INSTALLING AND OPERATING THE KELCO F21 SERIES FLOW SWITCH

INTRODUCTION

This F21 flow switch may have been supplied in one of several available configurations.  The model number of the specific switch is located inside the lid of the electrical housing.  The 

F21 series flow switch is a versatile heavy-duty paddle flow switch suitable for detecting flow of liquids in pipes of any diameter from 25 mm (1”) upward. This flow switch has several 

unique features:  

A) 

 The complete electrical assembly can be removed from the switch by undoing and removing the locking screw in the split clamp on the side of the switch’s electrical 

housing.  With the locking screw removed, the electrical housing can be pulled straight off the wet end of the switch.  Removing the electrical housing allows the wet end of the switch 

to be unscrewed from pipework without disturbing the cable connection to the switch.  This means the paddle of the switch can be changed, inspected or trimmed without the need to 

disturb the electrical connection to the switch.   replace and tighten the locking screw after completing any work on the wet end of the switch.   

B) 

 The standard version of the F21 flow 

switch has a built-in manual override.  On the end of the switch body underneath the cable entry port is a spring loaded push button.  Pressing this button actuates the switch, regardless 

of the state of flow.  Pumping systems can be manually started by pressing this button and holding it in until flow is established. The override button can be used to test control circuits 

and wiring during commissioning, without the need for water in the pipework.  The button is spring loaded so it can’t be inadvertently left in the on position and only overrides the flow 

switch while it is pressed.

Warning note on operating limitations: 

 Maximum  operating pressure of the  Polypropylene  F21-S must be linearly de-rated  as  operating  temperature is increased so that at 60°C 

the maximum permissible operating pressure for the switch is not more than one Bar Absolute.

INSTALLATION

OPERATING LIMITATIONS

ELECTRICAL DATA MICROSWITCH MODELS

Model

F21-S 

(All Poly)

F21-SS

(Stainless)

F21-D 

(Diesel)

Maximum operating pressure 

(Static or Dynamic) at ambient 

temperature

18 Bars 

(261 PSI)

200 Bars

 (2900 PSI)

200 Bars

 (2900 PSI)

Minimum burst  pressure at 

ambient temperature

45 Bars

 (652 PSI)

500 Bars 

(7251 PSI)

500 Bars 

(7251 PSI)

Maximum operating 

temperature

60ºC

 See note

 below

80ºC

80ºC 

Minimum operating

temperature

0ºC

0ºC

0ºC

Minimum liquid S.G.

0.8

0.8

0.8

RATED

VOLTAGE

NON INDUCTIVE LOADS

INDUCTIVE LOADS

RESISTIVE 

LOAD

LAMP LOAD

INDUCTIVE 

LOAD

MOTOR LOAD

NO

NC

NO

NC

NO

NC

NO

NC

125 VAC

15A

3A

1.5A

15A

5A

2.5A

250 VAC

15A

2.5A

1.25A

15A

3A

1.5A

500 VAC

10A

1.5A

0.75A

6A

1.5A

0.75

8 VDC

15A

3A

1.5A

15A

5A

2.5A

14 VDC

15A

3A

1.5A

10A

5A

2.5A

30 VDC

6A

3A

1.5A

5A

5A

2.5A

125 VDC

0.5A

0.5A

0.25A

0.05A

0.05A

0.05A

250 VDC

0.5A

0.5A

0.25A

0.03A

0.03A

0.03A

SWITCH

TYPE

CONTACT

SWITCHED 

POWER

SWITCHED VOLTAGE

MAXIMUM

SWITCHED CURRENT

(RESISTIVE)

CARRY

CURRENT

BREAKDOWN

VOLTAGE

TYPICAL

APPLICATIONS

DRY CONTACT

REED SWITCH

S.P.D.T BREAK

BEFORE MAKE

20W / VA

MAXIMUM

140V AC

150V DC

1 AMP

MAXIMUM

2 AMP

MAXIMUM

200V MINIMUM

PLC, TELEMETRY & GENERAL 

LOW VOLTAGE CONTROL

APPLICATIONS

The reed switch models are supplied with a high compliance single pole double  throw  reed  switch  suitable  for  all  low  wetting  current  and  low  voltage  applications.   Such 

applications include PLC control, signalling  in  telemetry  systems  and  relay logic  circuits.  

Note:

 the  reed  switch  models  are not  suitable  for use with  inductive  loads such as 

contactors or high wattage relays.

ELECTRICAL DATA REED SWITCH MODELS

Select a location for the flow switch in a straight run of pipe, ideally with five pipe diameters of straight pipe either side of the switch.  This will ensure a linear non turbulent flow acts 

against the paddle of the switch.  Do not install the flow switch in any location likely to expose it to turbulence, such as close to valves, pumps or pipe bends The idea is to install the 

switch in a location where there is a smooth flow of liquid past the paddle, and to obtain a stable non-chattering response from the flow switch.  The F21 flow switch can be mounted in 

either the suction or discharge pipe of a pump, the switch will work equally well in positive or negative pressure applications. 

The F21 flow switch has an extra long paddle so it can be used in large diameter pipes.  The paddle will require trimming if the flow 

switch is to be used in smaller diameter pipes.  The paddle can be cut and shaped as required using tin snips or a hacksaw.  Note, the 

paddle can be cut both in length and if required, in width.  Many installers maintain a more stable flow response can be obtained by 

narrowing down the paddle and avoiding turbulence close to the walls of the pipe. The F21 flow switch can be installed in any required 

orientation except on the under side of horizontal pipes.

Depending on the thread on the switch, a 25 mm, 1” BSP or 1” NPT threaded socket must be provided on the piping, to fit the flow 

switch.  This may be a tapping saddle or a pipe tee fitted with a threaded reducing bush, or a socket welded directly to the pipe.  Ensure 

that whatever fitting is used, sufficient clearance is allowed for the free movement of the paddle.  Normally a clearance to the full inside 

diameter of the 1” pipe thread will be required.  The F21 flow switch can be installed in a 1” pipe socket attached to a short stand off 

pipe, at 90° to the main pipe.  This method of mounting increases the sensitivity of the switch to low flows due to the extra leverage 

against the tip of a longer paddle.  If this mounting method is used make sure to leave extra clearance to allow for the full arc movement 

of the longer paddle. 

Use a suitable thread sealant and tighten the switch into the socket using the spanner flats provided on the switch body.  Do not tighten 

the switch into its socket by twisting the electrical housing of the switch, as damage to the flow switch may result.  Align the flow switch 

squarely to the axis of the pipe, with the direction of flow arrow on the side of the switch body parallel to the axis of the pipe and aligned 

in the direction of flow.  The F21 will not function correctly unless alignment is correct. When installing the flow switch in vertically 

aligned pipework, the sensitivity of the switch will be slightly increased; it will detect lower flows when flow is downward, and the 

sensitivity will be slightly decreased when flow is upward.  This is due to the effect of gravity on the dead weight of the paddle itself.  

This effect is more noticeable in larger pipes and low flows where long paddles may be used.

WARNING

Please read these installation and operating instructions fully and carefully before installing or servicing this level switch.  The F21 Series flow switch is 

mains voltage device.  Death or serious injury may  result if this switch is not correctly installed and operated.  All electrical work must be performed  by 

a fully qualified and licenced electrician.