background image

 

           

       

 

 

 

                         
 
                                      

 

 

 

 

IntesisBox

®

 Modbus Server – Cerberus ISO1745 

 

Doc. Rev.2 

Installation Manual

 

URL

email

tel

http://www.intesis.com                                         
info@intesis.com 
+34 938047134 
 

    1 / 5

This information is subject to change without notice.

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

IntesisBox must be installed by accredited electrician or similar technical personnel, following all the safety instructions 
given here, and in accordance always with the country legislation for installation of electric equipment. 

 

IntesisBox can not be installed outdoors or exposed to direct solar radiation, water, high relative humidity or dust. 

 

IntesisBox must only be installed in a restricted access location  

 

In case of wall mount, fix firmly IntesisBox on a not vibrating surface following the instructions below. 

 

In case of DIN rail mount fix IntesisBox properly to the DIN rail following the instructions below.  

 

Mounting on DIN rail inside a metallic cabinet properly connected to earth is recommended. 

 

Disconnect always power of any wires before manipulating and connecting them to IntesisBox. 

 

A power supply with an NEC Class 2 or Limited Power Source (LPS) and SELV rated is to be used.  

 

Respect always the expected polarity of power and communication cables when connecting them to IntesisBox.  

 

Supply always a correct voltage to power IntesisBox, see details of voltage range admitted by the device in the technical 
characteristics below.  

 

This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with 
static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure. When working in 
an  enclosure  (ex. making  adjustments, setting   switches  etc.) typical  anti-static  precautions should be  observed  before 
touching the unit 

Safety Instructions 

 

 

WARNING 

Follow  carefully  this  safety  and  installation  instructions.  Improper  work  may  lead  to  serious  harmful  for  your 
health and also may damage seriously the IntesisBox and/or any other equipment connected to it. 

Use  the  software  LinkBoxMB  to  configure  IntesisBox,  follow  the  instructions  of  the  user's  manual  for  more 
details. 

 

See instructions to download and install the latest version of LinkBoxMB and 

the user's manual at  
 

 

http://www.intesis.com/down/mb/linkboxmb.html

 

 

Configuration and setup 

 

 

Disconnect from mains the power supply before connecting it to IntesisBox. 

 

Disconnect power of any bus or communication cable before connecting it to IntesisBox. 

 

Mount  IntesisBox  on  the  wall  or  DIN  rail  following  the  instruction  given  below,  respecting  the  safety 
instructions given above. 

 

Connect  a  NEC  Class  2  or  Limited  Power  Source  (LPS)  and  SELV  rated  power  supply  to  IntesisBox, 
respect the polarity if DC power or Line and Neutral if AC power. Apply always a voltage within the range 
admitted by IntesisBox and of enough power (see technical characteristics). 

 

Circuit-breaker must be used before the power supply. Rating 250V-6A 

 

Connect the communication cables to IntesisBox, see details on the user's manual. 

 

Power IntesisBox and the rest of devices connected to it. 

 

Installation instructions 

 

Summary of Contents for Modbus Server-Cerberus ISO1745

Page 1: ...trostatic discharge to the unit in environments with static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure When working in an enclosure ex making adjustments setting switches etc typical anti static precautions should be observed before touching the unit Safety Instructions WARNING Follow carefully this safety and installation instructions Improper wo...

Page 2: ...low 2 Use the holes of the clips to fix the box in the wall using screws Use the template below for the wall holes With the clips of the box in their original position insert first the box in the upper edge of the DIN rail and later insert the box in the down part of the rail using a small screwdriver and following the steps in the figure below Wall mount Clips in their original position for DIN r...

Page 3: ...are allowed through all the LAN path Modbus RTU EIA485 Connect the EIA485 bus to the connector Modbus RTU EIA485 of IntesisBox Respect the polarity Remember the characteristics of the standard EIA485 bus maximum distance of 1200 meters maximum 32 device connected and a 120 ohms terminator resistor in each end of the bus IntesisBox comes with an internal bus biasing circuit which incorporates inter...

Page 4: ... DB9 male DTE SELV 1 x Serial EIA485 Plug in screw terminal block 2 poles SELV Cerberus port 1 x Serial EIA232 DB9 male DTE SELV LED indicators 1 x Power 2 x Cerberus serial port activity Tx Rx 2 x Modbus RTU serial port activity Tx Rx 2 x Ethernet port link and activity LNK ACT Console port EIA232 DB9 female connector DCE SELV Configuration Via console port 1 Firmware Allows upgrades via console ...

Page 5: ... intesis com 34 938047134 5 5 This information is subject to change without notice Dimensions External dimensions Free space recommended to install the device with spacing enough for external connections 115 mm 130 mm 100 mm Power Ethernet port 107 mm 105 mm 58 mm Cerberus port Console port Modbus RTU EIA232 485 ...

Reviews: