This unit should be fitted by a qualified electrician in accordance with the appropriate

national/IEE wiring regulations. Switch off mains supply before installation and maintenance.

This product must not be modified. Any modification will negate any Safety Mark Approvals and

may render the product unsafe. GreenBrook accepts no responsibility for modified products. 

This product must be installed in accordance with these instructions. This fitting should not be

installed in close proximity to any external source of heat or covered with any heat insulating

material, air flow around the fitting should not be restricted. Note any minimum distances to

adjacent surfaces. This unit should be connected to the lighting supply circuit, or fused at a

maximum of 

5

A.

This unit is a non-maintained (NM suffix), self-contained emergency luminaire.

To confirm model type, check the data provided on the fitting and packaging.

ELTSLED

65

NM

Non-maintained:

Incorporates two 

54

LED lamps which are 

illuminated only under mains failure conditions

SAFETY

GENERAL DESCRIPTION

INSTALLATION INSTRUCTIONS

EMERGENCY LUMINAIRE TEST RECORD SHEET

LUMINAIRE TYPE/REF:_________________________________

DATE OF INSTALLATION:_______________________________

LOCATION:________________________

Is

s

u

e

 n

o

7

0

3

7

4

9

PLEASE KEEP THESE INSTRUCTIONS SAFE FOR FUTURE REFERENCE

Month

Test

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

FUNCTIONAL

THREE HOUR

1

st Year

2

nd year

3

rd year

4

th year

5

th year

1

2

3

4

5

6

7

8

9

10

11

12

Signed

Signed

Signed

Signed

Signed

Date

Date

Date

Date

Date

 Installation / Operating 

Instructions for ELTSLED

65

NM

WEST  ROAD  .  HARLOW

ESSEX  .  CM

20  2

BG  .  UK

s a l e s @ g r e e n b r o o k . c o . u k

W W W . G R E E N B R O O K . C O . U K

Follow these instructions carefully to ensure safe and reliable operation. Retain this leaflet for 

future reference. The emergency luminaire should be connected to a stable and permanent

mains supply of the correct rated voltage and frequency as stated on the product specification

label. This may be from the lighting supply circuit, or fused at a maximum of

5

A. To facilitate 

testing a fused spur box can be included in the unswitched permanent live supply.

Class I. This product must be earthed.

All switching etc, shall comply with BS

5266 

Part

1. 

Unless specifically permitted, emergency

luminaires should not be connected or controlled by any energy management device. 

Before commencing installation, ensure that the electricity supply is disconnected. Surge

suppressors may be required at the point of connection to the supply wiring when installing

luminaires to MICC cable.

1

. Undo the four cover retaining screws and remove the front cover.

2

. Select and remove a knock out corresponding with the conduit and / or cable run and secure 

a suitable bush within the hole to prevent damage to the incoming cable.

3

. Mount the case in position on a suitable surface ensuring an adequate airflow will be 

maintained around it, or secure to wall using the four hole dimensions on the back case.

Routine Inspection & Test Procedure

All tests should be undertaken during daylight hours at times of minimum risk and be in accordance with

the recommendations of BS 

5266

Part 

1

2005

.

DAILY -

Check that the three green LED battery charging / lamp failure indicators are illuminated.

MONTHLY -

In addition to the daily check, a functional test through simulation of mains supply failure

should be carried out to confirm lamps are illuminated from the battery cell pack supply. This test need only

be approximately 

30

seconds. It should not exceed one quarter of the rated 

luminaire duration.

SIX - MONTHLY -

In addition to the monthly test, the lamps should be illuminated from the battery cell

pack supply for a continuous period of at least one hour.

THREE - YEARS - 

In addition to the monthly tests the lamps should be illuminated from the battery cell

pack supply for the full rated duration of the luminaire. (

180

minutes).

ANNUALLY THEREAFTER - 

As above, i.e, Check that the luminaire operates for the full rated duration (

180

minutes).

At the end of each test period the mains supply should be restored and a check made to ensure that all

three green LED battery charging/lamp failure indicators are illuminated.