Photovoltaic Module User Manual 

UL1703

 

 

 

Table of Contents: 

1. General information………………………………..………..…………….2-5 

1.1 Overview

 

1.2 Applicable Products 

1.3 Warning 

2. Installation……………............................................................................5-11

 

2.1Installation safety 

2.2Installation condition

 

2.2.1 Operation condition 

2.2.2 Site selection 

2.2.3 Tilt angle selection 

2.3 Mechanical Installation introduction 

2.3.1 Fixation with screw 

2.3.2 Fixation with clamps 

3. Wiring and connection…………………………………………..………..12-14 

4. Maintenance and care……………………………..………………………..14-15 

5. Electrical specification…………………………..………………………..15-20 

6. Disclaimer of liability………………………………...………………………21 

7. Contact us……………………………………………………………………...22

 

 

 

 

 

 

 

photovoltaikforum.com

Summary of Contents for JKM-160M-72

Page 1: ...safety 2 2Installation condition 2 2 1 Operation condition 2 2 2 Site selection 2 2 3 Tilt angle selection 2 3 Mechanical Installation introduction 2 3 1 Fixation with screw 2 3 2 Fixation with clamps 3 Wiring and connection 12 14 4 Maintenance and care 14 15 5 Electrical specification 15 20 6 Disclaimer of liability 21 7 Contact us 22 p h o t o v o l t a i k f o r u m c o m ...

Page 2: ...e array of modules installed with the Maximum permitted system voltage and the rating current and voltage of the sub equipments such as regulators and inverters The maximum permitted system voltage DC of the modules sold in America and Canada is 600V This module has a Class C Fire Rating and must be installed over a roof which is with appropriate fire resistance Before mounting the module please c...

Page 3: ...s All installations must be performed in compliance with the National Electrical Code NEC and modules installed in Canada need to follow Canadian electric code The installation work of the PV array can only be done under the protection of sun sheltering covers or sunshades and only qualified person can install or perform maintenance work on this module Follow the battery manufacture s recommendati...

Page 4: ...to the PV output Once the PV module has been shipped to the installation site all of the parts should be unpacked properly with care Do not stand or step on the PV module like below pictures show this is prohibited and There can be risks of micro crack which may cause a sharp declince of module s power performance what s more it may threat your safty Only PV modules with the same cell size should ...

Page 5: ...rdless of whether the PV module is connected to or disconnect from the system Do not expose the PV module to excessive loads on the surface of the PV module or twist the frame Do not hit or put excessive load on the glass or back sheet this may break the cells or cause micro crack During the operation don t use sharp tools to wipe the back sheet and glass it would leave scratch on the module Do no...

Page 6: ...ries the battery must be installed in a manner which will protect the performance of the system and the safety of its users Follow the battery manufacturer s guidelines concerning installation operation and maintenance recommendations In general the battery or battery bank should be away from the main flow of people and animal traffic Select a battery site that is protected from sunlight rain snow...

Page 7: ...hould confirm below important things 1 Visual check before installation to make sure there is no bug in the packing and junction box as well as the surface of module If have remove and clean it 2 Check the series number is right or not Note Jinko modules are designed to meet a maximum positive or upward and negative or downward pressure of 30 lb ft When mounting modules in snow prone or high wind ...

Page 8: ...least four clamps on each module two clamps should be attached on each long or short sides of the module Depending on the local wind and snow loads if excessive pressure load is expected additional clamps or support would be required to ensure the module can bear the load The applied torque should be big enough to fix it steadily about 8 Newton meter for safety you d better follow the clamps manuf...

Page 9: ...Rev C 9 Figure3 above PV module installed at long side with Clamp fitting method p h o t o v o l t a i k f o r u m c o m ...

Page 10: ...able 1 above Mechanical dimensions when modules installed at long side with Clamp fitting method Figure 4 above PV module installed at short side with Clamp fitting method p h o t o v o l t a i k f o r u m c o m ...

Page 11: ...ules will be rise when the temperature drops For example with JKM190M 72 modules Max System voltage is 600V the maximum series modules configuration number should NEVER can exceed N 13 600V 45 2V 13 2 c PV module connect in parallel should have similar voltage As reference the maximum number of modules in parallel M can be easily calculated by dividing the maximum rated current indicated in the el...

Page 12: ... Not that a stainless steel star washer is used between the ground wire and module frame see picture below This washer is used to avoid correosion due to dissimilar metals Tighten the screw securely f Follow the requirements of applicable local and national electrical codes g These modules contain factory installed bypass diode if these modules are incorrectly connected to each other the bypass di...

Page 13: ...nd mounting brackets are tight adjust and tighten as necessary 5 Electrical specification The module electrical rating are measured under Standard Test Conditions which are 1000W m2 irradiance with AM 1 5 spectrum and 25 deg 77 F ambient temperature The module might produce more or less voltage or current than rating value in uncertainty condition Accordingly the values of ISC and VOC marked on th...

Page 14: ...Voltage Vmp 35 0V 35 3V 35 5V 35 8V 36 0V 36 4V 36 6V 36 8V 36 9V Maximum Power Current Imp 4 57A 4 67A 4 79A 4 90A 5 00A 5 09A 5 19A 5 30A 5 42 A Open circuit Voltage Voc 43 9V 44 1V 44 3V 44 7V 44 8V 45 0V 45 2V 45 4V 45 6V Short circuit Current Isc 4 93A 5 02A 5 12A 5 23A 5 29A 5 43A 5 56A 5 67A 5 80A Maximum system Voltage 600VDC Dimensions 1580 808x35mm 62 20 31 81x1 38inch 1580 808x45mm 62 2...

Page 15: ...mp 48 0V 48 3V 48 5V 48 8V 49 0V 49 1V 49 5V 50 0V 50 5V 51 0V 51 5V Maximum Power Current Imp 4 58A 4 66A 4 74A 4 81A 4 89A 4 99A 5 05A 5 10A 5 15A 5 20A 5 24A Open circuit Voltage Voc 58 8V 58 9V 59 1V 59 1V 59 5V 59 7V 59 9V 60 5V 61 1V 61 7V 62 3V Short circuit Current Isc 5 01A 5 11A 5 19A 5 19A 5 35A 5 50A 5 61A 5 66A 5 72A 5 77A 5 82A Maximum system Voltage 600VDC Dimensions 1575 1082x45 62...

Page 16: ...age Vmp 28 7V 28 8V 29 0V 29 1V 29 2V 29 4V 29 6V 29 8V 30 0V 30 2V 30 4V Maximum Power Current Imp 6 97A 7 12A 7 24A 7 39A 7 53A 7 65A 7 78A 7 89A 8 01A 8 12A 8 23A Open circuit Voltage Voc 36 2V 36 3V 36 4V 36 5V 36 6V 36 7V 36 8V 36 9V 37 2V 37 4V 37 6V Short circuit Current Isc 7 65A 7 76A 7 88A 7 99A 8 10A 8 25A 8 35A 8 47A 8 56A 8 69A 8 81A Maximum system Voltage 600VDC Dimensions 1650 992x4...

Page 17: ...ge Vmp 36 5V 35 6V 35 8V 35 8V 35 9V 36 1V 36 3V 36 8V 37 2V 37 6V 38 0V 38 2V 38 5V 38 7V Maximum Power Current Imp 7 02A 7 16A 7 26A 7 40A 7 52A 7 61A 7 71A 7 74A 7 79A 7 85A 7 90A 7 09A 8 05A 8 13A Open circuit Voltage Voc 44 3V 44 4V 44 6V 44 8V 45 0V 45 3V 45 4V 45 4V 45 7V 46 0V 46 4V 46 8V 47 1V 47 4V Short circuit Current Isc 7 75A 7 90A 8 00A 8 13A 8 35A 8 37A 8 39A 8 41A 8 50A 8 59A 8 67...

Page 18: ...5Wp 300Wp 305Wp 310Wp 315Wp Maximum Power Voltage Vmp 34 7V 34 9V 35 0V 35 1V 35 2V 35 4V 35 5V 36 0V 36 4V 36 8V 37 2V 37 4V 37 7V 37 9V Maximum Power Current Imp 7 20A 7 31A 7 43A 7 55A 7 67A 7 77A 7 89A 7 92A 7 97A 8 02A 8 07A 8 16A 8 22A 8 31A Open circuit Voltage Voc 43 5V 43 7V 43 9V 44 1V 44 2V 44 4V 44 5V 44 7V 44 9V 45 2V 45 4V 45 6V 45 8V 46 1V Short circuit Current Isc 8 11A 8 20A 8 30A...

Page 19: ... 9V 30 0V 30 2V 30 4V 30 6V Maximum Power Current Imp 6 94A 7 07A 7 19A 7 34A 7 46A 7 57A 7 69A 7 83A 7 95A 8 06A 8 17A Open circuit Voltage Voc 36 5V 36 6V 36 7V 36 8V 36 9V 37 0V 37 1V 37 2V 37 3V 37 4V 37 6V Short circuit Current Isc 7 51A 7 62A 7 76A 7 85A 7 97A 8 08A 8 20A 8 31A 8 45A 8 58A 8 70A Maximum system Voltage 600VDC Dimensions 1650 992x45 64 97 39 06 x1 77 inch 1650x992x50 64 97 39 ...

Page 20: ...y Jinko for any infringement of patents or other rights of third parties which may result from use of the PV product NO license is granted by implication or otherwise under any patent or patent rights The information in this manual is based on Jinko s knowledge and experience and is believed to be reliable but such information including product specification without limitations and suggestions do ...

Page 21: ...iangxi Manufacture base No 1 Jingko Road Shangrao Economic Development Zone Jiangxi Province China Postcode 334100 Tel 86 793 8588188 Fax 86 793 8461152 Jinko solar Import and Export co LTD Xuri District Shangrao Economic Development Zone Jiangxi Province CHINA Postcode 334100 Tel 86 793 8618987 Fax 86 793 8461152 Customer Service cs jinkosolar com p h o t o v o l t a i k f o r u m c o m ...