background image

Taktis Network Vision Annunciator
Information Guide

UL Version 1.04 |   May 2019 |   MAN-1434KE

Summary of Contents for Taktis TRC00NC-10

Page 1: ...Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE ...

Page 2: ...dvanced Replacements 5 Overview 6 Fascia 8 Internal Components 9 Installation 10 Before You Begin 10 Mounting the Vision Annunciator 12 Trim Ring 13 Wiring 16 Specifications 19 Cabling 20 Index 21 Glossary 22 Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 2 ...

Page 3: ...essly approved by Kentec Electronics Ltd could void the user s authority to operate this equipment under the rules and regulations of the FCC Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation Installation Install this product in accor...

Page 4: ...ailure l A product was damaged during shipping l An incorrect product was shipped l An order was placed using an incorrect part number l An order was placed using an incorrect part quantity l An order is no longer required Restocking fees may apply All returned products are tested to confirm operating failures experienced in the field If the product is found to be functional contractors must absor...

Page 5: ...aintain an acceptable line of credit Initiate the advanced replacement process by requesting an RMA number from a Tech Support representative Advanced replacements can be shipped to your location when the product is covered under warranty and when a replacement product is in stock l Advanced replacements can be expedited at the request of the contractor Shipping costs associated with this process ...

Page 6: ...ary controls of Taktis Fire Alarm Control Panels connected to the same network The Annunciator connects via the network interface and any number of repeaters can be connected up to the maximum number of nodes allowed by the network Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page ...

Page 7: ...ces for applications where access to fire alarm controls are inappropriate The Annunciator can be configured to display events from any combination of nodes on the network Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 7 Taktis Network Vision Annunciator Information Guide ...

Page 8: ...Fascia Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 8 ...

Page 9: ...Internal Components Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 9 Taktis Network Vision Annunciator Information Guide ...

Page 10: ...Fire Alarm Control Panel Installation Manual MAN 1431KE for more information q From the Annunciator GUI set the node number This requires User Access Level 3 q Configure the Annunciator and all nodes on the network q Test the Annunciator to verify proper operation based on the configuration WARNING The Annunciator must be installed by personnel familiar with electronic components Electronic compon...

Page 11: ...provided in the packaging l Mounting Hardware Without Optional Trim Ring 4 10 screws appropriate for mounting location With Optional Trim Ring 4 M4 x 8mm machine screws and 4 M4 plain washers Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 11 Taktis Network Vision Annunciator Information Guide ...

Page 12: ...by disconnecting the ground and removing the hinge pins 2 Using the enclosure as a template mark the position of the holes 3 Mount the enclosure using appropriate hardware Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 12 ...

Page 13: ...ce enclosure back box The diagram below shows the trim ring external and advised wall cut out dimensions Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 13 Taktis Network Vision Annunciator Information Guide ...

Page 14: ...ng Fitting Options Trim Ring Fold Tabs Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 14 ...

Page 15: ...s and M4 plain washers to mount the enclosure to the trim ring Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 15 Taktis Network Vision Annunciator Information Guide ...

Page 16: ...wer and network connections when using a dedicated power supply Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 16 ...

Page 17: ...he Taktis panel Do not insert more than one conductor per terminal Use wire nuts or other suitable splice connectors to connect the 24V DC cables to both the AUX 24V OUT and RTN terminals Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 17 Taktis Network Vision Annunciator Information Guide ...

Page 18: ... network wiring scheme featuring two panels and two annunciators Taktis Network Vision Annunciator Information Guide Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 18 ...

Page 19: ...ical Size 9 25 x 6 7 x 2 2 235 mm x 170 mm x 55 mm Display Full color 800 x 480 LCD with resistive touch screen and automatic backlight dimming Construction 18 SWG 1 2mm mild sheet steel IP30 rated Cable Entry 2 x 20 mm knockouts on top bottom 4 x 20 mm and 2 x 28 mm knockouts in back Finish Epoxy powder coated Color Red RAL3002 Gray BS 00 A 05 Black RAL9005 Weight 4 4 lbs 2 kg maximum Environment...

Page 20: ...his means that the total cable length between adjacent cable segments should not be more than 3900 feet 1200 meters It is not important how this distance is made up i e it could be 3000 feet 900 feet or 1950 feet 1950 feet The following diagram shows an example of these cabling limitations l The length of CABLE A CABLE B cannot exceed 3900 feet 1200 meters l The length of CABLE B CABLE C cannot ex...

Page 21: ... B Buzzer 19 C Cabling 19 Class A 3 F Fascia 8 10 N Network 6 10 19 T Terminals 17 Kentec Electronics Ltd Taktis Network Vision Annunciator Information Guide UL Version 1 04 May 2019 MAN 1434KE Page 21 Taktis Network Vision Annunciator Information Guide ...

Page 22: ...r B S gauge C Class A A wiring classification of circuits capable of transmitting an alarm signal during a single open or non simultaneous ground fault on a conductor Class B A wiring classification of circuits NOT capable of ransmitting an alarm signal beyond a single open or during a short between conductors Class X A wiring classification capable of transmitting an alarm signal during a single ...

Page 23: ...t that connects horns strobes speakers etc to the control panel S SLC Signaling Line Circuit A Signaling Line Circuit SLC carries data to and from the field devices for the fire alarm system and also carries power from the control panel to the devices Supervision Monitoring the integrity of a circuit or device to detect a fault condition that would prevent nor mal operation Taktis Network Vision A...