Universal amplifier for rail mounting 200-500 W 

Light Management  

Universal amplifier for rail mounting 200-500 W 

Art. No. ULZ 1215 REG

Operating instructions 

1 Safety instructions 

Electrical equipment may only be installed and fitted by electrically skilled persons. 

Serious injuries, fire or property damage possible. Please read and follow manual fully. 

Danger of electric shock. Device is not suitable for disconnection from supply voltage. 
The load is not electrically isolated from the mains even when the device is switched off. 

Danger of electric shock. Always disconnect before carrying out work on the devise or 
load. At the same time, take into account all circuit breakers that supply dangerous 
voltage to the device or load. 

Fire hazard. For operation with inductive transformers, each transformer must be fused 
on the primary side in accordance with the manufacturer's instructions. Only safety 
transformers according to EN 61558-2-6 may be used. 

A minimum power of 10 kVA is required for operation on isolating transformer networks. 
Otherwise it is not ensured that the dimmer will correctly recognise the dimming 
principle suitable for the load. Device can be damaged. 

These instructions are an integral part of the product, and must remain with the end 
customer. 

2 Device components 

Figure 1: Device components 

(1)  Power booster 
(2)  LED on/off: power booster on/off 

3 Function 

Intended use 

Power enhancement for the Tronic or universal dimmers contained in the reference list 
(see section Technical data) 

Switching and dimming of incandescent lamps, HV halogen lamps and Tronic or dimmable 
inductive transformers with halogen lamps. 

1/7 

82557263 
J:0082557263 

27.02.2013 

Summary of Contents for ULZ 1215 REG

Page 1: ...re hazard For operation with inductive transformers each transformer must be fused on the primary side in accordance with the manufacturer s instructions Only safety transformers according to EN 61558 2 6 may be used A minimum power of 10 kVA is required for operation on isolating transformer networks Otherwise it is not ensured that the dimmer will correctly recognise the dimming principle suitab...

Page 2: ... represent any defect in the device i Brightness differences between the lighting on a dimmer without powerpower booster and a dimmer with power booster are possible 4 Information for electrically skilled persons 4 1 Fitting and electrical connection DANGER Electrical shock when live parts are touched Electrical shocks can be fatal Before carrying out work on the device or load disengage all the c...

Page 3: ...Figure 2 Connection diagram with RMD dimmer Figure 3 Connection diagram with FM dimmer 3 7 82557263 J 0082557263 27 02 2013 Light Management Universal amplifier for rail mounting 200 500 W ...

Page 4: ...r boosters figure 4 o If multiple circuit breakers supply dangerous voltages to the device or load couple the circuit breakers to ensure tripping Calculation example for the number of power boosters required PL Load to be dimmed e g 2200 W PD Max dimmer load e g 500 W PLZ Max universal power extension load e g B 500 W PLZG Power that the power boosters have to provide n Number of power boosters re...

Page 5: ...esult capacitive inductive not permitted Minimum connected load 200 W VA Power reduction per 5 C in excess of 45 C 15 Connection single stranded max 4 mm finely stranded with conductor sleeve 0 5 2 5 mm finely stranded without conductor sleeve 0 75 4 mm Number of power boosters see reference list Total length power cable max 100 m Fitting width 36 mm 2 modules Figure 5 Reference list of convention...

Page 6: ...om mains switch off circuit breakers Let system cool down for approx 15 minutes Check the installation situation Reduce the connected load Switch circuit breakers and system on again i Load is initially distributed to the remaining devices The further behaviour of the system depends on the dimmer used and the number utilisation and installation situation of the devices 5 3 Warranty We reserve the ...

Page 7: ...chalksmühle Telefon 49 23 55 8 06 0 Telefax 49 23 55 8 06 2 04 kundencenter jung de www jung de Service Center Kupferstr 17 19 44532 Lünen Germany 7 7 82557263 J 0082557263 27 02 2013 Light Management Universal amplifier for rail mounting 200 500 W ...