background image

 
VariTrans® P 27000-S008 
Universal Isolators 

TA-251.101-KNE01   20111128

Read these instructions before using the product and retain for future information.

Summary of Contents for P 27000 H1-S008

Page 1: ...VariTrans P 27000 S008 Universal Isolators TA 251 101 KNE01 20111128 Read these instructions before using the product and retain for future information ...

Page 2: ...ecting it from each operating energy supply source The disconnecting means shall disconnect all current carrying conductors It must be easily accessible and clearly identifiable by the operator Mains supply must be protected by a fuse of 20 A max Caution Be sure to take protective measures against electrostatic discharge ESD when handling the devices The warning symbol on the device exclamation po...

Page 3: ...mponents may impair suitability for Class I Division 2 For the use in hazardous locations this equipment is to be installed into suitable enclosure providing a degree of protection not less than IP 54 Devices containing user accessible switches and or potentiometers the device must be installed into an end use enclosure with tool removable cover Conditions for safe use Haz Loc ...

Page 4: ...ns of the broad range mains adapter the units can be powered by voltages from 20 to 253 V AC DC Connection is made using pluggable screw clamp terminals Warning against misuse Do not operate the device outside the conditions specified by the manufacturer as this might result in hazards to operators or malfunction of the equipment 3 Configuration 3 1 Tools A screwdriver with a width of 2 5 mm is re...

Page 5: ...t of the housing and the electronics section until they lock 3 3 Settings Adjust the output range using DIP switches S1 S2 and S3 as shown in the tables or on the rating plate Input Output S1 S2 S3 1 X 1 2 3 4 5 1 2 3 0 200 V 0 10 V OFF OFF OFF OFF ON ON ON ON ON OFF 0 200 V 0 20 mA ON OFF OFF OFF ON ON ON OFF OFF OFF ...

Page 6: ...g torque 0 7 Nm Wiring has to be suitable for a temperature of min 75 C 4 Mounting The universal isolators are mounted on standard TS 35 rails 5 Electrical Connection Warning For applications with high working voltages take measures to prevent accidental contact and make sure that there is sufficient distance or insulation between adjacent devices 5 1 Power supply 22 to 230 V AC DC 10 0 9 W AC 48 ...

Page 7: ...7 6 Dimensions Metal lock for fastening on top hat rail Fixed screw clamp terminals 111 99 ...

Page 8: ...onformity is included in the documentation The Statement of Conformity for ATEX Zone 2 apparatus is included in the documentation GL Certificate No 42 843 02 HH Environmental Category D Test Standard Regulations of the Performance of Type Tests Part 1 EN 61010 1 8 Order Information Adjustable Device Order No Pluggable screw clamp terminals P 27000 S008 Universal Isolator P 27000 H1 S008 ...

Page 9: ...al data Gain error 0 08 meas value typical additional error for AC 45 65 Hz sinus 0 05 meas value Temperature coefficient2 50 ppm K of final value Cutoff frequency approx 20 kHz Test voltage 5 kV input against output 4 kV output against power supply Working voltage3 basic insulation 1 kV for overvoltage category II and pollution degree 2 to EN 61010 1 For applications with high working voltages ta...

Page 10: ...tance to adjacent devices or sufficient insulation between them EMC4 2004 108 EC EN 61326 EN 61326 A1 Surge withstand 5 kV 1 2 50 μs to IEC 255 4 Ambient temperature Operation Transport and storage 10 to 70 C 40 to 85 C Ambient conditions Stationary application weather protected Relative air humidity 5 95 no condensation Barometric pressure 70 106 kPa altitude up to 2000 m Water or wind driven pre...

Page 11: ... GRP A B C D T4 1 Higher output load on request 2 Average TC in specified operating temperature range 10 C 70 C 3 cULus certification Working voltage basic insulation up to 600 V working voltage reinforced insulation up to 300 V across input and output each for overvoltage category II and pollution degree 2 4 Slight deviations are possible while there is interference ...

Page 12: ...12 Knick Elektronische Messgeräte GmbH Co KG Beuckestraße 22 D 14163 Berlin Phone 49 0 30 801 91 0 Fax 49 0 30 801 91 200 Internet http www knick de Email knick knick de ...

Reviews: