background image

CTC-4001/4004 

Installation Guide

Installation Guide

3-Way, Switching, Duct Thermostat

CTC-4001/4004

 

 

 

Mounting

1.   Drill a 5/8" diameter hole in the duct work.
2.   Insert the thermostat in the duct.
3.   Secure with sheet metal screws fastened through 

the two 3/16" (5 mm) mounting holes.

Connections

General

The CTC-4001 and CTC-4004 are not snap-acting. 

The unit must be below or above the setpoint range 

to completely switch. At temperatures within the 

setpoint range, all three ports are connected.

The setpoint adjustment allows ranges to be moved 

up 5° F or down 10° from the default values.
The CTC-4001 and CTC-4004 use 1/4" (6 mm) OD 

polyethylene tubing for all connections. Make neces-

sary connections based on the model.

CTC-4001

•  Port C is the (filtered) common
•  Port A is closed above 75° F (24° C)
•  Port B is closed below 70° F (21° C)
NOTE:  For the CTC-4001, when temperature 

is 

below

 70° F (21° C), ports A and C 

are connected, but B is blocked. When 

temperature is 

above

 75° F (24° C), ports 

B and C are connected, but A is blocked. 

Between 70 and 75° F, all ports are 

connected.

CTC-4004

•  Port C is the (filtered) common
•  Port A is closed above 70° F (21° C)
•  Port B is closed below 65° F (18° C)
NOTE:  For the CTC-4004, when temperature 

is 

below

 65° F (18° C), ports A and C 

are connected, but B is blocked. When 

temperature is 

above

 70° F (21° C), ports 

B and C are connected, but A is blocked. 

Between 65 and 70° F, all ports are 

connected. 

Mounting 

1

Connections 

1

General 

1

CTC-4001 

1

CTC-4004 

1

Adjustments and Calibration  2
Maintenance 

2

Sample Application  2
Important Notices  2

Reviews: