background image

WT-ROUTER Router Installation Instructions

1

 Refer to the 

QuickLIT website

 for the most up-to-date version of this document.

Application

The WT-ROUTER Router relays wireless 
transmissions from a Johnson Controls® WT-4000 
Series Pneumatic-to-Direct Digital Control (DDC) 
Room Thermostat to other WT-ROUTER Routers or 
to a Johnson Controls WT-BAC-IP Gateway. Adding 
routers to a wireless mesh network enhances the 
robustness of the network by extending the wireless 
mesh communication range up to 750 ft (229 m). 
In addition, the routers provide multiple routes of 
communication with the gateway.

The WT-ROUTER Router installs in minutes with no 
need to run network cables. An 

STS

 LED indicator 

(Figure 1) allows for strategic positioning in areas with 
reliable network connectivity. The router is powered by 
a low-voltage 5 to 30 VDC power supply.

The WT-ROUTER Router is designed for indoor, 
intra-building applications only. The router uses 
direct-sequence, spread-spectrum RF technology, 
and operates on the 2.4 GHz Industrial, Scientific, 
and Medical (ISM) band. The router also meets the 
IEEE 802.15.4 standard for low power, low duty cycle 
RF transmitting systems. 

 

North American Emissions Compliance

United States 

Canada 

IMPORTANT:

Use the WT-ROUTER Router only to 

provide an input to equipment under normal 
operating conditions. Where failure or malfunction of 
the router could lead to personal injury or property 
damage to the controlled equipment or other 
property, additional precautions must be designed 
into the control system. Incorporate and maintain 
other devices, such as supervisory or alarm systems 
or safety or limit controls, intended to warn of or 
protect against failure or malfunction of the router.

Compliance Statement (Part 15.19)

This device complies with Part 15 of the FCC Rules. 
Operation is subject to the following two conditions:

1.

This device may not cause harmful interference, 
and

2.

This device must accept any interference 
received, including interference that may cause 
undesired operation.

Warning (Part 15.21)

Changes or modifications not expressly approved by 
the party responsible for compliance could void the 
user’s authority to operate the equipment.

Industry Canada Statement

The term 

IC

 before the certification/registration 

number only signifies that the Industry Canada 
technical specifications were met.

Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est 
conforme aux spécifications techniques d'Industry 
Canada.

WT-ROUTER Router

Installation Instructions

WT-ROUTER

Part No. 24-10732-13, Rev. B

Issued August 2017

24- 10732- 13,  Rev .  B

Summary of Contents for WT-ROUTER

Page 1: ...tes Canada IMPORTANT Use the WT ROUTER Router only to provide an input to equipment under normal operating conditions Where failure or malfunction of the router could lead to personal injury or property damage to the controlled equipment or other property additional precautions must be designed into the control system Incorporate and maintain other devices such as supervisory or alarm systems or s...

Page 2: ...he device the router is not user serviceable Parts Included one WT ROUTER Router one power adaptor one installation instructions sheet Mounting The WT ROUTER Router can be surface mounted using two field furnished screws Mount the unit to the surface at the two mounting hole locations on the device Figure 1 The router can also be secured to a bracket above a drop ceiling using field furnished tie ...

Page 3: ... installing the router near equipment that may interfere with the 2 4 GHz RF signal such as cordless telephones or Wi Fi access points that operate on the 2 4 GHz ISM band 2 Document the device ID and location of each router on the floor plan prior to installation The device ID sticker is located on the back of the router Note You may operate the router while it is resting on a desktop or mounted ...

Page 4: ...ge 3 1 VDC Wireless Band Direct sequence spread spectrum 2 4 GHz ISM band Operating Frequency Range 2 405 to 2 475 MHz Channels Quantity 15 Spacing 5 MHz Transmissions Power 18 dBm maximum Rate 250 Kbits per second Ambient Conditions Operating 14 to 131 F 10 to 55 C 5 to 95 RH noncondensing Storage 40 to 185 F 40 to 85 C 5 to 95 RH noncondensing Materials Gray ABS plastic housing Compliance United...

Page 5: ...Installation Instructions 5 Metasys and Johnson Controls are registered trademarks of Johnson Controls All other marks herein are the marks of their respective owners 2017 Johnson Controls Building Technologies Solutions 507 E Michigan Street Milwaukee WI 53202 ...