installed with over current protection up to 60 A.
Maintenance:
•
AC Voltage SPD:
•
Periodically check SPD to ensure green indicator LED is ON.
If green LED is OFF, protection has diminished and the SPD
should be replaced immediately.
INSTALLATION INSTRUCTIONS
IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS
Model AG3000
Type 1 or Type 2 Surge Protection Device (SPD)
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Intended for indoor or outdoor use.
• Installation and/or wiring must be in accordance with national and local electrical code(s).
• Installation and service to be performed by a qualified licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 20,000 rms symmetrical amperes.
• This unit contains no serviceable parts.
WARNING
Risk of Fire or Electric Shock
NOTICE
•
Thoroughly read instructions before installing SPD Unit.
•
This product does not protect against lightning strikes.
•
If the unit is mounted outdoors, the threaded nipple must be mounted horizontally into a suitable enclosure.
• L’installation et/ou le câblage doivent être conformes aux exigences du code de l’électricité local en vigueur et/ou du Code canadien de l’électricité.
• L’installation et l’entretien doivent être effectués par un technicien ou électricien qualifié.
• Convient à un circuit capable de fournir PAS plus de 20 000 A efficaces symétriques.
• Cet appareil ne contient aucune pièce réparable.
AVERTISSEMENT
Risque d’incendie ou de choc électrique
Typical 120/240 VAC Application
Black
White
Black
AC Disconnect
Line
Load
Load
Line
Neut/Grnd
Line
Line
AG3000
120 VAC Two wire single phase with
separate ground.
Found at connections for individual
pieces of equipment such as pumps,
single phase motors and HVAC applications.
NOTE:
Both Black wires connect to Line.
Line
Neutral
Ground
0 V
120 V
120 V
Neutral/
Grounded
(WHITE)
Line
(BLACK)
Line
(BLACK)