JUMO Dtrans T100

Screw-in RTD temperature probe

with transmitter

B 902815.0

Operating Instructions

201

6

-0

2

-

17

/00495568

Summary of Contents for Dtrans T100

Page 1: ...JUMO Dtrans T100 Screw in RTD temperature probe with transmitter B 902815 0 Operating Instructions 2016 02 17 00495568 ...

Page 2: ......

Page 3: ...ction diagram 8 3 2 Connection example with power supply unit 9 3 3 Connection example with supply isolator 9 4 Setup program 10 4 1 Configurable parameters 11 4 2 Software requirements 12 4 3 Important information about Windows user administration 12 4 4 Fine calibration 12 4 5 Connection arrangement 13 5 Dimensions 15 5 1 Basic types 15 5 2 Process connection PA 16 6 Technical data 19 ...

Page 4: ...tter is used for measuring temperatures from 50 to 150 C 58 to 302 F with an extension up to 260 C 500 F The range fine calibration measuring circuit monitoring etc can all be configured through the setup program The 4 to 20 mA or reversed 20 to 4 mA output signal that is provided is linear with temperature The instrument is designed for industrial application and complies with the European standa...

Page 5: ...D temperature probe with programmable transmitter connection M12 1 machine connector high temperature version with extension parts in contact with the medium electrolytically polished surface roughness Ra 0 8 μm 2 Operating temperature in C x 370 50 to 150 C max transmitter temperature 85 C x 386 50 to 260 C max transmitter temperature 85 C 3 Measuring insert x x 1013 1 Pt1000 in 4 wire circuit 4 ...

Page 6: ...N 32676 x x 681 Weld in ball socket with clamping thread x x 682 Weld in socket with CIP compliant conical seal x x 684 Varivent connection DN 15 10 with EHEDG certification x x 685 Varivent connection DN 32 25 with EHEDG certification x x 686 Varivent connection DN 50 40 with EHEDG certification x x 840 Ball weld in pocket material 316 Ti x x 997 JUMO PEKA with EHEDG certification 8 Protection tu...

Page 7: ...12 1 socket length 2 meters part no 00404585 5 pole contact box M12 1 straight without connecting cable to be patched by the customer part no 00419130 5 pole contact box M12 1 angled without connecting cable to be patched by the customer part no 00419133 PC interface with USB TTL converter and USB cable part no 00456352 Transmitter supply units 1 way and 4 way data sheet 707500 Ex i power supply i...

Page 8: ...35 V DC Current output 4 to 20 mA Setup communication via special configuration cable for configuration only continuous operation is not permissible V Caution After the machine connector has been plugged in correctly care must be taken that the prescribed voltage supply is applied and the pins are assigned correctly during connection If this is not observed the device will be destroyed 1 3 V V 2 4...

Page 9: ...9 3 Installation 3 2 Connection example with power supply unit 3 3 Connection example with supply isolator ...

Page 10: ...J 45 Western plug In addition you will also need the PVC connecting cable 2 meters long The PC interface with USB TTL converter and USB cable is needed for connecting up to a PC see accessories for the programmable 2 wire transmitter H In order to configure the 2 wire transmitter it must be connected to the voltage supply If no power supply unit or supply isolator is available the transmitter can ...

Page 11: ...t ID TAG number Measuring range C or F configurable Offset Range start Range end 50 150 C or 260 C with extension 0 0 C 0 0 C 100 0 C Analog output Reversion of the output Signal on probe break or short circuit 4 to 20 mA 20 to 4 mA 3 8 mA 21 mA 4 to 20 mA 21 mA Further parameters Filter time constant Unit 0 s 125 s C F 0 1 s C ...

Page 12: ...h the program The user must have administrator rights during the installation of the software After installation the rights can be restricted again If this is disregarded it is not possible to ensure a correct and complete installation 4 4 Fine calibration Fine calibration means adjustment of the output signal Fine calibration is carried out with the aid of the setup program Using the setup progra...

Page 13: ...ug b to the PC interface with USB TTL converter c This ensure a safe grounding on the PC laptop side 2 Connect the RJ 45 Western plug d of the configuration cable e to the PC interface with USB TTL converter c and the M12 1 socket f to the JUMO Dtrans T100 g 3 Connect the M12 1 socket i of the PVC connecting cable j to the M12 1 plug h of the configuration cable e 4 Connect the 8 to 35 V DC voltag...

Page 14: ...e black brown PIN 1 blue PIN 3 approx 600 PC interface with USB TTL converter Part no 00456352 with USB cable USB type A plug USB type B plug RJ 45 Western plug M12 socket Configuration cable Part no 00484692 JUMO Dtrans T100 M12 socket M12 plug PVC 4 pole connecting cable Part no 00404585 8 35 VDC a b c d approx 2000 approx 600 h e f i j g ...

Page 15: ...15 5 Dimensions 5 1 Basic types Basic type 902815 20 Basic type 902815 21 with extension ...

Page 16: ...n PA Screw fitting Screw fitting with CIP compliant conical seal Clamping nipple according to DIN 32676 clamp PA G 103 3 8 104 1 2 PA 380 PA DN D1 PA DN D1 Ø 25 613 40 1 5 Ø 50 5 611 10 20 Ø 34 616 50 2 Ø 64 613 25 1 Ø 50 5 617 2 5 Ø 77 5 ...

Page 17: ... cap nut according to DIN 11851 milk pipe fitting Weld in socket with CIP compliant conical seal PA 681 PA DN D1 D2 D3 D4 L1 L2 601 10 Ø 22 Ø 18 RD 28 1 8 Ø 38 9 18 604 25 Ø 44 Ø 35 RD 52 1 6 Ø 63 13 21 605 32 Ø 50 Ø 41 RD 58 1 6 Ø 70 13 21 28 EL 15 41 D 30 Ø G1 2 18 Ø PA 682 ...

Page 18: ...ld in pocket JUMO PEKA PA 997 Process connection adapter see data sheet 409711 PA DN D1 684 15 10 Ø 31 685 32 25 Ø 50 686 50 40 Ø 68 PA 840 Varivent Clamp Aseptic Weld in socket DN 25 32 DN 25 32 40 DN 40 Ø 55 mm DN 40 125 DN 50 DN 50 NKS DN 40 ...

Page 19: ...to account Response time Water 0 4 m s protection tube standard t0 5 5 s t0 9 12 s Water 0 4 m s protection tube stepped t0 5 2 s t0 9 5 s Air 3 0 m s protection tube standard t0 5 40 s t0 9 110 s Air 3 0 m s protection tube stepped t0 5 21 s t0 9 70 s Input Shortest span 10 K Sampling rate 1 measurement per second Input filter 1st order digital filter filter constant is adjustable within the rang...

Page 20: ...perature Maximum burden RB RB Ub 8 V devided by 23 mA max 600 Ω Burden error 0 02 per 100 Ω The value refers to the range end value 20 mA Settling time on a temperature change 5 s Settling time after a switch on or reset 5 s Measuring accuracy of electronics 0 1 C or 0 08 The value refers to the measuring span that was set the larger value applies Electrical data Voltage supply Ub DC 8 to 35 V pin...

Page 21: ...temperature range 30 to 90 C Ambient temperature error 15 ppm C range end value 200 50 ppm C measuring range set Δυ Δυ deviation of ambient temperature from the reference temperature Calibration reference conditions DC 24 V at 25 C 5 C 77 F 9 F Climatic conditions According to IEC 60068 2 30 rel humidity 95 with condensation Vibration strength According to IEC 60068 2 6 according to GL characteris...

Page 22: ...22 6 Technical data ...

Page 23: ......

Page 24: ...s 36035 Fulda Germany Phone 49 661 6003 0 Fax 49 661 6003 607 E mail mail jumo net Internet www jumo net JUMO House Temple Bank Riverway Harlow Essex CM20 2DY UK Phone 44 1279 63 55 33 Fax 44 1279 63 52 62 E mail sales jumo co uk Internet www jumo co uk 6733 Myers Road East Syracuse NY 13057 USA Phone 315 437 5866 1 800 554 5866 Fax 315 437 5860 E mail info us jumo net Internet www jumousa com ...