The JA-151TH Wireless temperature detector
The JA-151TH Wireless temperature detector
1 / 2
MNG51308
The JA-151TH is a component of the
JABLOTRON 100
system.
It serves for temperature measurement and forwarding measured
data to MyJABLOTRON. MyJABLOTRON analyses and stores
measured data for further use for instance the SMS reporting
of exceeding temperature limits or to create graphs of measured
temperatures.
All
functions are programmable
directly
in MyJABLOTRON. The PG control function can be assigned
to maximum of 2 thermometers per control panel. This product
should be installed by a trained technician with a valid certificate
issued by an authorised distributor.
Installation
Select the installation place according to the temperature
measuring requirements. It is not recommended to install
the detector near heat sources affecting measuring (heaters,
electric fans, air conditioning outlets, fireplace inserts, etc.).
The detector can also be installed in an outdoor environment but
it has to be placed into a suitable box with a minimum of IP65
housing, the JA-192PL-A for example.
Figure 1: 1 – cover tab; 2 – LED indication
1. Open the cover by pushing the tab (1).
2. Attach the plastic base to the required place using screws.
3. Follow the instructions in the control panel installation manual.
Basic procedure:
a. Go to the
F-link
software, select the required position
in the
Devices
tab and launch the enrollment mode
by clicking on the
Enroll
option.
b. The enrollment signal is transmitted when the battery
is inserted into the detector.
4. Close the detector cover.
Figure 2: 3 – production code; 4 – activation button; 5 – battery
Note:
Enrolling the detector to the system is also possible with active
enrolment mode by entering the production code (3) via
the F-Link software. All digits in the production code are
required (1400-00-0000-0001).
If you want to remove the detector from the control panel, erase
it from its position.
Functions
The JA-114E and JA-154E series of keypads are able to display
up to 2 current temperatures on the keypad screen. See the JA-10xK
installation manual.
The detector has a fixed antifreeze temperature of +6 °C with ±1 °C
hysteresis. Therefore the detector has an activation temperature
of +5 °C. The deactivation temperature is +7 °C.
Using the F-Link software, it is possible to configure the JA-10xK
control panel’s reaction (PG output, 24h alarm, etc.) to react
to temperature detector activation. Thus the selected PG output
is controlled directly by the control panel.
All thermometer functions can be fully used in MyJABLOTRON.
The registration procedure is described in the
Control panel installation
manual.
MyJablotron
All thermometers and their measured values are stored and shown
in the
Thermostats and Thermometers
tab in MyJABLOTRON.
The temperatures are stored automatically every 5 minutes.
The temperatures are displayed in a graph with an adjustable timeline.
It’s possible to export data from the graphs in various formats for further
processing. The graph function enables you to compare temperatures
from two thermometers or different time periods (only available
in the MyJABLOTRON mobile app).
The app offers the following functions:
PG control by measured temperature
Using MyJABLOTRON, it’s possible to configure activation of a PG
output by a temperature measured by the thermometer. The selected
PG output is controlled remotely from MyJABLOTRON therefore stable
external communication is necessary for this function to work properly.
If this function is selected, the user can use a slider to configure
the desired temperature which will activate the PG output. These
settings are located in the
Thermostats and Thermometer
tab.
Linking
the thermometer with a PG output is done by a service
technician in the
Installation management
section
of
the
MyCOMPANY app. Select the control panel, enter the
Devices
tab,
press the symbol of a gearwheel on the thermometer and select a PG
output which should be controlled by the measured temperature.
Use the slider to configure the desired activation temperature.
This configured link is indicated by a PG symbol at the thermometer’s
position.
Warning!
The controlled PG output must be configured to have
ON/OFF
or
Impulse
functions (configurable in the F-Link software).
Notes:
Establishing the link and controlling the PG output by the measured
temperature can also be done in the MyCOMPANY and
MyJABLOTRON mobile app.
This function can be configured for a maximum of 2 thermometers
enrolled to the control panel (the sum of wireless and BUS
thermometers).
Connection via GSM and LAN communicators is required in order
to make sure that PG output control from MyJABLOTRON works
properly.
Due to fact that PG outputs are controlled via an external app,
we cannot guarantee proper functioning under all
circumstances
. When the connection with MyJABLOTRON is lost,
the status of the PG output stays unchanged until the connection
is re-established. This is why we recommend using a controlled PG
output along with the IMPULS function set to an activation time
of 2:00:00. The PG output will be controlled by commands from
MyJABLOTRON. If the connection is lost, activation of the PG
output will be limited by the activation time of the IMPULS function.
The activation hysteresis of a PG output is +/- 1 °C. The PG output
will be activated when the measured temperature is 1 °C lower than
the activation temperature. Deactivation will occur when this
temperature is exceeded by 1 °C.
Notifying
the user when the temperature exceeds the allowed
range
You can set a higher and a lower temperature limit and a certain
period of time of temperature monitoring for a selected thermometer
in
Settings
Æ
Thermometer notification
. When one of these limits
is exceeded or gone below then it’s reported by an SMS, an e-mail
or push notifications if you use the MyJABLOTRON app.
Battery replacement
The system sends a report automatically when the battery is low.
During the battery replacement it is not necessary to switch
the system to service mode (this detector has no tamper contact).
After taking out the battery, presses the activation button (4)
to discharge the capacitors in the detector and then insert
a new battery.
Apply the same procedure if you need to enroll the detector