IMPORTANT SAFEGUARDS

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

  1. 

WARNING 

– Dual Power Supply - Risk of shock hazard even if AC power is OFF.

 2. 

WARNING 

 

Disconnect TSPL (Test Switch Pilot Light) connector before servicing fixture.

 3. 

WARNING 

 

DO NOT mount near a gas or electric heater.

  4. 

CAUTION 

– Before wiring to power supply, turn off electricity at fuse panel or circuit breaker.

  5. 

CAUTION 

– Service by Qualified Personnel only. De-energize before opening.

  6. 

CAUTION 

– DO NOT attempt to service the battery. It is not field replaceable.

  7. 

CAUTION 

– DO NOT use outdoors, in air handler heated outlets, or in hazardous locations. This product is for 

use with indoor and damp rated fixtures where the ambient temperature is 0°C minimum to 55°C maximum.

  8. 

CAUTION 

– DO NOT use accessory equipment not recommended by the manufacturer.

  9. 

CAUTION 

– DO NOT use this equipment for other than its intended use.

 10.  Consult your local building code for approved wiring or installation.

 11.  The LED Emergency Driver must be connected to an un-switched AC power source of 120 to 277 Vac.

 12.  Product  output voltage varies accorting to wattage. Refer to 

Illustration 1

 for output voltage per model.

13.  Equipment should be mounted in a location and at heights where it will not be readily subject to tampering by 

unauthorized personnel.

 14.  Make sure that the branch circuits are derived from a common phase for both normal lighting LED drivers and 

the LED Emergency Driver 

prior

 to installation.

 15.  When used with a switched fixture, it is important that the power to the LED Emergency Driver be provided by 

an un-switched circuit.

 16.  LED Emergency Drivers are for factory and field installation. They are not field serviceable.

 17.  Allow Battery Packs to charge 24 hrs before initial and full-discharge testing.

18.  Emergency lighting system should be tested per all of the required tests and as often as local codes require or 

at least quarterly to ensure all components are operational.

19.  Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before 

final installations.

SAVE THESE  INSTRUCTIONS

ILB-LP-CP-HE-SD-HV

“S” MOUNTING STYLE

HIGH-EFFICIENCY EMERGENCY

LIGHTING EQUIPMENT 

FOR LED

INSTRUCTION MANUAL

P.O. BOX 11846  TUCSON, AZ 85734 

(520) 294-3292   •  FAX (520) 741-2837

www.iotaengineering.com

HIGH EFFICIENCY PERFORMANCE 
MEETS CA T20 BATTERY CHARGER 
EFFICIENCY STANDARDS

Summary of Contents for ILB-LP-CP-HE-SD-HV

Page 1: ...rting to wattage Refer to Illustration 1 for output voltage per model 13 Equipment should be mounted in a location and at heights where it will not be readily subject to tampering by unauthorized personnel 14 Make sure that the branch circuits are derived from a common phase for both normal lighting LED drivers and the LED Emergency Driver prior to installation 15 When used with a switched fixture...

Page 2: ...ly engage the TSPL Connector to the TSPL Socket Ensure the TSPL Connector is properly seated in the TSPL Socket then mark the TSPL location on the switch box plate with the TSPL Label and apply the SD Status Indicator Sticker INSTALLATION INSTRUCTIONS Refer to the appropriate wiring diagram below Make sure all connections are in accordance with NEC and any other local requirements ILB LP NORMAL DR...

Page 3: ...e ILB LP CP HE SD HV is in the standby charging mode The TSPL will be lit providing a visual indication that the battery is being charged Emergency Mode The A C power fails The ILB LP CP HE SD HV senses the A C power failure and automatically switches to the Emergency Mode The LED Module is illuminated at reduced output for a minimum of 90 minutes When the A C power is restored the ILB LP CP HE SD...

Page 4: ... Testing Manual testing of the ILB LP CP HE SD HV can be performed by pressing and releasing the TSPL test button Table A TSPL Diagnostic Codes CONDITION STATUS INDICATION STEADY GREEN OR STEADY RED NORMAL MODE FLASHING GREEN SELF TESTING OFF EMERGENCY MODE FLASHING RED GREEN INSUFFICIENT CHARGE 1 RED FLASH BATTERY PACK FAILURE 2 RED FLASHES EMERGENCY LAMP FAILURE 3 RED FLASHES FIXTURE DIAGNOSTIC ...

Page 5: ...k on search the DLC Qualified Product List button on the DLC homepage In the search by keyword text window enter luminaire manufacturer name and part number Click on Search tab to open the Qualified Products List Determine per RATED DATA efficacy shown in lumens per watt lm w Multiply lumens per watt by ILB LP CP rated output example lm w x 5 watts Refer to table ILB MODEL SPECIFICATION CHART belo...

Page 6: ... la puissance électrique Reportez vous à l Illustration 1 pour connaître la tension de sortie de chaque modèle 13 Il faut installer cet équipement à un endroit et à une hauteur qui permettent d éviter toute manipulation par des personnes non autorisées 14 Assurez vous que les circuits de branchement sont dérivés d une phase commune pour les pilotes des DEL d éclairage normal et le pilote d urgence...

Page 7: ...t le connecteur de la LTBT dans la douille de la LTBT Assurez vous que le connecteur de la LTBT est bien en place dans sa douille puis marquez son emplacement sur la plaque de la boîte de distribution à l aide de l étiquette TSPL LBTB et apposez l autocollant de l indicateur de statut SD INSTRUCTIONS D INSTALLATION Reportez vous au diagramme de câblage approprié ci dessous Assurez vous que toutes ...

Page 8: ...mode de chargement en veille La LTBT est allumée et indique de manière visuelle que la batterie est en cours de chargement Mode d urgence L alimentation secteur tombe en panne L ILB LP CP HE SD HV détecte la panne de courant et bascule automatiquement en mode d urgence Le module DEL s allume donnant un éclairage réduit pendant un minimum de 90 minutes Lorsque l alimentation secteur se rétablit l I...

Page 9: ...appuyant et en relâchant le bouton de test LTBT Tableau A Codes de diagnostic de la LTBT CONDITION VOYANT D ÉTAT DEMEURE VERT OU ROUGE FIXES MODE NORMAL CLIGNOTEMENT EN VERT TEST D AUTODIAGNOSTIC ÉTEINT MODE D URGENCE CLIGNOTEMENT EN ROUGE VERT CHARGE INSUFFISANTE 1 CLIGNOTEMENT ROUGE PANNE DE BATTERIE 2 CLIGNOTEMENTS ROUGES PANNE DE L ACCESSOIRE DE LAMPE D URGENCE 3 CLIGNOTEMENTS ROUGES PANNE DÉT...

Page 10: ... page d accueil de DLC Dans la fenêtre de texte Recherche par mot clé entrez le nom du fabricant du luminaire et le numéro de pièce Cliquez sur l onglet Recherche pour ouvrir la Liste des produits homologués Déterminez par DONNÉES NOMINALES l efficacité indiquée en lumens par watt lm w Multipliez les lumens par watt par la puissance nominale ILB LP CP exemple lm w x 5 watts Consultez le TABLEAU DE...

Reviews: