DUCT SMOKE DETECTOR

SL-2000 SERIES

DESCRIPTION

The  SL-2000 Series Duct Smoke Detectors provide
early detection of smoke and combustion products pre-
sent in air moving through HVAC ducts. Air sampling is
accomplished by intake sampling tubes, which are
ordered separately. A standard length exhaust tube is
provided with each detector. These devices are designed
to prevent the recirculation of smoke in areas by the air
handling systems, fans, and blowers. Complete systems
may be shut down in the event of smoke detection.

OPERATION

The  SL-2000 Series is designed to operate in duct
widths from 12.0" to 10.0' (30.5 cm to 3.05m) with an air
velocity from 100-4000 fpm (0.5-20.3 mps). The 
SL-2000 Series will operate on any one of four input
voltages: 24 VAC, 24 VDC, 115 VAC, or 230 VAC. It
uses either a photoelectric or ionization smoke detector
head. Each detector contains two Form C and one Form
A alarm contact, which transfer in the event of smoke.
There is also one trouble contact, which supervises the
presence of input power and removal of the detector
head. A manual test/reset switch and visual indicators of
pilot and alarm are provided on the front of the detector.
Up to 30 SL-2000 Series units may be wired to use a
common test/reset function and to alarm simultaneously
when a single unit alarms. 

Power requirements

50/60 Hz (without

accessories)

24 VAC   @ 55 mA standby,

190 mA alarm

24 VDC   @ 15 mA standby,

70 mA alarm

115 VAC @ 16 mA standby,

32 mA alarm

230 VAC @ 10 mA standby,

20 mA alarm

Relay contact rating

Alarm (2)

SPDT, 10A, 115 VAC, resistive

Alarm (1)

SPST-NO, 2A, 115 VAC, 
resistive

Trouble (1)

SPDT, 10A, 115 VAC, resistive

Radioactive element

For SL-2000-N only 
Americium 241, 0.9  µCi

Air velocity

100-4000 fpm (0.5-20.3 mps)

Approvals

UL

268A; UROX.S2829

CSFM

3240-1004:105

MEA

73-92-E, Vol. 27

Ambient temp

SL-2000-N

32° to 155°F (0° to 68°C)

SL-2000-P

32° to 100°F (0° to 38°C)

Humidity

10% to 85% RH noncondensing

Material

Gray plastic back box, 
clear plastic cover

Weight

2.5 lb (1.13 kg)

Mounting

7" (17.8 cm) exhaust tube, sampling
tube end cap, mounting template
and  hardware supplied

Dimensions

13.5"L x 4.5"H x 2.25"D
(34.3 x 11.4 x 5.7 cm)

FEATURES

• Low flow technology, 100-4000 fpm
• Universal voltage: 24 VAC, 24 VDC, 115 VAC, or

230 VAC

• Two Form C and one Form A alarm contacts and

one trouble contact

• Interchangeable "plug-in" photoelectric or ioniza-

tion heads

• Compatible with building automation and fire

alarm systems

• Dust filtering included in detector head
• Interconnect up to 30 detectors for common 

functions

• Compatible with MS Series Remote Accessories
• Cover removal trouble indication
• Magnet test capability
• Front or rear loading sampling tubes
• Optional weatherproof enclosure

SPECIFICATIONS

SL-2000

April 2004