IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS

INSTALLATION INSTRUCTIONS

IG2240-IMSK

TYPE 1 AND 2 SURGE PROTECTIVE DEVICES

APPLICATION NOTES

1. 

Thoroughly read instructions before installing SPD unit.

2. 

This product is designed to protect against momentary transient overvoltage events.

3. 

This product may not protect against nearby lightning strikes.

4. 

This device features internal protection that will disconnect the surge protective component at the end of its useful life but will maintain power to the load-now unprotected. If this situation is undesirable 
for the application, follow the manufacturers instructions for replacing 

I

Module™

 

units.

5. 

Observe warnings and instructions on front panel and unit label of product.

DEFINITIONS

Type 1 SPD: A typical Type 1 SPD installation will be connected between the secondary of the service transformer and the line side of the service panel. This installation is intended to be installed without 

overcurrent protection to the SPD.

Type 2 SPD: A typical Type 2 SPD installation will be connected to the load side of the service panel and is intended to be installed with overcurrent protection to the SPD.

INSTALLATION:

1. Verify system voltage. 

2. Make sure SPD is correctly rated for your system. 

3. Determine mounting location of SPD unit.

 The SPD unit should be located as close as possible to the load to be protected to minimize all wire lengths.

4. Mount enclosure

- Remove dead front from SPD unit.

- Disconnect power to unit at power source before installation.

- Remove needed knockout from SPD unit once wire routing has been determined.

- Only one conduit connection may be made to SPD unit enclosure.

-  Mount enclosure using suitable fasteners in locations shown below. Do not rely on conduit fitting to support SPD.

5. Follow wiring diagram for all connections (Located within instruction sheet and SPD unit).

- Lead lengths can be replaced at terminal; splicing of leads is not recommended.

- Cut all wires to a minimum suitable length while maintaining a 4” recommended bend radius.

- Do not coil excess wire.

- Make sure all connections are secure.

- Replace dead front.

6. Energize SPD unit

- Flip circuit breaker (when used) to ON position at main service panel or disconnect switch(es).

- Flip Module Power Switch within SPD unit to on position.
- Indicators: Each 

I

Module™ has a blue LED to indicate the SPD unit has power and a green LED to indicate that the 

I

Module™ is providing protection.

*C/B

GND (green)

Neutral (white)

Line (black)

Line (black)

SPD TYPE 1 AND 2  WIRING DIAGRAM

120/240 VAC SINGLE-PHASE

SPD

*2 Pole 30 A circuit breaker in Service Panel.

(Not required for SPD type 1 installations) 

 2 1/2" 

 5" 

 1 5/8" 

 3/4" 

 3/4" 

 1 5/8" 

 10 3/8" 

Metal indoor enclosure

(Flush mount kit IG2200--FMK)

SERVICING INSTRUCTIONS:

 

The 

I

Module™will absorb the energy of the surges to protect the connected load. If the green LED is OFF, the 

I

Module™ is no longer providing protection and should be replaced as soon as possible.

All three of the removable 

I

Module™ units must be replaced every three years to maintain the connected equipment warranty.

TO REPLACE IModule™:

1. 

POWER MUST BE REMOVED FROM THE 

I

Module™ UNITS BEFORE REPLACING.

2. 

Move the Module Power Switch within the SPD to the OFF position. This will ONLY remove power to the 

I

Module™ units. This switch does not remove power to the protected load. This switch is not used 

as an overcurrent protection device (OCPD).

3. 

Remove 

I

Module™ to be replaced by firmly pulling straight out from SPD unit. The module door within the unit will close once the 

I

Module™ is removed.

4. 

Make sure 

I

Module™ is correctly rated for system. 

5. 

Place new 

I

Module™ back into SPD unit. Make sure 

I

Module™ alignment key is oriented correctly when inserting.

6. 

Make sure the 

I

Module™ is fully seated.

7. 

Re-energize SPD unit.

8. 

Verify the blue and green LED’s within each 

I

Module™ are lit.

SPD

UNIT

Main Breaker

2-Pole, 30A circuit
breaker

Green (Ground)

Type 2 Installation

Black (Line)

Black (Line)

Neutral (White)

Blue LED: Power indicator

Green LED: Status indicator

Alignment key of module

ON: Protection is being provided.
OFF: IModule™ is no longer providing
protection. Replace IModule™ as soon
as possible.

I

Module™

Risk of Fire or Electric Shock

•  Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  Turn Module Power Switch to the OFF position, (if provided), or remove power at the power source before replacing 

I

Module™ units.

•   Confirm 

Smart Guard 

™ is rated for the correct voltage per part number specified on your SPD enclosure.

•  Installation and/or wiring must be in accordance with national and local electrical code requirements.
•  Installation and service to be performed by a qualified licensed technician or electrician.
•  Bonding between conduit connections is not automatic and must be provided as part of the installation.
•  KEEP DOOR CLOSED AT ALL TIMES when not servicing.

 

WARNING

Summary of Contents for Smart-Guard IG2240-IMSK

Page 1: ... to indicate the SPD unit has power and a green LED to indicate that the IModule is providing protection C B GND green Neutral white Line black Line black SPD TYPE 1 AND 2 WIRING DIAGRAM 120 240 VAC SINGLE PHASE SPD 2 Pole 30 A circuit breaker in Service Panel Not required for SPD type 1 installations 2 1 2 5 1 5 8 3 4 3 4 1 5 8 10 3 8 Metal indoor enclosure Flush mount kit IG2200 FMK SERVICING IN...

Page 2: ...d Equipment d Equipment with additional telephone or data cable connections must be properly connected to an Intermatic Listed Surge Protection Device see www Intermatic com and e the Product s and Protected Equipment must not be opened modified exposed to extreme heat or cold submerged or subjected to abnormal use or service For purposes of this Limited Warranty a Power Transient shall mean over ...

Page 3: ...pour indiquer que le SPD est alimenté et d une DEL verte pour indiquer que l IModule fournit de la protection C B TERRE vert Neutre blanc Ligne noir Ligne noir SCHÉMAS DE CÂBLAGE DES SPD DE TYPE 1 ET 2 120 240 VCA MONOPHASÉ SPD Disjoncteur à 2 pôles de 30 A au niveau du panneau de service Pas nécessaire pour des installations de SPD de type 1 2 1 2 5 1 5 8 3 4 3 4 1 5 8 10 3 8 Enceinte intérieure ...

Page 4: ...é ne devront pas être ouverts modifiés exposés à la chaleur ou au froid intenses immergés ni soumis à une utilisation ou à un entretien inappropriés Aux fins de la présente garantie limitée une Transitoire électrique est une surtension résultant de pointes ou crêtes momentanées de tension sur la ligne d alimentation secteur d une amplitude que le Produit conformément à ses caractéristiques est con...

Page 5: ...verde para indicar que el IModule está brindando protección Disyuntor GND verde Neutro blanco Línea negro Línea negro DIAGRAMA DE CABLEADO DE SPD TIPO 1 Y 2 MONOFÁSICO DE 120 240 V CA SPD Disyuntor bipolar de 30A en el panel de servicio No se requiere para las instalaciones de SPD tipo 1 2 1 2 5 1 5 8 3 4 3 4 1 5 8 10 3 8 Caja metálica para interior Kit para montaje empotrado IG2200 FMK INSTRUCCIO...

Page 6: ...com y e el los Producto s y Equipo dañado no se deben abrir modificar exponer al calor o el frío extremo sumergir ni someterse a un uso o mantenimiento anormales Para propósitos de esta Garantía limitada un transitorio eléctrico se entenderá como sobretensión o sobrevoltaje causado por picos de tensión o sobretensiones momentáneos en una línea de alimentación CA de una magnitud que el Producto seg...

Reviews: