Main Breaker

2-Pole, 20 A circuit

breaker shown

A=Black (Line)
B=Black (Line)
C=Neutral/Grounded (White)

Type 2 Installation

Type 1 installation:

A typical installation of a type 1 SPD will be connected between the 
secondary of the service transformer and the line side of the service 
panel. This installation is intended to be installed without overcurrent 
protection to the SPD.
  1.  Determining location:
   

•  

Ensure conductor lengths are as short and straight as 
possible for best performance. Do not coil excess wire. The 
SPD functions best if all bends in wires are rounded, ideally 
to a 4” radius. Hard 90 degree bend will reduce efficiency. 
Cut all leads to the correct length. Do not coil excess leads.

   

•   Install appropriate weatherproof fittings if the unit is to be 

mounted outside.

  2.   Ensure all mounting and connections are correct and secure. 

Once energized the green indicator LED will be ON and visible 
through the cover of the SPD.

Type 2 installation:

A typical installation of a type 2 SPD will be connected to the  load side 
of the service panel and is intended to be installed with overcurrent 
protection to the SPD.
  1.  Determining location:
   

•  

Ensure conductor lengths are as short and straight as 
possible for best performance. Do not coil excess wire. The 
SPD functions best if all bends in wires are rounded, ideally 
to a 4” radius. Hard 90 degree bend will reduce efficiency. 
Cut all leads to the correct length. Do not coil excess leads.

   

•   Install appropriate weatherproof fittings if the unit is to be 

mounted outside.

  2.   Connect the white wire from the SPD to the neutral bus bar in 

the panel as shown.

   

•   Connection may also be made to the neutral/ground bus bar 

if panel does not have a separate ground bus bar.

   3.   Connect the two black wires to a circuit breaker as shown. 

For best performance from SPD the maximum recommended 
circuit breaker size of 240 VAC,up to 30 A, 2-pole should be 
used.

  4.   Ensure all mounting and electrical connections are correct and 

securely fastened. Once energized the green indicator LED will 
be ON and visible through the cover of the SPD.

AC Disconnect Installation

  1.  To be installed with over current protection up to 60 A.

Maintenance:

• 

AC Voltage SPD:

 

•  

Periodically check SPD to ensure green indicator LED is ON. 
If green LED is OFF, protection has diminished and the SPD 
should be replaced immediately.

INSTALLATION INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS

Model AG3000

Type 1 or Type 2 Surge Protection Device (SPD)

• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Intended for indoor or outdoor use.
• Installation and/or wiring must be in accordance with national and local electrical code(s).
• Installation and service to be performed by a qualified licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 20,000 rms symmetrical amperes.
• This unit contains no serviceable parts.

    

WARNING

Risk of Fire or Electric Shock

NOTICE

• 

Thoroughly read instructions before installing SPD Unit.

• 

This product does not protect against lightning strikes.

• 

If the unit is mounted outdoors, the threaded nipple must be mounted horizontally into a suitable enclosure.

• L’installation et/ou le câblage doivent être conformes aux exigences du code de l’électricité local en vigueur et/ou du Code canadien de l’électricité.
• L’installation et l’entretien doivent être effectués par un technicien ou électricien qualifié.
• Convient à un circuit capable de fournir PAS plus de 20 000 A efficaces symétriques.
• Cet appareil ne contient aucune pièce réparable.

    

AVERTISSEMENT

Risque d’incendie ou de choc électrique

Typical 120/240 VAC Application

Black

White 

Black

AC Disconnect

Line

Load

Load

Line

Neut/Grnd

Line

Line

AG3000

120 VAC Two wire single phase with 

separate ground.

Found at connections for individual 

pieces of equipment such as pumps, 

single phase motors and HVAC applications. 

NOTE:

 Both Black wires connect to Line.  

Line

Neutral

Ground

0 V

120 V

120 V

Neutral/

   Grounded 

  (WHITE)

   Line

(BLACK)

   Line

(BLACK)