background image

Portable BACnet/IP to MS/TP Router

Installation Instructions

Applications

The Portable BACnet

®

/Internet Protocol to MS/TP Router (TL-BRTRP-0) routes information between

BACnet/IP and MS/TP networks. It is intended to be used as an interface between the following

applications:
• Controller Configuration Tool (CCT) software (running on your computer) and 

Metasys

®

 BACnet

Controllers (CGMs, CVMs, FACs, FECs, and VMAs)

• FX CommPro BACnet software (running on your computer) and Facility Explorer

®

 (FX) Controllers

fitted with BACnet MS/TP communication cards

Note: 

CCT must be at Release 5.3 or later to support the BACnet routing connection.

To configure the BACnet/IP to MS/TP router, use the router webpage.
The router electronics exist in a small portable case and are powered from the computer USB port;

however, no USB drivers are needed. The router contains a 10/100 Mbps Ethernet Auto-Medium

Dependent Interface Crossover (MDIX) port and an MS/TP compatible port.
The MS/TP port offers a choice of EIA-485 connectors (an RJ-11 connector or a 3-pin terminal block

with removable plug) and is optically isolated from USB power. The MS/TP port can support 127

devices. The MS/TP port also supports up to 32 devices on a single segment, and you can use

repeaters to add additional devices or to extend bus length. All MS/TP baud rates are supported.

Installation

Parts included

Included in this package are the following items:
• BACnet/IP to MS/TP Router

Portable BACnet/IP to MS/TP Router Installation Guide (Part No. 24-10414-2)

• USB cable
• CAT5 Ethernet cable

(barcode for factory use only)

TL-BRTRP-0

*24104142G*

Part No. 24-10414-2   Rev. G
2019-07-16

Summary of Contents for TL-BRTRP-0

Page 1: ...ics exist in a small portable case and are powered from the computer USB port however no USB drivers are needed The router contains a 10 100 Mbps Ethernet Auto Medium Dependent Interface Crossover MDIX port and an MS TP compatible port The MS TP port offers a choice of EIA 485 connectors an RJ 11 connector or a 3 pin terminal block with removable plug and is optically isolated from USB power The M...

Page 2: ...e unused RJ 45 Medium Dependent Interface MDI Ethernet Pin 1 TD 2 TD 3 RD 6 RD All other pins are unused USB port The BACnet router has a USB 2 0 Type B receptacle which is only used to obtain power from a computer No communications are supported via the USB port Note Since no USB driver is required disregard the unknown hardware window that appears when you connect the BACnet router to a computer...

Page 3: ...Cnet router to the FC RJ12 connector of a Metasys and FX controller A standard modular jack 6 pin cable does not function correctly The following figure and table provide the pinout required for the custom cable Figure 2 BACnet router to Field Controller cable pinout Table2 Custom RJ 11 Cable Connections BACnet Router Plug Field Controller Plug Terminal 2 Terminal 2 Terminal 4 COM Terminal 5 COM T...

Page 4: ... when sufficient power is provided from the USB host ETH An Ethernet LED glows green for 100 Mbps and yellow for 10 Mbps also indicates activities by flashing MS TP A green LED flashes when the router receives MS TP traffic Webpage consideration The BACnet IP to MS TP Router contains a web server that can be accessed from any Internet compatible computer on the local network Microsoft Internet Exp...

Page 5: ...ll the Internet Protocol TCP IP protocol 5 Click Use the following IP address and enter the values defined in Table 5 6 Click OK Windows Vista and later 1 Open the control panel 2 Click on Network and Sharing Center 3 In the View your active networks section click the Local Area Connection or Ethernet link or click the Internet connection name next to Connections 4 On the Local Area Connection or ...

Page 6: ...vices on the same BACnet network must have the same BACnet IP UDP port assignment Normally you do not need to change this value If you do avoid well known ports that have hexadecimal addresses such as 15 17 or 50 Instead choose port numbers in the range of BAC1 through BACF Default Value BAC0 hexadecimal Note MS CCT and FX CommPro BACnet identify the BACnet IP UDP port number in decimal format whi...

Page 7: ...exceed the highest MAC address for any master on the network Optimum performance occurs when this value equals the highest MAC address all masters use sequential MAC addresses Default Value 127 Max Info Frames Enter the maximum number of messages that can route onto the MS TP network by the router per token pass The range is 1 to 100 and the typical values are above 20 Smaller values provide less ...

Page 8: ...idity 10 to 95 noncondensing Signaling USB 1 1 2 0 compatible Ethernet 10BASE T 100BASE TX MS TP EIA 485 American National Standards Institute American Society of Heating Refrigerating and Air Conditioning Engineers ANSI ASHRAE 135 2004 Cable Length Limit USB 5 m Ethernet 100 m MS TP 1 200 m for 18 AWG MS TP bps 9600 19 200 38 400 76 800 MS TP Node Limit 127 devices 32 devices per segment LEDs MS ...

Page 9: ...55022 Class A CE Mark ROHS Patents Patents http jcipat com Product warranty This product is covered by a limited warranty details of which can be found at www johnsoncontrols com buildingswarranty Points of single contact APAC Europe NA SA JOHNSON CONTROLS C O CONTROLS PRODUCT MANAGEMENT NO 32 CHANGJIJANG RD NEW DISTRICT WUXI JIANGSU PROVINCE 214028 CHINA JOHNSON CONTROLS WESTENDHOF 3 45143 ESSEN ...

Page 10: ...www johnsoncontrols com ...

Reviews: