P/N 10-4221-501-3KZA-04 • ISS 18JUN20
KZ715AS Mounting Base with Sounder
Installation Sheet
EN CS ES FR IT PL PT
1
2
4
3
EN: Installation Sheet
Description
The KZ715AS five-contact mounting base with sounder is for
use with Kilsen addressable fire alarm control panels. It is
designed for indoor use only.
Installation
Caution:
This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any other
applicable local authority laws.
Electrical connections
Connect the mounting base as shown in Figure 1. An earth
connection is required.
Addressing
Each device requires a numeric address between 128 and 252
for identification purposes. This is set using DIP switches 1-7
(see page 12).
Acoustic output
Adjust the acoustic output of the siren using DIP switch 8, as
shown below.
Acoustic output
DIP switch 8
Low
ON
See Figure 2
High
OFF
See Figure 3
Installing the detector
To install the detector, insert it into the base and rotate it
clockwise until it locks into place (Figure 4).