Series TY-L – 5.6 and 8.0 K-factor
Upright, Pendent, and Recessed Pendent Sprinklers
Standard Response, Standard Coverage
Page 1 of 6
MAY 2020
TFP110
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the “INSTALLER
WARNING” that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Worldwide
Contacts
www.tyco-fire.com
General
Description
The TYCO Series TY-L 5.6 and
8.0 K-factor Upright, Pendent,
and Recessed Pendent Sprin-
klers described herein are stan-
dard response, standard coverage,
solder type spray sprinklers. They are
designed for use in light, ordinary, and
extra-hazard commercial occupan-
cies such as banks, hotels, shopping
malls, factories, refineries, and chemi-
cal plants.
The Series TY-L Recessed Pendent
Sprinkler, where applicable, is
intended for use in areas with a fin-
ished ceiling. It uses a two-piece
Style 20 (1/2 in. NPT) or Style 30
(3/4 in. NPT) Recessed Escutcheon.
The Recessed Escutcheon provides
1/4 in. (6,4 mm) of recessed adjust-
ment or up to 1/2 in. (12,7 mm) of total
adjustment from the flush pendent
position. The adjustment provided by
the Recessed Escutcheon reduces the
accuracy to which the fixed pipe drops
to the sprinklers must be cut.
Corrosion-resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
what would be obtained when exposed
to corrosive atmospheres. Although
corrosion-resistant coated sprinklers
have passed the standard corrosion
tests of the applicable approval agen-
cies, the testing is not representative
of all possible corrosive atmospheres.
Consequently, it is recommended
that the end-user be consulted about
the suitability of these coatings for
any given corrosive environment. The
effects of ambient temperature, con-
centration of chemicals, and gas/
chemical velocity, should be consid-
ered as a minimum, along with the cor-
rosive nature of the chemical to which
the sprinklers will be exposed.
An intermediate level version of the
Series TY-L Pendent Sprinkler can be
obtained by utilizing the Series TY-L
Pendent Sprinkler in combination with
the Model S Shield.
NOTICE
The Series TY-L 5.6 and 8.0 K-fac-
tor Upright, Pendent, and Recessed
Pendent Sprinklers described herein
must be installed and maintained in
compliance with this document, as
well as with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards of any other authorities
having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
NFPA 13 prohibits installation of 1/2 in.
NPT sprinklers with K-factors greater
than 5.6 in new construction. They are
intended for retrofit in existing sprinkler
systems only.
Sprinkler
Identification
Number (SIN)
TY3111 � � � Upright 5�6K, 1/2 in� NPT
TY3211 � � �Pendent 5�6K, 1/2 in� NPT
TY4111 � � � Upright 8�0K, 3/4 in� NPT
TY4211 � � �Pendent 8�0K, 3/4 in� NPT
TY4811 � � � Upright 8�0K, 1/2 in� NPT
TY4911 � � �Pendent 8�0K, 1/2 in� NPT
TY3111 is a re-designation for S1800 and G3111
TY3211 is a re-designation for S1801 and G3112
TY4111 is a re-designation for S1810 and G3101
TY4211 is a re-designation for S1811 and G3102
TY4811 is a re-designation for S1805
TY4911 is a re-designation for S1806