Anti explosive type lumina res

i

980820200_09_004

Page 1 from 3

IP-66

CONFORMITY WITH STANDARDS EN 60598-2-22 - UNE 

20392.93 - UNE 20062.93 -  EN 50014  EN50018

CONFORMITY TO DIRECTIVE 94/9/CE (ATEX)

ο

CERTIFICATE N  02ATEX2041 X

 

 

CE 0163

   

e

x   

II2GD

 

o

o

EExd IIC T6 T85 C Y EExd IIC T6 T85 C

 

156 

115 

196.5 

DIMENSIONS

TYPE

L

D

FSA-8202C

FSA-8352C
FSA-2118C

FSP-3236CC

IFA-3136P

IFA-3236

IFA-3236P
IFA-4258P

485mm

485mm
750mm

1350mm
1350mm
1350mm
1350mm
1650mm

391mm

391mm
656mm

1256mm
1256mm
1256mm
1256mm
1556mm

MOUNTING & CONNECTING

 

FIG. A 

FIG. D 

FIG. B 

 

 

 

FIG. C 

REMOTE 

CONTROL 

DEVICE

 

 

 

230 V – 50 Hz

 

4

 

 

 

 

1. Unscrew the hexagonal screw with 2 mm Allen key (Fig. A). 
2. Turn the cover until completely being taken off (Fig. A).
3. Extract the connecting plates (Fig. B). 
4.  Connect  the  wires  to  the  mains  supply  (Fig.  C).  The  main  supply 

connection  are  indicated  on  the  label  next  to  the  connecting  plate.  The 
connections  must  be  done  with  the  mains  supply  cables  out  of  tension. 
The  mains  supply  cables  must  be  introduced  into  the  housing  through 
the  metallic  stuffing  box  due  to  ATEX  directive  and  certified  by  an 
organism, adapted to used cables (threads: ¾ NPT). 

5. Insert again the connecting plates into their right place (Fig. D).
6. Put the cover in its place and turn it until being completely closed (fig E). 
7. Screw the hexagonal screw with the 2 mm Allen key (Fig. E). Maximum 

tightens force: 0.85 N*m (±15%) 

8.  Mount  the  ceiling-bracket.  The  ceiling-bracket  are  mounted  in  the 

housing  with  screws  M8x15  +  ø16/8.5  flat  washer  +  ø14/8.5  fluted 
washer (Fig. F).

9  .Fix  luminaire  in  ceiling  or  wall,  screwing  in  the  holes  located  in  the 

ceiling-bracket (Fig. F). 

10. Mains supply: ~230 V  50 Hz .

 