PD05M-PCR-LE/PD05S-PCR-LE 1

PART NO. Z1-005-530, I0025001
Sep 2020

PD05M-PCR-LE

PD05S-PCR-LE

Setup Guide

PCR-LE series Parallel Operation Driver

Thank you for purchasing the PCR-LE Series Parallel operation 
driver.
This option is used to perform master-slave parallel operation on 
the PCR-LE Series AC power supplies (excluding the PCR500LE 
and PCR1000LE; up to 5 units (power is 27 kVA or less)). Parallel 
operation is possible between different PCR-LE models as long as 
the number of units is 5 or less (power is 27 kVA or less).

The PD05M-PCR-LE is used on the master unit.
The PD05S-PCR-LE is used on slave units.

Number of PCR-LE 

operated in parallel 

Number of PD05M-

PCR-LE (for master)

Number of PD05S-

PCR-LE (for slave)

2

1

1

3

1

2

4

1

3

5

1

4

Features

•  Enabling PCR-LE AC Power Supplies to Generate Large-capaci-

ty, Multifunctional High-quality Output 
Using this product in combination with 2P05-PCR-LE single-
phase, three-wire output drivers or 3P05-PCR-LE three-phase 
output drivers creates a high capacity, multi-phase output AC 
power supply.

•  Expansion of Output Capacity in the Future or Temporarily  (eco-

nomical equipment investment)
Use of the Parallel Operation Driver allows expansion of the output 
capacity if a PCR-LE is small capacity and the capacity is to be 
increased later. Alternatively, PCR-LE installed singly can be inte-
grated for use if they are generally used at small capacity, but a 
large capacity is required due to provisional testing or the like.

Check at Unpacking

Upon reception of the product, confirm that the package contains 
the necessary accessories and that the device and accessories 
have not been damaged during transportation. If the device is 
damaged or any accessory is missing, notify Kikusui distributor/
agent.

Setup Guide

(This sheet, 1pc.)

PD05M-PCR-LE or

PD05S-PCR-LE (1pc.)

PD05M-PCR-LE only

Protection sockets(2 pcs.)

[84-49-0110]

Connecting cable

(70 cm, 1pc.)

91-88-0180

Power signal cable

(30 cm, 1pc.)

91-88-0182

PD05S-PCR-LE only

Functional limitations during paral-

lel operation

You will not be able to use the following features when you install 
this product.

Power-saving function (only when performing parallel operation 
using different models)
High speed response setting (FAST)

Firmware version of PCR-LE

When using the PD05M-PCR-LE/ PD05S-PCR-LE, the PCR-LE must 
be required with the firmware version of 3.00 or later. If the firmware 
version of the PCR-LE is 2.99 or previous version, the PCR-LE is 
required for the firmware update.
When using the PD05M-PCR-LE/ PD05S-PCR-LE, the firmware of 
all the PCR-LE series that make up the system must be the same.
To check the firmware version of the PCR-LE, refer to the operation 
manual of the PCR-LE series. In case, the PCR-LE needs update, 
contact your Kikusui agent or distributor.

Handling Precautions

 

„

Handling of the boards

•  Ground yourself by touching a grounded metal object before 

touching the board.

•  Avoid handling the interface board in an environment subject to 

strong static electricity.

•  For storage, provide electrostatic protection measures such as 

the anti-static bag accompanying the interface board.

•  Do not drop a board or subject it to other impact.
•  Do not install or uninstall the interface board with the power ON 

of the PCR-LE Series.

 

„

Handling of the cables

•  Do not damage the cable.
•  Do not pull, bend, or apply any other stress to the cable.

KIKUSUI ELECTRONICS CORP.

 

www.kikusui.co.jp

©2012 KIKUSUI Electronics Corp.

Summary of Contents for PCR-LE Series

Page 1: ...nd accessories have not been damaged during transportation If the device is damaged or any accessory is missing notify Kikusui distributor agent Setup Guide This sheet 1pc PD05M PCR LE or PD05S PCR LE 1pc PD05M PCR LE only Protection sockets 2 pcs 84 49 0110 Connecting cable 70 cm 1pc 91 88 0180 Power signal cable 30 cm 1pc 91 88 0182 PD05S PCR LE only Functional limitations during paral lel opera...

Page 2: ... panel 8 Follow the same procedure to install the other board This completes installation of the parallel board Connecting the Boards Use the master unit to control all the slave units It is convenient to place the master unit in an easy to operate location Use the connecting cables to connect between boards and the power signal cables to connect the PCR LEs Arrange the PCR LEs so that they are as...

Page 3: ... J4 connectors are on the rear panel Insert the cable firmly into the connectors until the are locked in place PCR LE Power signal cable Power signal cable Power signal cable Master unit Slave unint Slave unit Example of three PCR LEs parallel control J2 J4 J1 J3 J2 J4 J1 J3 J2 J4 J1 J3 Locking tab Connect for J1 J2 connector Connect for J3 connector Locking tab Connect for J4 connector Locking ta...

Page 4: ...n an Emergency In an emergency turn OFF all POWER switches To Stop Synchronization Set the POWER SELECTOR switches of all PCR LEs to MASTER Operation Check Check the operation of the PCR LE series before you connect the load Check the following items with no load connected For detail of settings see the PCR LE series operation manual POWER switch ON Voltage setting OUTPUT ON OFF Voltage range swit...

Page 5: ...om the master unit The master unit displays the total output current of the system For details of settings see the operation manual included with the PCR LE series The screen captures used in the PCR LE series operation manual are examples They may differ from the screens that are displayed when you are setting parallel operation To Stop master slave parallel operation To quit master slave paralle...

Page 6: ...对环境污染 人身 财产产生重大的影响 产品的废弃请遵守有关规定 产品的制造年月可以在以下网址中确认 http www kikusui co jp pi 毒有害物质或元素名称及含有标示 Name of hazardous materials and symbol of elemet in the equipment and quantity 有毒有害物质或元素 铅 Pb 汞 Hg 镉 Cd 六价铬 Cr VI 多溴联苯 PBB 多溴二苯醚 PBDE 本表格依据 SJ T 11364 的规定编制 该部件所有均质材料的有毒有害物质的含量不超过 GB T 26572 标准所规定的极 限值要求 该部件至少有一种均质材料的有毒有害物质的含量超过 GB T 26572 标准所规定 的极限值要求 ...