background image

Ultra K17 — 16.8 K-factor 

Upright Control Mode Specific Application Sprinkler 

Standard Response, 155°F (68°C) & 200°F (93°C)

Page 1 of 4 

AUGUST 2018 

TFP330

IMPORTANT

Refer to Technical Data Sheet 

TFP2300 for warnings pertaining to 

regulatory and health information.
Always refer to Technical Data 

Sheet TFP700 for the “INSTALLER  

WARNING” that provides cautions 

with respect to handling and instal-

lation of sprinkler systems and com-

ponents. Improper handling and 

installation can permanently damage 

a sprinkler system or its compo-

nents and cause the sprinkler to fail  

to operate in a fire situation or cause  

it to operate prematurely.

Worldwide 

Contacts

www.tyco-fire.com

General 

Description

The TYCO 16.8 K-factor, Ultra K17, 

Standard Response, Upright Control 

Mode Specific Application Sprinkler 

(Ref. Figure 1) is an automatic sprin-

kler of the frangible bulb type. It is 

intended for use with National Fire Pro-

tection Association Control Mode Spe-

cific Application installation criteria for 

the protection of high piled storage. It 

may also be utilized as a 16.8 K-fac-

tor, upright, standard response storage 

sprinkler in accordance with Factory 

Mutual Loss Prevention Data Sheets. 

See FM 2-0 and 8-9 for specific design 

and installation criteria.
The Ultra K17 Sprinkler can provide a 

higher level of protection than other 

standard spray sprinklers and, in some 

cases, it can provide an economi-

cal advantage by eliminating in-rack 

sprinklers.
Applications for the Ultra K17 Upright 

Control Mode Specific Application 

Sprinkler are expanding beyond the 

current specific application listings/

approvals. For information regard-

ing research fire tests which may be 

acceptable to an authority having juris-

diction, please contact the Technical 

Services Department.

NOTICE

The Ultra K17, Standard Response, 

Upright Control Mode Specific Applica-

tion Sprinkler described herein must be 

installed and maintained in compliance 

with this document and with the appli-

cable standards of the National Fire 

Protection Association, in addition to 

the standards of any authorities having 

jurisdiction. Failure to do so may impair 

the performance of these devices.
The owner is responsible for main-

taining their fire protection system 

and devices in proper operating con-

dition. Contact the installing contrac-

tor or product manufacturer with any 

questions.

Sprinkler 

Identification 

Number (SIN)

Refer to Table A for sprinkler identification 
number.

Technical 

Data

Approvals

UL and C-UL Listed 

FM and NYC Approved
Refer to Table C for specific details on 

laboratory listings and approvals. The 

approvals apply to the service conditions 

indicated in the Design Criteria section.

Finish

Natural Brass

Physical Characteristics

Frame  . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Button . . . . . . . . . . . . . . . . . . . . . . . . . . . .Bronze

Sealing Assembly  . .Beryllium Nickel w/TEFLON

Bulb (5 mm) . . . . . . . . . . . . . . . . . . . . . . . . .Glass

Compression Screw . . . . . . . . . . . . . . . . . .Brass

Deflector  . . . . . . . . . . . . . . Chrome Plated Brass

Additional Technical Data

Refer to Table A for additional technical 

data.

Operation

The glass bulb contains a fluid that 

expands when exposed to heat. When 

the rated temperature is reached, the 

fluid expands sufficiently to shatter the 

glass bulb, allowing the sprinkler to 

activate and flow water.

Summary of Contents for tyco ULTRA K17

Page 1: ...7 Upright Control Mode Specific Application Sprinkler are expanding beyond the current specific application listings approvals For information regard ing research fire tests which may be acceptable to an authority having juris diction please contact the Technical Services Department NOTICE The Ultra K17 Standard Response Upright Control Mode Specific Applica tion Sprinkler described herein must be...

Page 2: ...lled with the applicable storage sprinkler guide lines provided by Factory Mutual FM guidelines may differ from UL and C UL Listing criteria Item Description Sprinkler Identification Number SIN TY7153 TY7153 is a redesignation for C7153 G1887 and S8042 K factor gpm psi lpm bar 16 8 gpm psi 241 9 lpm bar Temperature Rating ºF ºC 1 155ºF 68ºC 1 200ºF 93ºC Thread Size 3 4 in NPT Sprinkler Orientation...

Page 3: ...IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Solid Pile or Palletized Storage of Class I IV and Group A or B Plastics Refer to NFPA 13 Refer to FM 2 0 and 8 9 Idle Pallet Storage Refer to NFPA 13 Refer to FM 2 0 8 9 and 8 24 Rubber Tire Storage Refer to NFPA 13 Refer to FM 2 0 and 8 3 Roll Paper Storage Refer to the Standard Refer to NFPA 13 Refer to FM 8 21 Flammable Igni...

Page 4: ...onnel who may be affected by this action must be notified Sprinklers that are found to be leaking or exhibiting visible signs of corrosion must be replaced Automatic sprinklers must never be painted plated coated or other wise altered after leaving the factory Modified sprinklers must be replaced Sprinklers that have been exposed to corrosive products of combustion but have not operated should be ...

Reviews: